background image

Copyright HK Instruments 2021

www.hkinstruments.fi

Installation version 1.0 2021

INSTALLATION

INSTRUCTIONS

Indoor air quality transmitters

Siro-MOD series

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING 

TO INSTALL, OPERATE OR SERVICE THIS DEVICE.

•  Failure to observe safety information and comply with instructions 

can result in PERSONAL INJURY, DEATH AND/OR PROPERTY 

DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect 

power before installing or servicing and use only wiring with 
insulation rated for full device operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially 

flammable or explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered system 

whose specifications and performance characteristics are not 
designed or controlled by HK Instruments. Review applications 
and national and local codes to assure that the installation will 
be functional and safe. Use only experienced and knowledgeable 
technicians to install this device.

Thank you for choosing an HK Instruments Siro-MOD series indoor air 

quality transmitter. The Siro-MOD series transmitters are intended for 
use in building automation systems in the HVAC/R industry.

Siro-MOD is an indoor air quality transmitter with a modern design. The 

transmitter  is  available  with  several  optional  air  quality  sensors.  The 

modular device can be equipped with CO

2

 concentration and VOC (Vola-

tile Organic Compounds) measurements or alternatively PM (Particulate 

Matter) measurement and in addition temperature and humidity meas-

urements.  It  offers  easy  installation  and  adjustment,  several  different 

model options and various output signals that are configurable separately 
for each measurement parameter.

The Siro-MOD series devices are available with user interface that in-

cludes LCD display and buttons making the configuration of the device 

quick and easy. An external configuration tool is necessary for commis-

sioning  preparations  for  Siro-MOD  without  user  interface.  Configura-

tion is also possible via Modbus network. Siro-MOD utilizes the industry 

standard NDIR measurement principle with self-calibrating ABC logic

TM

 

for CO

2

 measurement.

•  PM concentration to measures the size and amount of particulates

 

in the indoor air for example to assess the performance of air filters

•  temperature and humidity in HVAC/R environment

SPECIFICATIONS

Performance

Measurement ranges:

CO

2

:  

 

 

0–2000 ppm / 400–2000 ppm

  

 

(selectable via jumper)

VOC:    

 

CO₂eq: 400–2000 ppm

 

 

 

TVOC ppm: 0–30.0 ppm

 

 

 

TVOC µg/m

3

: 0–10000 µg/m

3

  

 

IAQ index:  1–5 (UBA rating)

 

PM1/PM2.5/PM10:  0–50 μg/m

³

 / 0–500 μg/m

³

 

 

 

(selectable via jumper)

 

 

 

IAQ index: 1-5 (WHO rating)

Temperature:    

0...50 °C

Relative humidity:  

0–100 %rH

Accuracy:

CO

2

:  

 

 

±30 ppm + 3 % of reading (typical),

 

 

 

additional ±60 ppm for first weeks

VOC*:    

 

15 % of reading (typical)

*VOC sensor is tuned for typical IAQ Mix of 22 VOCs as 
defined by Mølhave et al. (1997)

PM:    

0…100 µg/m3: 

PM2.5:   

 

±15 µg/m³ (at 25 ⁰C ±5 ⁰C)

PM1/PM10*: 

 

±25 µg/m³ (at 25 ⁰C ±5 ⁰C)

100…1000 µg/m3: 

PM2.5:   

 

±15 % (at 25 ⁰C ±5 ⁰C)

PM1/PM10*: 

 

±25 % (at 25 ⁰C ±5 ⁰C)

*PM1 and PM10 values are calculated from PM2.5 
measurement reading with the default particle distribution.

Temperature:    

±0.4 ⁰C (typical at 20 ⁰C)

Relative humidity:  

±2.2 %rH (typical at 20 ºC, 30 %rH)

Technical Specifications

Media compatibility:

Dry air or non-aggressive gases

Measuring units:

CO₂:  

 

 

ppm

VOC:    

 

CO

2

eq: ppm

 

 

 

TVOC: ppm, µg/m

³

PM: 

 

 

PM1/PM2.5/PM10: µg/m

³

Temperature:    

°C/°F

Relative humidity:  

%rH

Measuring element:

CO

2

:

 Non-dispersive infrared (NDIR)

VOC:

 Complementary Metal Oxide 

Semiconductor (CMOS)

PM:

  Laser-based light scattering particle sensing

Temperature:

 Integrated to CMOS

Relative humidity:

 Thermoset polymer capacitive 

sensing element

Calibration:

 

Automatic self-calibration ABC Logic

TM 

for CO

measurement

Environment:

Operating temperature: 0...50 °C

Storage temperature: -20...70 °C

Humidity: 0 to 95 %rH, non condensing

Physical

Dimensions:  

Case: 95 x 103 x 30 mm

(width x height x depth)

Weight: 

130 g

Mounting:

2 screw holes slotted, distance c/c 60 mm

Materials:

Case: ABS

Protection standard: 

IP20

Display (optional)

Monochrome LCD, 38 x 23 mm

Electrical connections:

  

10-pin spring loaded terminal block

0.2...1.5 mm² (16-24 AWG)

Electrical

Input:

 24 VAC or VDC, ±10 %

Power consumption: 2 W max + 25 mW for each 

voltage output or 50 mW for each current output

Outputs: 

4 outputs, have to select voltage or current

Voltage outputs:

 

0–10 V

 

2–10 V / 0–5 V (optional, display or   

 

configuration tool required)

Current output:

 

4–20 mA (optional)

Output signal limits:

 

Voltage outputs: R > 1 kΩ

 

Current output: R > 20 Ω, R < 500 Ω

Communication

Protocol: MODBUS over Serial Line

Transmission Mode: RTU

Interface: RS485

Byte format 11 bits (10 bits if parity none):

           Coding System: 8-bit binary

           Bits per Byte:

 

  1 start bit

 

  8 data bits, least significant bit sent first

 

  1 bit for parity

 

  1 stop bit

Baud rate: selectable in configuration

Modbus address: 1−247 addresses selectable in

configuration menu

Conformance

Meets requirements for CE marking:

EMC Directive 2014/30/EU

RoHS Directive 2011/65/EU

WEEE Directive 2012/19/EU

INTRODUCTION

APPLICATIONS

WARNING

Siro-MOD series devices are commonly used to monitor and control:

•  indoor air quality in offices, public spaces, meeting rooms and 

classrooms

•  CO

2

 and VOC concentration to regulate demand-controlled 

ventilation and to keep the indoor air quality in a good level

COMPANY WITH

MANAGEMENT SYSTEM

CERTIFIED BY DNV GL

= ISO 9001 = ISO 14001 =

RoHS 2

2011/65/EU

Содержание Siro-MOD Series

Страница 1: ...A rating PM1 PM2 5 PM10 0 50 μg m 0 500 μg m selectable via jumper IAQ index 1 5 WHO rating Temperature 0 50 C Relative humidity 0 100 rH Accuracy CO2 30 ppm 3 of reading typical additional 60 ppm for first weeks VOC 15 of reading typical VOC sensor is tuned for typical IAQ Mix of 22 VOCs as defined by Mølhave et al 1997 PM 0 100 µg m3 PM2 5 15 µg m at 25 C 5 C PM1 PM10 25 µg m at 25 C 5 C 100 100...

Страница 2: ... MODBUS MODULE 4 Pin header Description Open Connected Open Connected CO2 PM output range selection 400 2000 ppm CO2 models 0 2000 ppm CO2 models 0 500 μg m3 PM models 0 50 μg m3 PM models Pin header Description Open Connected Menu lock Menu lock disabled Menu lock enabled 1 2 Connector Description A B RS485 Modbus RTU slave DATA DATA 24 V GND GND Power supply 24 VAC DC 10 Ground Ground 3 Connecto...

Страница 3: ... uncooled areas 2 Use the device as a template and mark the screw holes 3 Mount the wall plate with screws CAUTION Incorrect installation may cause a shift in measurements Figure 1c Mounting location 120 cm 4 ft 180 cm 6 ft 50 cm 20 in 20cm 8in 20cm 8in NOTE When using long connection wires it may be necessary to use a separate GND wire for voltage output current to prevent measurement dis tortion...

Страница 4: ...g the display Install the jumper 2 figure 3 to lock the display to prevent access to the con figuration menu after installation is completed 4 Modbus termination Install a jumper 4 figure 3 to terminate Modbus In order to avoid signal reflections Modbus termination jumper must be installed in case if the device is the last one of the bus Modbus registers continued Register Parameter description Da...

Отзывы: