25 (42)
5.2
Basic Settings
For more detailed explanations of each configuration setting, see the help texts in the
Information Window.
5.2.1
Project
Used to store project information such as project name, project creator, version and description.
5.2.2
Network Settings
General
During startup the fieldbus interface is initialized to fit the configuration created in Anybus
Configuration Manager. Some initialization parameters can optionally be set manually to provide
better control over how the data shall be treated by the Anybus Communicator CAN.
Network Type
The higher level network type must be selected here in order to create a valid configuration.
5.2.3
Communicator Settings
Additional settings for the Anybus Communicator CAN.
General
Parameter
Comment
Control/Status Word
If enabled, the Control/Status Word will occupy the first two bytes of the Output/Input
areas of the memory.
To avoid memory address collisions this parameter should be enabled
before
adding
frames to the configuration.
Start-up Operation Mode
Decides the start-up mode of the CAN subnetwork if the Control Word is enabled.
Transaction Live List
If the Transaction Live List is enabled it is mapped from the beginning of the input area
or, if the Control/Status Word is enabled, after the Status Word. It is possible to map
from 8 to 128 transactions, in steps of 8. Each transaction is represented by a bit that
tells the system whether the transaction is alive or not.
Statistics
Parameter
Comment
Counters
The receive counter and the transmit counter count successful CAN messages on the
subnetwork. If enabled, the counters can be mapped to the input data area. The first
free address in the input data area is selected by default. The counters can be disabled
and enabled separately.
To avoid memory address collisions this parameter should be enabled
before
adding
frames to the configuration.
The messages are counted only if they have been configured in Anybus Configuration
Manager.
Receive Counter Address
Enter the address in the input data area where the receive counter shall be mapped. The
receive counter occupies 2 bytes.
Transmit Counter Address
Enter the address in the input data area where the transmit counter shall be mapped.
The transmit counter occupies 2 bytes.
Fatal Event
Parameter
Values
Comment
Action
Stay in Safe-State
In case of a fatal software event, the Anybus Communicator
CAN will be locked in the safe state.
Software Reset
In case of a fatal software event, the software will be reset and
the Anybus Communicator CAN will be restarted.
Anybus
®
Communicator
™
CAN PROFINET
®
IRT (2.32) User Manual
SCM-1202-035 1.2 en-US