background image

Copyright HK Instruments 2020

www.hkinstruments.fi

Installation version 9.0 2020

SCHEMATICS

DIMENSIONAL DRAWINGS

Figure 1 - Mounting orientation

Connection for display

Terminal block

Pressure

sensor

Menu buttons

LED

SELECT

UP

DOWN

ZERO

CONTROL OUT

P/V OUT

24 V

GND

CT

RL

 O

UTPUT

PRES

SUR

E

4–20 mA

Out

0–10 V

90.0

77.0

71.5

53.0

4.2

95.0

36.0

DPT-Ctrl

YES

NO

NO

INSTALLATION

1) Mount the device in the desired location (see step 1).
2) Open the lid and route the cable through the strain relief and 

connect the wires to the terminal block(s) (see step 2).

3) The device is now ready for configuration.

 

  WARNING! Apply power only after the device is properly wired.

STEP 2: WIRING DIAGRAMS

For CE compliance, a properly grounded shielding cable is required.
1) Unscrew the strain relief and route the cable. 
2) Connect the wires as shown in figure 2.
3) Tighten the strain relief.

Figure 2a - Wiring diagram

Control output

Pressure/Flow output

24 V

GND

+

Power supply

24 VDC / 24 VAC

0–10 V / 4–20 mA
0–10 V / 4–20 mA

STEP 1: MOUNTING THE DEVICE

1) Select the mounting location (duct, wall, panel).
2) Use the device as a template and mark the screw holes.
3) Mount with appropriate screws.

MOUNTING THE DEVICE 

CONTINUED

Figure 2b - Output mode selection:
Default selection 0–10 V for both

Jumper installed to the two upper pins on the left side: 

4–20 mA output selected for control output

Ctrl output

Pr

essur

e

Jumper installed to the two lower pins on the left side: 

0–10 V output selected for control output

Jumper installed to the two upper pins on the right side: 

4–20 mA output selected for pressure

Jumper installed to the two lower pins on the right side: 

0–10 V output selected for pressure

Содержание DPT-Ctrl Series

Страница 1: ... 125 Pa 1 2 Pa Pressure 125 Pa 1 1 Pa Model 7000 Pressure 125 Pa 1 5 2 Pa Pressure 125 Pa 1 5 1 Pa Accuracy specifications include general accuracy linearity hysteresis long term stability and repetition error Overpressure Proof pressure 25 kPa Burst pressure 30 kPa Zero point calibration Automatic autozero or manual pushbutton Response time 1 0 20 s selectable via menu Technical Specifications Me...

Страница 2: ...le is required 1 Unscrew the strain relief and route the cable 2 Connect the wires as shown in figure 2 3 Tighten the strain relief Figure 2a Wiring diagram Control output Pressure Flow output 24 V GND Power supply 24 VDC 24 VAC 0 10 V 4 20 mA 0 10 V 4 20 mA STEP 1 MOUNTING THE DEVICE 1 Select the mounting location duct wall panel 2 Use the device as a template and mark the screw holes 3 Mount wit...

Страница 3: ...tion P OUTPUT MAX 2000 Pa SELECT UP DOWN 5 Response time Select response time between 1 0 20 s RESPONSE TIME 20 s SELECT UP DOWN 6 Select the setpoint of the controller REF PRESSURE 100 Pa SELECT UP DOWN 7 Select proportional band according to your application specifications P VALUE 206 SELECT UP DOWN 8 Select integration time according to your application specifications I VALUE 4 00 SELECT UP DOW...

Страница 4: ... the expiration of the original product s warranty time The warranty includes the repair of a defective part or device or if needed a new part or device but not installation or ex change costs Under no circumstance is the seller liable for damages compensation for indirect damage 2 Autozero calibration If the device includes the optional autozero circuit no action is re quired Autozero calibration...

Отзывы: