Copyright HK Instruments 2017
www.hkinstruments.fi
Installation version 5.0 2017
STEP 2: WIRING DIAGRAMS
SELECTING THE MEASUREMENT RANGE
CONTINUED
For CE compliance, a properly grounded shielding cable is required.
1) Unscrew the strain relief and route the cable.
2) Connect the wires as shown in figure 2.
3) Tighten the strain relief.
Figure 2 - Wiring diagram 4–20 mA
1) Select the desired measurement range. (see step 4)
2) Select the desired response time. (see step 5)
3) Zero the device. (see step 6)
4) Connect the pressure tubes. Connect positive pressure to
port labeled “+” and negative pressure to port “-”.
7) Close the lid. The device is now ready to be used.
STEP 3: CONFIGURATION
STEP 4: SELECTING THE MEASUREMENT RANGE
A. For R8 models
1) Find the required measurement range and determine the range
number in the header of Chart 1.
2) Install jumpers on J1, J2 and J3 in device, as shown in Chart 2.
(Grey colour indicates that a jumper is installed. Reference Figure
3 for jumper installation.)
No jumper
Circuit open
Jumper stored
Jumper installed
Circuit closed
(Grey colour indicates that a jumper is installed)
Figure 3 - Jumper installation
4–20 mA
Power supply
10...35 VDC
A
4–20 mA
Polarity free
Range 1
Range 2
Range 3
Range 4
Range 5
Range 6
Range 7
Range 8
Pa
-100...+100
0...100
0...250
0...500
0...1000
0...1500
0...2000
0...2500
Model DPT-2W-2500-R8
Chart 1 - R8 ranges
Chart 2 - R8 jumpers
Range 7
Range 8
Range 1
Range 2
Range 3
Range 4
Range 5
Range 6
Jumper J1
Jumper J2
Jumper J3
(Grey colour indicates that a jumper is installed)
B. For R4 models
1) Find the required model and measurement range and determine the
range number in the header of Chart 3.
2) Install jumpers on J2 and J3 in device, as shown in Chart 4.
(Grey colour indicates that a jumper is installed. Reference Figure 3
for jumper installation.)
Chart 3 - R4 ranges
Range 1
Range 2
DPT-2W-1000-R4
0...250
0...500
4-range models
Pa
DPT-2W-3000-R4
0...750
0...1500
Pa
DPT-2W-5000-R4
0...1250
0...2500
Pa
Range 3
Range 4
0...750
0...2250
0...1000
0...3000
0...3750
0...5000
Chart 4 - R4 jumpers
Range 1
Range 2
Range 3
Range 4
RESPONSE TIME SELECTION
Jumper J2
Jumper J3
(Grey colour indicates that a jumper is installed)
C. For R2 models
1) Find the required model and measurement range and determine the
range number in the header of Chart 5.
2) Install jumpers on J2 and J3 in device, as shown in Chart 6.
(Grey colour indicates that a jumper is installed. Reference Figure 3
for jumper installation.)
Chart 5 - R2 ranges
Range 1
Range 2
DPT-2W-100-R2
0...50
0...100
2-range models
Pa
DPT-2W-±100-R2
-50...50
-100...100
Pa
DPT-2W-250-R2
0...100
0...250
Pa
DPT-2W-500-R2
0...250
0...500
Pa
DPT-2W-1000-R2
0...500
0...1000
Pa
DPT-2W-2500-R2
0...1500
0...2500
Pa
DPT-2W-5000-R2
0...2500
0...5000
Pa
Chart 6 - R2 jumpers
Range 1
Range 2
RESPONSE TIME SELECTION
Jumper J2
Jumper J3
(Grey colour indicates that a jumper is installed)