APL-9 Series Limit Switch Box
Installation Operation & Maintenance Manual
Doc No. : HumG-APL9-21 Rev0
Page 4 / 10
Valve Automation Leader HKC
L :
SUS316L & SUS316 Stainless Steel
UN :
SUS304 Stainless Steel + PDC coating
UL :
SUS316L & SUS316 Stainless Steel + PDC coating
○
4
Bracket type
S :
80X30 H20, 80X30 H30,
O :
80X30 H20, 80X30 H30, 130X30 H30, 130X30 H40, 130X30 H50
S :
80X30 H20, 80X30 H30,
O :
80X30 H20, 80X30 H30,
130X30 H30, 130X30 H40, 130X30 H50
4.
Standard and Optional Specification
Model
APL-9..N
Enclosure Rated
Weather proof IP67 (Standard), Watertight IP68 2m 72hr (Option)
Enclosure Material
Press-formed stainless steel
Ambient Temperature
-20 ℃ ~ + 80 ℃ (Standard)
-50 ℃ ~ + 80 ℃ (Option for Low Temperature)
-40 ℃ ~ + 110 ℃ (Option for High Temperature)
Cable Entries
Standard: Two NPT1/2”
Option: Two M20, PG13.5, PF1/2”
Travel Angle
90 /- 10%
Position Indicator
Open-Yellow, Close-Red
Language : English (option : French, German)
Terminal Strip
8 point (option : 10P)
External Coating
Standard : No coating
Option : Dry powder polyester, PDC coating
5.
Marking
5.1.
Cover front
5.1.1.
HKC & CE Logo
5.1.2.
Model
5.1.3.
Micro Switches type
5.1.4.
Bar code
5.2.
Cover inside
5.2.1.
Wiring diagram