background image

Copyright HK Instruments, Inc. 2017

www.hkinstrumentsinc.com

Installation version 2.0 2017

1) Highlight submenu, the display will change to 

FLOW UNIT

 and 

m/s

 will be blinking.

2) Cycle up or cycle down to select the correct 

flow unit.

3) Confirm selection when the correct option is 

shown on the display.

4) Cycle down to the next step in configuring 

the device. For the next configuration step in 
these installation instructions, go to step 4-19.

Flow units

Volume

  m

3

/s

  m

3

/h

  CFM

  l/s

Velocity

  m/s

  FPM

Menu

Continuing from step 4-16 or step 4-18.

1) Highlight submenu, the top line of the display 

will show 

SEL: K-VALUE

 and the bottom line 

will begin to blink.

2) Cycle up or down by tilting joystick 2 or 3 

respectively to increase or decrease the value 
shown on the display. If the desired number is 
passed, then tilt the opposite joystick to cycle 
back within 1.25 seconds, after which the 
display will begin to blink indicating that the 
steps 2 and 3 must be repeated.

Display

SEL:K-VALUE

1.000

3) Confirm selection when the correct value is shown on the display.
4) Cycle down to the next step in configuring the device. For the 

next configuration step in these installation instructions, go to 
step 4-8.

STEP 4-19: SELECT K-VALUE

Each pre-configured fan manufacturer has its own equation, 
K-value, K-value range, and equation units (flow and pressure), see 
table below. By selecting a pre-configured fan manufacturer from 
the menu, the correct configuration settings for that manufacturer 
will automatically be configured into the DPT-Flow S-4.

FAN MANUFACTURER’S EQUATIONS

Fan

manufacturer

Manufacturer’s

equation

K-value

range

Formula

unit flow

Formula

unit 

pressure

Fläkt Woods

0.3–99

m

3

/s

Pa

Rosenberg

37–800

m

3

/h

Pa

Nicotra

10–1,500

m

3

/h

Pa

Comefri

10–2,000

m

3

/h

Pa

Ziehl-Abegg

10–1,500

m

3

/h

Pa

ebm-papst

10–1,500

m

3

/h

Pa

Gebhardt

50–4,700

m

3

/h

Pa

1

k

Q

 =

P

*

Q

 = 

*

2

 

P

ρ

Q

 = 

*

2

 

P

ρ

Q

 = 

*

2

 

P

ρ

Q

 = 

*

2

 

P

ρ

Q

 = 

*

  

P

Q

 = 

*

  

P

Q  

= Air volume in (m

3

/s, m

3

/h, CFM, l/s)

k  

= K

VOL

 (K-value for air volume) in (flow unit/pressureunit)

P

   = Differential pressure measured by the FloXact probe

ρ    

= Density of the gas (air) in (kg/m

3

) or (lb/ft

3

).

 

    - at 20 °C, 1013.25 mbar, and 50 % rH, air has a density  
    of 1.2041 kg/m

3

 

    - at 70 °F, 14.6956 psi, and 50 % rH, air has density of   
    0.074887 lb/ft

3

.

 

    - The correction for different densities is determined with  
    the following formulas:

    
 

 

 

Metric 

  USA

 

    correction = 

 

correction =

ρ

1.2041

ρ

0.074887

STEP 4-18: 

OTHER

 FORMULA UNIT: FLOW

Continuing from the selection of OTHER: Formula 
unit: pressure.

The formula unit for flow will be supplied by the 
fan manufacturer or probe manufacturer. The 
DPT-Flow can accept several options in the 
flow units menu. If the flow unit supplied by the 
manufacturer is different than menu options,  
then convert the supplied value to one of the 
listed.

Display

FORMULA UNIT

FLOW

FLOW UNIT

m/s

Display selected

STEP 4-17: 

OTHER

 FORMULA UNIT: PRESSURE

Continuing from step 4-16: Other Fan Mfg OR 
Step 4-2: OTHER: Probe.

The formula unit for pressure will be supplied by 
the fan manufacturer or probe manufacturer. The 
DPT-Flow can accept Pa or inWC. If the pressure 
unit supplied by the manufacturer is different, 
then convert the supplied value to Pa or inWC.

1) Highlight submenu, the display will change to 

PRESS. UNIT

 and 

Pa

 will be blinking.

Display

 

FORMULA UNIT

PRESSURE

Display selected

 

PRESS.UNIT

Pa

2) Cycle up or cycle down between the options of Pa and inWC.
3) Confirm selection when the correct option is shown on the 

display.

4) Cycle down to the next step in configuring the device. For the 

next configuration step in these installation instructions, go to 
step 4-18.

Содержание DPT-Flow-4 Series

Страница 1: ...0 to 95 rH non condensing Physical Case Dimensions 3 54 x 3 74 x 1 4 90 0 x 95 0 x 36 0 mm Weight 5 3 oz 150 g Mounting 2 each 11 64 4 3 mm screw holes one slotted Materials Case ABS UL 94 V 0 Approved Lid PC UL 94 V 1 Approved Protection standard IP54 NEMA3 Display required for configuration 2 line display 12 characters line Size 1 81 W x 0 57 H 46 0 x 14 5 mm Electrical connections 4 screw termi...

Страница 2: ... holes 3 Mount with appropriate screws not included MOUNTING THE DEVICE CONTINUED STEP 2 WIRING DIAGRAMS For CE compliance a properly grounded shielding cable is required 1 Unscrew the strain relief and route the cable s 2 Connect the wires as shown in figure 2 3 Tighten the strain relief Figure 2 Wiring diagram V Out P Out 24V GND Power Supply 24VDC 24VAC V A V A Output 0 10V 4 20mA Output 0 10V ...

Страница 3: ...ick 1 will select and store that value Joystick 2 UP Cycle up Tilting joystick 2 will cycle up through the menu or submenu choices If you cycle past your desired choice the menu cycles through all the choices and return to the beginning of the list Joystick 3 DOWN Cycle down Tilting joystick 3 will cycle down through the menu or submenu choices If you cycle past your desired choice the menu cycles...

Страница 4: ...onfiguring the device For the next configuration step in these installation instructions If Round is selected go to step 4 4 If Rectangle is selected go to step 4 5 Display Select duct Round inch Round mm Rectangle inch Rectangle mm Menu STEP 4 3 SELECT DUCT STEP 4 4 DUCT DIAMETER SEL PROBE Probe SEL DUCT Round inch Continuing from the selection of Round inch or Round mm 1 Highlight submenu the to...

Страница 5: ...PT Flow 8 DPT Flow 20 DPT Flow 30 Pa 100 1 000 200 2 000 500 5 000 700 7 000 kPa 0 1 1 0 0 2 2 0 0 5 5 0 0 7 7 0 mbar 1 10 2 0 20 5 0 50 7 0 70 mmWC 10 100 20 200 50 500 70 700 inWC 0 4 4 0 0 8 8 0 2 0 20 2 5 30 Pressure output Upper range maximum settings Example The DPT Flow 4 has a capable range of 0 4 0 inWC If pressure readings are expected below 2 50 inWC adjust the pressure output maximum t...

Страница 6: ... The device is now ready to be used Display SELECT EXIT MENU STEP 4 15 EXIT MENU Continuing from step 4 1 selection of the fan manufacturer 1 Determine if the fan manufacturer is included in the list of included fan manufacturers in the menu 2 Highlight submenu the display will show SEL FAN MFG and the menu of fan manufacturers If the fan manufacturer is included in the menu then 3a Cycle up or cy...

Страница 7: ... s Pa Rosenberg 37 800 m3 h Pa Nicotra 10 1 500 m3 h Pa Comefri 10 2 000 m3 h Pa Ziehl Abegg 10 1 500 m3 h Pa ebm papst 10 1 500 m3 h Pa Gebhardt 50 4 700 m3 h Pa 1 k Q P Q k 2 P ρ Q k 2 P ρ Q k 2 P ρ Q k 2 P ρ Q k P Q k P Q Air volume in m3 s m3 h CFM l s k KVOL K value for air volume in flow unit pressureunit P Differential pressure measured by the FloXact probe ρ Density of the gas air in kg m3...

Страница 8: ...anges to Products already purchased HK will give a new warranty for Products being replaced or repaired within the warranty period however only to the expiration of the original Product s warranty period The warranty includes the repair of a defective part or device or if needed a new part or device but no other costs except as otherwise stated in the HK Distributor Terms and Conditions The parts ...

Отзывы: