Media Redundancy Protocol (MRP)
Media Redundancy Protocol (MRP) is a PROFINET specific ring protocol ensuring redundancy in the network, which
can significantly decrease network downtime. It is a token-based ring protocol with a master-slave hierarchy.
All the nodes in the PROFINET network part of the ring are connected using ring topology (that is, the last node is
connected directly to the first node). If, at any point, the connection between two nodes would break, the data will
flow the other way instead, guaranteeing that data can be sent to/from the IO Controller to the IO Device(s). The self-
healing time is approximately 200 ms.
The Media Redundancy Master (MRM) is responsible for checking the functional capability of the ring network, by
sending out cyclic tokens. The Media Redundancy Clients (MRC) basically work as switches that pass on the tokens.
The Intesis gateway supports acting as a Media Redundancy Client (MRC)
. It also supports propagating link
change to the Media Redundancy Master.
LED Indicators
Network Status LED (LED1)
LED state
Status
Comments
Off
Offline
No connection with IO controller
Green
Online (RUN)
Connection with IO controller
established, IO controller in Run state
Green, 1 flash
Online (STOP)
Connection with IO controller
established, IO controller in Stop state
or IO data bad.
Green, blinking (1Hz)
Blink (DCP_Identify)
Used by engineering tools to identify the
node on the network.
Red
Fatal event
Major internal error (this indication is
combined with a red module status LED)
Red, 1 flash
Station name error
Station name not set
Red, 2 flashes
IP address error
IP address not set
Red, 3 flashes
Configuration error
Expected identification differs from Real
identification.
Module Status LED (LED2)
LED state
Status
Comments
Off
Not Initialized
PROFINET interface not initialized.
Green
Normal Operation
PROFINET interface initialized.
Red
Exception error
Module in state Exception
Fatal event
Major internal error (this indication is
combined with a red module status LED)
Alternating Red/Green
Firmware Update
Do NOT power off the module. Turning
the module off during this phase could
cause permanent damage.
7.
Connections
Find below information regarding the Intesis connections available.