HK Instruments RHT-MOD Series Скачать руководство пользователя страница 4

Copyright HK Instruments 2021

www.hkinstruments.fi

Installation version 7.0 2021

The seller is obligated to provide a warranty of five years for the deliv-
ered goods regarding material and manufacturing. The warranty period 
is considered to start on the delivery date of the product. If a defect 
in raw materials or a production flaw is found, the seller is obligated, 
when the product is sent to the seller without delay or before expira-
tion of the warranty, to amend the mistake at his/her discretion either 
by repairing the defective product or by delivering free of charge to the 
buyer a new flawless product and sending it to the buyer. Delivery costs 
for the repair under warranty will be paid by the buyer and the return 
costs by the seller. The warranty does not comprise damages caused by 
accident,  lightning,  flood  or  other  natural  phenomenon,  normal  wear 
and tear, improper or careless handling, abnormal use, overloading, im-
proper storage, incorrect care or reconstruction, or changes and instal-
lation work not done by the seller or his/her authorized representative. 
The selection of materials for devices prone to corrosion is the buyer’s 
responsibility, unless otherwise is legally agreed upon. Should the man-
ufacturer alter the structure of the device, the seller is not obligated to 
make comparable changes to devices already purchased. Appealing for 
warranty requires that the buyer has correctly fulfilled his/her duties 
arisen from the delivery and stated in the contract. The seller will give 
a new warranty for goods that have been replaced or repaired within 
the warranty, however only to the expiration of the original product’s 
warranty time. The warranty includes the repair of a defective part or 
device, or if needed, a new part or device, but not installation or ex-
change  costs.  Under  no  circumstance  is  the  seller  liable  for  damages 
compensation for indirect damage.

STEP 5: MODBUS REGISTERS

Register

Parameter description

Data Type

Value

Range

1x0001

Relay status

Bit 0

0...1

0=Off - 1=On

1x0002

Relay trend

Bit 0

0...1

0=Increasing, 1=Decreasing

Function code 02 - Read input status

Register

Parameter description

Data Type

Value

Range

4x0001

Parameter for P-controller

16 bit 

0...3

1=rH, 2=TE, 3=MAX

4x0004

rH high limit

16 bit

100...1000

10.0...100.0 %

4x0005

rH low limit

16 bit

0...900

0.0...90.0 %

4x0006

TE high limit

16 bit

50...500

5.0...50.0 °C

4x0007

TE low limit

16 bit

0...450

0...45.0 °C

4x0008

Parameter for relay

16 bit

0...3

1=rH, 2=TE, (3=Off)

4x0011

rH relay on

16 bit

15...990

1.5...99.0 %

4x0012

rH relay off

16 bit

10...985

1.0...98.5 %

4x0013

TE relay on

16 bit

15...490

1.5...49.0 °C

4x0014

TE relay off

16 bit

10...485

1.0...48.5 °C

Function code 03 - Read input holding register

Function code 04 - Read input register

Register

Parameter description

Data Type

Value

Range

3x0001

Parameter for P-controller

16 bit 

0...3

1=rH, 2=TE, 3=MAX

3x0003

rH reading

16 bit

0...1000

0,0...100.0 %

3x0004

Temp. reading

16 bit

0...500

0.0...50.0 °C

3x0007

rH high limit

16 bit

100...1000

10.0...100.0 %

3x0008

rH low limit

16 bit

0...900

0.0...90.0 %

3x0009

TE high limit

16 bit

50...500

5.0...50.0 °C

3x0010

TE low limit

16 bit

0...450

0...45.0 °C

3x0011

Parameter for relay

16 bit

0...3

1=rH, 2=TE, (3=Off) 

3x0014

rH relay on

16 bit

15...990

1.5...99.0 %

3x0015

rH relay off

16 bit

10...985

1.0...98,5 %

3x0016

TE relay on

16 bit

15...490

1.5...49.0 °C

3x0017

TE relay off

16 bit

10...485

1.0...48.5 °C

Function code 05 - Write single coil

Register

Parameter description

Data Type

Value

Range

0x0001

Relay trend

Bit 0

0...1

0=Increasing, 1=Decreasing

Functions for Modbus communication:

Function Code

Description

01

Read coil status

02

Read input status

03

Read holding registers

04

Read input registers

05

Force single coil

06

Preset single register

07

Read exception status

15

Force multiple coils

16

Preset multiple registers

17

Report slave ID

MODBUS REGISTERS

 CONTINUED

Function code 16 - Write multiple registers

Register

Parameter description

Data Type

Value

Range

4x0001

Parameter for P-controller

16 bit 

0...3

1=rH, 2=TE, 3=MAX

4x0004

rH high limit

16 bit

100...1000

10.0...100.0 %

4x0005

rH low limit

16 bit

0...900

0.0...90.0 %

4x0006

TE high limit

16 bit

50...500

5.0...50.0 °C

4x0007

TE low limit

16 bit

0...450

0...45.0 °C

4x0008

Parameter for relay

16 bit

0...3

1=rH, 2=TE, (3=Off)

4x0011

rH relay on

16 bit

15...990

1.5...99.0 %

4x0012

rH relay off

16 bit

10...985

1.0...98.5 %

4x0013

TE relay on

16 bit

15...490

1.5...49.0 °C

4x0014

TE relay off

16 bit

10...485

1.0...48.5 °C

RECYCLING/DISPOSAL

The  parts  left  over  from  installation  should  be 
recycled  according  to  your  local  instructions. 
Decommissioned  devices  should  be  taken  to  a 
recycling site that specializes in electronic waste.

WARRANTY POLICY

Function code 06 - Write single register

Register

Parameter description

Data Type

Value

Range

4x0001

Parameter for P-controller

16 bit 

0...3

1=rH, 2=TE, 3=MAX

4x0004

rH high limit

16 bit

100...1000

10.0...100.0 %

4x0005

rH low limit

16 bit

0...900

0.0...90.0 %

4x0006

TE high limit

16 bit

50...500

5.0...50.0 °C

4x0007

TE low limit

16 bit

0...450

0...45.0 °C

4x0008

Parameter for relay

16 bit

0...3

1=rH, 2=TE, (3=Off)

4x0011

rH relay on

16 bit

15...990

1.5...99.0 %

4x0012

rH relay off

16 bit

10...985

1.0...98.5 %

4x0013

TE relay on

16 bit

15...490

1.5...49.0 °C

4x0014

TE relay off

16 bit

10...485

1.0...48.5 °C

Jumper settings 

CONTINUED

Jumper installed to the left side pins:

0–10 V output selected

N/A
N/A
Analog

0...10 V   4...20 mA

Jumper installed to the right side pins:

4–20 mA output selected

N/A
N/A
Analog

0...10 V   4...20 mA

Figure 4

2) Locking the display:

Install the jumper to lock the display to prevent access to the 
configuration menu after installation is completed (see the 
schematics for the location of the pins).

Содержание RHT-MOD Series

Страница 1: ...SPECIFICATIONS Performance Measurement ranges Temperature 0 50 C Relative humidity 0 100 Accuracy Temperature 0 5 ºC Relative humidity 2 3 at 0 50 C and 10 90 rH Total error band includes accuracy hysteresis and temperature effect over 5 50 C and 10 90 rH Technical Specifications Media compatibility Dry air or non aggressive gases Measuring units C and rH Measuring element Temperature Integrated R...

Страница 2: ...t in an area with good ventilation and an average temperature where it will be responsive to changes to the room conditions The RHT MOD should be mounted on a flat surface Do not locate the RHT MOD where it can be affected by Direct sunlight Drafts or dead areas behind doors Radiant heat from appliances Concealed pipes or chimneys Outside walls or unheated uncooled areas 2 Use the device as a temp...

Страница 3: ...outs Wires can be routed through the bottom knockouts NC COM NO STEP 2 WIRING DIAGRAMS Figure 2d Wiring diagram Relay NOTE When using long connection wires it may be necessary to use a separate GND wire for voltage output current to prevent measurement dis tortion The need for an extra GND wire depends on the cross section and length of the used connection wires If long and or small cross section ...

Страница 4: ...on code 04 Read input register Register Parameter description Data Type Value Range 3x0001 Parameter for P controller 16 bit 0 3 1 rH 2 TE 3 MAX 3x0003 rH reading 16 bit 0 1000 0 0 100 0 3x0004 Temp reading 16 bit 0 500 0 0 50 0 C 3x0007 rH high limit 16 bit 100 1000 10 0 100 0 3x0008 rH low limit 16 bit 0 900 0 0 90 0 3x0009 TE high limit 16 bit 50 500 5 0 50 0 C 3x0010 TE low limit 16 bit 0 450 ...

Отзывы: