HK Instruments RHT Series Скачать руководство пользователя страница 2

Copyright HK Instruments 2017

www.hkinstruments.fi

Installation version 5.0 2017

SCHEMATICS

DIMENSIONAL DRAWINGS

INSTALLATION

STEP 1: MOUNTING THE DEVICE

1) Mount the device in the desired location (see step 1).
2) Route the cables and connect the wires (see step 2).
3) The device is now ready for configuration.

 

 WARNING! Apply power only after the device is properly wired.

Figure 1 - Surface mounting

1) Select a mounting location on the wall at 1.2–1.8 m (4–6 ft) 

above the floor and at least 50 cm (20 in) from the adjacent wall. 
Locate the unit in an area with good ventilation and an average 
temperature, where it will be responsive to changes to the room 
conditions. The RHT may be mounted on a flat surface.

Do not locate the RHT where it can be affected by:
•  Direct sunlight
•  Drafts or dead areas behind doors
•  Radiant heat from appliances
•  Concealed pipes or chimneys
•  Outside walls or unheated / uncooled areas

2) Use the device as a template and mark the screw holes.
3) Mount the wall plate with screws.
•  Incorrect installation may cause a shift in temperature output

Display locking

jumper

Jumpers

Contact pins for

relay terminal

Contact pins for

terminal block

Terminal block

Terminal block for relay

99.0

90.0

83.0

49.5

14.0

45.0

18.0

Ø 4.0

32.0

Содержание RHT Series

Страница 1: ...temperature levels in offices public spaces hospitals meeting rooms and classrooms humidity and temperature in various commercial applications humidity and temperature in HVAC R environment SPECIFICATIONS Performance Measurement ranges Temperature 0 50 C Relative humidity 0 100 Accuracy Temperature 0 5 ºC Relative humidity 2 3 at 0 50 C and 10 90 rH Total error band includes accuracy hysteresis an...

Страница 2: ...l Locate the unit in an area with good ventilation and an average temperature where it will be responsive to changes to the room conditions The RHT may be mounted on a flat surface Do not locate the RHT where it can be affected by Direct sunlight Drafts or dead areas behind doors Radiant heat from appliances Concealed pipes or chimneys Outside walls or unheated uncooled areas 2 Use the device as a...

Страница 3: ...ck plate or for surface wiring select a knockout on the top or bottom of the wall plate as shown in Figure 2a 2 Connect the wires as shown in Figure 2b and 2c STEP 3 CONFIGURATION WIRING DIAGRAMS CONTINUED Configuration of the RHT series device consists of 1 Configuring the jumpers see step 4 2 Configuration menu options Display versions only See the user manual for further details Figure 2a Routi...

Страница 4: ...t done by the seller or his her authorized representative The selection of materials for devices prone to corrosion is the buyer s responsibility unless otherwise is legally agreed upon Should the man ufacturer alter the structure of the device the seller is not obligated to make comparable changes to devices already purchased Appealing for warranty requires that the buyer has correctly fulfilled ...

Отзывы: