background image

Copyright HK Instruments 2020

www.hkinstruments.fi

Installation version 9.0 2020

INSTALLATION

INSTRUCTIONS

AIR HANDLING CONTROLLER

DPT-Ctrl Series

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE 

ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS 
DEVICE.

•  Failure to observe safety information and comply with 

instructions can result in PERSONAL INJURY, DEATH AND/OR 

PROPERTY DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect 

power before installing or servicing and use only wiring with 
insulation rated for full device operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially 

flammable or explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered 

system whose specifications and performance characteristics 
are not designed or controlled by HK Instruments. Review 
applications and national and local codes to assure that the 
installation will be functional and safe. Use only experienced and 
knowledgeable technicians to install this device.

Thank you for choosing an HK Instruments DPT-Ctrl series air han-
dling controller with differential pressure or airflow transmitter.  The 
DPT-Ctrl series PID controllers are engineered for building automa-
tion in the HVAC/R industry. With the built-in controller of the DPT-
Ctrl it is possible to control the constant pressure or flow of fans, 
VAV systems or dampers. When controlling air flow, it is possible to 
select a fan manufacturer or a common measuring probe that has a 
K-value.

DPT-Ctrl series devices are commonly used in HVAC/R systems for:
• Controlling differential pressure or air flow in air handling systems
• VAV applications
• Controlling parking garage exhaust fans

SPECIFICATIONS

Performance

Accuracy (from applied pressure):

Model 2500:

     Pressure < 125 Pa = 1 % + ±2 Pa

     Pressure > 125 Pa = 1 % + ±1 Pa

Model 7000:

     Pressure < 125 Pa = 1.5 % + ±2 Pa

     Pressure > 125 Pa = 1.5 % + ±1 Pa

(Accuracy specifications include: general accuracy, 

linearity, hysteresis, long term

stability, and repetition error)

Overpressure:

Proof pressure: 25 kPa

Burst pressure: 30 kPa

Zero point calibration:

Automatic autozero or manual pushbutton 

Response time:

1.0−20 s, selectable via menu

Technical Specifications

Media compatibility:

Dry air or non-aggressive gases

Controller parameter (selectabe via menu):

Setpoint 0...2500/7000 Pa 

P-band 0...100 000

I-time 0...1000 s 

D-factor 0...100

Pressure units (select via menu):

Pa, kPa, mbar, inWC, mmWC, psi

Flow units (select via menu):

Volume: m

3

/s, m

3

/hr, cfm, l/s

Velocity: m/s, ft/min

Measuring element:

MEMS, no flow-through

Environment:

Operating temperature: -20...50 °C, 

-40C model: -40...50 °C

Models with autozero calibration -5...50 °C

Temperature compensated range 0...50 °C

Storage temperature: -40...70 °C

Humidity: 0 to 95 % rH, non condensing

Physical

Dimensions: 

Case: 90.0 x 95.0 x 36.0 mm

Weight: 

150 g

Mounting:

2 each 4.3 mm screw holes, one slotted

Materials:

Case: ABS

Lid: PC

Protection standard:

IP54 

Display

2-line display (12 characters/line)

 

Line 1: Direction of control output

 

Line 2: Pressure or air flow measurement,  

 

 

selectable via menu

Size: 46.0 x 14.5 mm

Electrical connections:

4-screw terminal block

Wire: 0.2–1.5 mm

2

  (12–24 AWG)

Cable entry:

Strain relief: M16

Knockout : 16 mm

Pressure fittings

5.2 mm barbed brass

+ High pressure

− Low pressure

Electrical

Voltage:

Circuit: 3-wire (V Out, 24 V, GND)

Input: 24 VAC or VDC, ±10 %

Output: 0–10 V, selectable via jumper

Power consumption: <1.0 W

Resistance minimum: 1 kΩ

Current:

Circuit: 3-wire (mA Out, 24 V, GND)

Input: 24 VAC or VDC, ±10 %

Output: 4–20 mA, selectable via jumper

Power consumption: <1.2 W

Maximum load: 500 Ω

Minimum load: 20 Ω

Conformance

Meets requirements for CE marking:

EMC Directive 2014/30/EU

RoHS Directive 2011/65/EU

WEEE Directive 2012/19/EU

WARNING

INTRODUCTION

APPLICATIONS

RoHS 2

2011/65/EU

COMPANY WITH

MANAGEMENT SYSTEM

CERTIFIED BY DNV GL

= ISO 9001 = ISO 14001 =

Содержание DPT-Ctrl Series

Страница 1: ... 125 Pa 1 2 Pa Pressure 125 Pa 1 1 Pa Model 7000 Pressure 125 Pa 1 5 2 Pa Pressure 125 Pa 1 5 1 Pa Accuracy specifications include general accuracy linearity hysteresis long term stability and repetition error Overpressure Proof pressure 25 kPa Burst pressure 30 kPa Zero point calibration Automatic autozero or manual pushbutton Response time 1 0 20 s selectable via menu Technical Specifications Me...

Страница 2: ...le is required 1 Unscrew the strain relief and route the cable 2 Connect the wires as shown in figure 2 3 Tighten the strain relief Figure 2a Wiring diagram Control output Pressure Flow output 24 V GND Power supply 24 VDC 24 VAC 0 10 V 4 20 mA 0 10 V 4 20 mA STEP 1 MOUNTING THE DEVICE 1 Select the mounting location duct wall panel 2 Use the device as a template and mark the screw holes 3 Mount wit...

Страница 3: ...tion P OUTPUT MAX 2000 Pa SELECT UP DOWN 5 Response time Select response time between 1 0 20 s RESPONSE TIME 20 s SELECT UP DOWN 6 Select the setpoint of the controller REF PRESSURE 100 Pa SELECT UP DOWN 7 Select proportional band according to your application specifications P VALUE 206 SELECT UP DOWN 8 Select integration time according to your application specifications I VALUE 4 00 SELECT UP DOW...

Страница 4: ... the expiration of the original product s warranty time The warranty includes the repair of a defective part or device or if needed a new part or device but not installation or ex change costs Under no circumstance is the seller liable for damages compensation for indirect damage 2 Autozero calibration If the device includes the optional autozero circuit no action is re quired Autozero calibration...

Отзывы: