  Set-up procedure 

 
1.  Install Intesis MAPS on your laptop, use the setup program supplied for this and follow the instructions given by 

the Installation wizard. 

 
2.  Install Intesis in the desired installation site. Installation can be on DIN rail or on a stable not vibrating surface 

(DIN rail mounted inside a metallic industrial cabinet connected to ground is recommended). 

 
3.  If using BACnet IP, connect the communication cable coming from the BACnet IP network to the port marked as 

Ethernet on Intesis (More details in section 6.4). 

 

If using BACnet MSTP, connect the communication cables coming from the BACnet MSTP network to the port 
marked as Port A on Intesis (More details in section 6.4). 

 
4.  Connect the communication cable coming from PROFINET network to the port marked as Port C of Intesis (More 

details in section 6.4). 

 
5.  Power up Intesis. The supply voltage can be 9 to 30 Vdc. Take care of the polarity of the supply voltage applied. 
 

WARNING!

 In order to avoid earth loops that can damage Intesis and/or any other equipment connected to 

it, we strongly recommend:  
 

 

The use of DC power supplies, floating or with the negative terminal connected to earth. 

Never use a 

DC power supply with the positive terminal connected to earth

.  

 
6.  If you want to connect using IP, connect the Ethernet cable from the laptop PC to the port marked as Ethernet

 

of 

Intesis (More details in section 6.4)
 
If you want to connect using USB, connect the USB cable from the laptop PC to the port marked as Console

 

of 

Intesis (More details in section 6.4). 

 
7.  Open Intesis MAPS, create a new project selecting a template of the one named 

INBACPRT---0000

 
8.  Modify  the  configuration  as  desired, save  it  and  download  the  configuration  file  to  Intesis  as  explained  in  the 

Intesis  MAPS  user  manual.  Remember  to  activate  HICP  to  configure  network  settings  of  the  PROFINET 
interface. 

 

9.  Connect the Ethernet cable from the laptop PC to the PROFINET network and open HMS IPConfig tool, then 

modify settings as desired and validate new configuration by clicking 

Set

 
10.  Visit the Diagnostic section, on Intesis MAPS, and check that there is communication activity, some TX frames 

and some other RX frames. This means that the communication with the BACnet master device and PROFINET 
IO  Controller  is  OK.  In  case  there  is  no  communication  activity  between  Intesis  and  the  BACnet  and/or 
PROFINET devices, check that those are operative: check all communication parameters and connection of all 
devices. 

 

 
 

 
 

 

 

Содержание Intesis BACnet

Страница 1: ...BACnet Server PROFINET IO Device USER MANUAL Issue date 05 2020 r1 0 ENGLISH...

Страница 2: ...s and are only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the many variabl...

Страница 3: ...0 eng HMS Industrial Networks S L U All rights reserved This information is subject to change without notice URL https www intesis com 3 46 Gateway to connect BACnet MSTP or BACnet IP installations wi...

Страница 4: ...2 2 Analog Input Object Type 17 5 2 3 Analog Output Object Type 18 5 2 4 Analog Value Object Type 19 5 2 5 Binary Input Object Type 20 5 2 6 Binary Output Object Type 21 5 2 7 Binary Value Object Typ...

Страница 5: ...rial Networks S L U All rights reserved This information is subject to change without notice URL https www intesis com 5 46 9 2 5 Sending the configuration to Intesis 42 9 2 6 Diagnostic 42 Set up pro...

Страница 6: ...sed control systems or devices merging both systems into one The gateway acts as a BACnet IP Server or BACnet MSTP device in its BACnet interface allowing other BACnet devices to perform subscription...

Страница 7: ...ct has active subscriptions the new value will be sent to the subscripted BACnet device s From the BACnet system point of view after the start up process the gateway listens to any subscription COV re...

Страница 8: ...L BACnet Operator Workstation B OWS BACnet Building Controller B BC BACnet Advanced Application Controller B AAC BACnet Application Specific Controller B ASC BACnet Smart Sensor B SS BACnet Smart Actu...

Страница 9: ...t all routing configurations e g ARCNET Ethernet Ethernet MS TP etc Annex H BACnet Tunneling Router over IP BACnet IP Broadcast Management Device BBMD Does the BBMD support registrations by Foreign De...

Страница 10: ...DS COVP A Data Sharing COVP A SubscribeCOVProperty ConfirmedCOVNotification UnconfirmedCOVNotification DS COVP B Data Sharing COVP B SubscribeCOVProperty ConfirmedCOVNotification UnconfirmedCOVNotific...

Страница 11: ...ends Inernal B ReadRange T VMT E B Trending Viewing and Modifying Trends External B ReadRange T ATR A Trending Automated Trend Retrieval A ConfirmedEventNotification ReadRange T ATR B Trending Automat...

Страница 12: ...onfirmedTextMessage DM TS A Device Management TimeSynchronization A TimeSynchronization DM TS B Device Management TimeSynchronization B TimeSynchronization DM UTC A Device Management UTCTimeSynchroniz...

Страница 13: ...Access Services AddListElement RemoveListElement CreateObject DeleteObject ReadProperty ReadPropertyConditional ReadPropertyMultiple ReadRange WriteProperty WritePropertyMultiple Remote Device Managem...

Страница 14: ...orted are shown in the table below Object Type ID Supported Management Point Analog Input 0 Analog Output 1 Analog Value 2 Averaging 18 Binary Input 3 Binary Output 4 Binary Value 5 Calendar 6 Command...

Страница 15: ...ing O Protocol_Version Unsigned 1 R R Protocol_Revision Unsigned 14 R R Protocol_Services_ Supported BACnetServiceSupported Refer to section 4 Service Types R R Protocol_Object_Types_ Supported BACnet...

Страница 16: ...OV_ Subscriptions List of BACnetCOVSubscription List of BACnetCOVSubscription O R Slave_Proxy_Enable BACnetArray N of BOOLEAN O Manual_Slave_Address_ Binding List of BACnetAddressBinding O Auto_Slave_...

Страница 17: ...FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIABLE_OTHER 7 O R Out_Of_Service BOOLEAN FALSE R R Update_Interval Unsigned O Un...

Страница 18: ...0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Update_Interval Unsigned O Units BACnetEngineeringUnits Configurable through BACnet and Config Tool R R Min...

Страница 19: ...ALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Update_Interval Unsigned O Units BACnetEngineeringUnits...

Страница 20: ...RMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIABLE_OTHER 7 O R Out_Of_Service BOOLEAN FALSE R R Polarity BACnetPolarity NORMAL 0 R R Inactive_Text CharacterString Configurable thr...

Страница 21: ...ce BOOLEAN FALSE R R Polarity BACnetPolarity NORMAL 0 R R Inactive_Text CharacterString Configurable through BACnet and Config Tool O R Active_Text CharacterString Configurable through BACnet and Conf...

Страница 22: ...ity BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Inactive_Text CharacterString Configurable through BACnet and Config Tool O R Active_Text CharacterString Configurable th...

Страница 23: ...String O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIABLE_OTHER 7 O R Out_Of...

Страница 24: ...us_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Number_Of_...

Страница 25: ...racterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN F...

Страница 26: ...Object Type Property Identifier Property Datatype Value ASHRAE IBOX Object_Identifier BACnetObjectIdentifier Calendar 6 R R Object_Name CharacterString Configurable through BACnet and Config Tool R R...

Страница 27: ...ailySchedule R W Exception_Schedule BACnetARRAY N of BACnetSpecialEvent R W Schedule_Default Any R W List_Of_Object_Property_Refer ences BACnetLIST of BACnetDeviceObjectProper tyReference R R Priority...

Страница 28: ...ty Datatype Value ASHRAE IBOX Object_Identifier BACnetObjectIdentifier Notification_Class 15 R R Object_Name CharacterString Configurable through BACnet and Config Tool R R Object_Type BACnetObjectTyp...

Страница 29: ...g_Interval Unsigned O COV_Resubscription_Interval Unsigned O Client_COV_Increment BACnetClientCOV O Stop_When_Full BOOLEAN R R Buffer_Size Unsigned R R Log_Buffer List of BACnetLogRecord R R Record_Co...

Страница 30: ...ropertyReference O R Log_Interval Unsigned O COV_Resubscription_Interval Unsigned O Client_COV_Increment BACnetClientCOV O Stop_When_Full BOOLEAN R R Buffer_Size Unsigned R R Log_Buffer List of BACnet...

Страница 31: ...the network is automatically scanned for Intesis BACnet PROFINET modules The network can be rescanned at any time by cliking Scan To change the network settings of a BACnet PROFINET module double clic...

Страница 32: ...rt 80 The default web pages provide access to Network configuration parameters Network status information Access to the host application ADIs The network configuration page provides interfaces for cha...

Страница 33: ...n unicast packets broadcast and multicast Out Discards Outgoing packets discarded due to no available memory buffers Out Errors Transmission errors Media Counters Description Alignment Errors Frames r...

Страница 34: ...y Client MRC It also supports propagating link change to the Media Redundancy Master LED Indicators Network Status LED LED1 LED state Status Comments Off Offline No connection with IO controller Green...

Страница 35: ...sure traffic on the port used is allowed through all the LAN path check the gateway user manual for more information With factory settings after powering up the gateway DHCP will be enabled for 30 se...

Страница 36: ...ect a mini type B USB cable from your computer to the gateway to allow communication between the Configuration Software and the gateway Remember that Ethernet connection is also allowed Check the user...

Страница 37: ...tive and reachable from the network connection used by Intesis Check the Intesis Ethernet interface sending Pings to its IP address using a PC connected to the same Ethernet network Check as well with...

Страница 38: ...ice in a line topology either Port 1 or Port 2 can be used The cable to be used shall be a straight Ethernet UTP FTP CAT5 cable PROFINET interface contains a dual port Ethernet switch they both operat...

Страница 39: ...Tx Rx Expansion Module communication Off There is no activity on this port Tx Blinking green Every data packet sent to Expansion module it blinks Rx Blinking yellow Every data packet received from Ex...

Страница 40: ...to download the configuration tool USB Console cable to communicate with gateway Product documentation Intesis MAPS Configuration monitoring tool for Intesis BACnet series 9 2 1 Introduction Intesis M...

Страница 41: ...e subsets of information are shown in this window General Gateway general parameters BACnet Server BACnet interface configuration and PROFINET interface parameters Figure 9 2 Intesis MAPS configuratio...

Страница 42: ...e Intesis Communication Console window Intesis will reboot automatically once the new configuration is loaded Figure 9 4 Intesis MAPS Receive Send tab After any configuration change do not forget to s...

Страница 43: ...ng HMS Industrial Networks S L U All rights reserved This information is subject to change without notice URL https www intesis com 43 46 Figure 9 5 Diagnostic More information about the Diagnostic se...

Страница 44: ...nected to it we strongly recommend The use of DC power supplies floating or with the negative terminal connected to earth Never use a DC power supply with the positive terminal connected to earth 6 If...

Страница 45: ...3 poles Positive Negative Earth 24VDC 10 Max 580mA Push Button Button A Check section 8 Button B Check section 8 Operation Temperature 0 C to 60 C Ethernet 1 x Ethernet 10 100 Mbps RJ45 2 x Ethernet...

Страница 46: ...reserved This information is subject to change without notice URL https www intesis com 46 46 11 Dimensions Recommended available space for its installation into a cabinet wall or DIN rail mounting w...

Отзывы: