HK Instruments DPT-2W-2500-R8 Скачать руководство пользователя страница 3

Copyright HK Instruments 2017

www.hkinstruments.fi

Installation version 5.0 2017

STEP 2: WIRING DIAGRAMS

SELECTING THE MEASUREMENT RANGE 

CONTINUED

For CE compliance, a properly grounded shielding cable is required.
1) Unscrew the strain relief and route the cable. 
2) Connect the wires as shown in figure 2.
3) Tighten the strain relief.

Figure 2 - Wiring diagram 4–20 mA

1) Select the desired measurement range. (see step 4)
2) Select the desired response time. (see step 5)
3) Zero the device. (see step 6)
4) Connect the pressure tubes. Connect positive pressure to 

port labeled “+” and negative pressure to port “-”.

7) Close the lid. The device is now ready to be used.

 

STEP 3: CONFIGURATION

 

STEP 4: SELECTING THE MEASUREMENT RANGE

A. For R8 models

1) Find the required measurement range and determine the range 

number in the header of Chart 1.

2) Install jumpers on J1, J2 and J3 in device, as shown in Chart 2.
  (Grey colour indicates that a jumper is installed. Reference Figure 

3 for jumper installation.)

No jumper

Circuit open

Jumper stored

Jumper installed

Circuit closed

(Grey colour indicates that a jumper is installed)

Figure 3 - Jumper installation

4–20 mA

Power supply

10...35 VDC

A

4–20 mA

Polarity free

Range 1

Range 2

Range 3

Range 4

Range 5

Range 6

Range 7

Range 8

Pa

-100...+100

0...100

0...250

0...500

0...1000

0...1500

0...2000

0...2500

Model DPT-2W-2500-R8

Chart 1 - R8 ranges

Chart 2 - R8 jumpers

Range 7

Range 8

Range 1

Range 2

Range 3

Range 4

Range 5

Range 6

Jumper J1
Jumper J2
Jumper J3

(Grey colour indicates that a jumper is installed)

B. For R4 models

1) Find the required model and measurement range and determine the 

range number in the header of Chart 3.

2) Install jumpers on J2 and J3 in device, as shown in Chart 4.
  (Grey colour indicates that a jumper is installed. Reference Figure 3 

for jumper installation.)

Chart 3 - R4 ranges

Range 1 

Range 2

DPT-2W-1000-R4

0...250

0...500

4-range models

Pa

DPT-2W-3000-R4

0...750

0...1500

Pa

DPT-2W-5000-R4

0...1250

0...2500

Pa

Range 3

Range 4

0...750

0...2250

0...1000
0...3000

0...3750

0...5000

Chart 4 - R4 jumpers

Range 1

Range 2

Range 3

Range 4

RESPONSE TIME SELECTION

Jumper J2
Jumper J3

(Grey colour indicates that a jumper is installed)

C. For R2 models

1) Find the required model and measurement range and determine the 

range number in the header of Chart 5.

2) Install jumpers on J2 and J3 in device, as shown in Chart 6.
  (Grey colour indicates that a jumper is installed. Reference Figure 3 

for jumper installation.)

Chart 5 - R2 ranges

Range 1 

Range 2

DPT-2W-100-R2

0...50

0...100

2-range models

Pa

DPT-2W-±100-R2

-50...50

-100...100

Pa

DPT-2W-250-R2

0...100

0...250

Pa

DPT-2W-500-R2

0...250

0...500

Pa

DPT-2W-1000-R2

0...500

0...1000

Pa

DPT-2W-2500-R2

0...1500

0...2500

Pa

DPT-2W-5000-R2

0...2500

0...5000

Pa

Chart 6 - R2 jumpers

Range 1

Range 2

RESPONSE TIME SELECTION

Jumper J2
Jumper J3

(Grey colour indicates that a jumper is installed)

Содержание DPT-2W-2500-R8

Страница 1: ...onitoring pressure and flow monitoring valve and damper control pressure monitoring in cleanrooms SPECIFICATIONS Performance Accuracy 1 5 FS over operation temperature range 10 50 C FS from highest pressure range including general accuracy temperature drift linearity hysteresis and repetition error Long term stability Typical 1 year 8 Pa DPT 2W 2500 Thermal effects Temperature compensated across t...

Страница 2: ... relief and connect the wires to the terminal block s see step 2 3 The device is now ready for configuration WARNING Apply power only after the device is properly wired 1 Select the mounting location duct wall panel 2 Use the device as a template and mark the screw holes 3 Mount with appropriate screws Jumpers Terminal block Pressure sensor Connection for optional display LED Zero button J3 J2 J1 ...

Страница 3: ...2500 Model DPT 2W 2500 R8 Chart 1 R8 ranges Chart 2 R8 jumpers Range 7 Range 8 Range 1 Range 2 Range 3 Range 4 Range 5 Range 6 Jumper J1 Jumper J2 Jumper J3 Grey colour indicates that a jumper is installed B For R4 models 1 Find the required model and measurement range and determine the range number in the header of Chart 3 2 Install jumpers on J2 and J3 in device as shown in Chart 4 Grey colour i...

Страница 4: ...t least one hour prior to zero point adjustment 2 Disconnect both pressure tubes from the pressure ports labeled and 3 Push the zero button at least 4 seconds until the LED light red shows one long blink see Figure 4 4 The zeroing of the device will proceed automatically Zeroing is complete when the LED turns off 5 Reinstall the pressure tubes ensuring the high pressure tube is connected to the po...

Отзывы: