HKC CPT-01-A Скачать руководство пользователя страница 5

CPT Current Position Transmitter 

Installation Operation& Maintenance Manual 

Doc No. : HumG-CPT-20 Rev0 

Page  5 / 6 

Valve Automation Leader, HKC 

8.2.

 

Using L-wrench, loosen clamp bolts on cam. And rotate CLS cam clock wise or counter clock wise until 
switch lever arm rides on the curved portion of the cam. Then tighten fixing bolt by using L-wrench. 
(Actuator can go further toward closed position as CLS cam is rotated toward CCW like below picture). 

8.3.

 

Rotate actuator and/or damper to open position. And rotate OLS cam clock wise or counter clock wise 
until switch lever arm rides on the curved portion of the cam. Then tighten fixing bolt by using L-wrench. 
(Actuator can go further toward closed position as OLS cam is rotated toward CW like below picture) 

 

9. 

Maintenance 

9.1.

 

Test operation in regular: You’d better do test operation in regular (once a week). And please always 
supply electric power even though actuator and valve are not used for more than a month. 

9.2.

 

Periodical maintenance: Periodical check and maintenance is necessary for long term operation. You 
should do overhaul check at least once a year and do maintenance immediately if required. 

9.3.

 

General manual: This manual is mainly for CPT card. So, please refer to HQ series IOM manual if you 
need more detailed information. 

 

10. 

CPT card layout 

 CPT Card (CPT4-TR V1.2) 

 

 

Содержание CPT-01-A

Страница 1: ...umG CPT 20 Rev0 Page 1 6 Valve Automation Leader HKC Current Position Transmitter Installation Operation Maintenance Manual Address 26 Emtibeui 28 ro Siheung si Gyeonggi do 15119 Republic of Korea Tel 82 31 488 8266 Fax 82 31 488 8269 Home page www hkcon co kr email hkcon hkcon co kr ...

Страница 2: ...rpose 3 1 2 Safety Notices 3 2 Pre check points before operation 3 2 1 Check point 3 3 General concept 3 3 1 General information 3 3 2 Standard specification 3 4 Main function and how to use Zero Span setting 3 5 Tools of adjustment 4 6 How to set for normal open actuator 4 7 How to set potentiometer 4 8 How to set limit switches 4 9 Maintenance 5 10 CPT card layout 5 ...

Страница 3: ... of the actuator s installation and operation 2 Pre check points before operation 2 1 Check point 2 1 1 User should confirm if actuator and valve are assembled correctly and firmly 2 1 2 And check limit switches stopper bolts indicator setting 2 1 3 Please check electric power input and output signal and wiring and etc 2 1 4 In case electric power is 3 phases you must check Rotating direction of a...

Страница 4: ...means that you need to change direction of the actuator from clock wise close type It is same means counter clock wise open type 6 1 Open top cover of the actuator using Allen key 6 2 Cross change wiring of P1 P3 Red Black where connected to Potentiometer in CPT card 6 3 Change wiring of No 9 No 10 first and No 11 No 12 in Terminal block 6 4 Change direction of Position indicator 6 5 Move indicato...

Страница 5: ...ever arm rides on the curved portion of the cam Then tighten fixing bolt by using L wrench Actuator can go further toward closed position as OLS cam is rotated toward CW like below picture 9 Maintenance 9 1 Test operation in regular You d better do test operation in regular once a week And please always supply electric power even though actuator and valve are not used for more than a month 9 2 Per...

Страница 6: ... PIU is fault Check resistance value CPT card is damaged Replace a new one produced by the maker Torque switch fails to stop of the valve travel in correct position Valve or Damper torque value is higher than the actuator Change actuator that has enough torque for valve or damper torque Corrosion or some materials of valve increase required operation torque of the valve Check the valve and repair ...