Local Configuration
Local configuration is normally not required and should only be carried out when
necessary. Please read the instructions below carefully.
The built-in web interface is primarily intended for informational purposes and troubleshooting.
Netbiter Argos is always the preferred way of configuring the gateway. The only configuration
changes that should be made using the local web interface are:
•
Proxy settings (if required)
•
Modem/Ethernet connection mode (EC350 only)
•
Firmware updates
3.1
Connecting via USB
Connect a USB Micro B cable between the computer and the
USB
port on the Netbiter.
The USB device driver will automatically load and create a virtual network interface on the com-
puter with an IP address in the range 169.254.200.xxx. The local web interface of the gateway
can then be accessed by entering the IP address
169.254.200.200
in a web browser.
Fig. 20
Network Connections
3.2
Connecting via Ethernet
Connect an Ethernet cable between the computer and the
LAN
port on the Netbiter.
The default IP address of the LAN port interface is
10.200.1.1
. The connecting computer must
have an IP address within the same subnet (10.200.1.xxx). The LAN IP address can be
changed after logging in or from Netbiter Argos when the Netbiter is online.
3.3
Login
Enter the IP address of the gateway in a web browser to log in. The default user name is
admin
,
and the password is the activation code that was supplied with the unit.