HK Instruments DPT-2W-2500-R8 Скачать руководство пользователя страница 1

Copyright HK Instruments 2017

www.hkinstruments.fi

Installation version 5.0 2017

INSTALLATION

INSTRUCTIONS

DIFFERENTIAL PRESSURE TRANSMITTERS 

DPT-2W Series

• 

READ THESE INSTRUCTIONS CAREFULLY BEFORE 
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS DEVICE.

•  Failure to observe safety information and comply with 

instructions can result in 

PERSONAL INJURY, DEATH AND/OR 

PROPERTY DAMAGE

.

•  To avoid electrical shock or damage to equipment, disconnect 

power before installing or servicing and use only wiring with 
insulation rated for full device operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially 

flammable or explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered 

system whose specifications and performance characteristics 
are not designed or controlled by HK Instruments. Review 
applications and national and local codes to assure that the 
installation will be functional and safe. Use only experienced and 
knowledgeable technicians to install this device.

SPECIFICATIONS

Thank you for choosing an HK Instruments DPT series differential 
pressure transmitter. The DPT series is intended for use in commer

-

cial  environments.  The  DPT-2W  series  differential  pressure  trans

-

mitter provides a 4–20 mA loop output.

All  DPT-2W  series  differential  pressure  transmitters  are  available 
with display and/or flow linear output.

DPT-2W series devices are commonly used in HVAC/R systems for:
•  fan, blower and filter monitoring
•  pressure and flow monitoring
•  valve and damper control
•  pressure monitoring in cleanrooms

SPECIFICATIONS

Performance

Accuracy:

±1.5 % FS over operation temperature range:

-10...50 °C %/FS from highest pressure

range (including: general accuracy, temperature drift,

linearity, hysteresis, and repetition error)

Long term stability:

Typical 1 year:  ±8 Pa; DPT-2W-2500

Thermal effects:

Temperature compensated across the full spectrum of

capability.

Overpressure:

Proof pressure: 25 kPa

Burst pressure: 30 kPa

Zero point calibration:

Manual pushbutton

Response time:

4.0 s or 0.8 s, selectable

Technical Specifications

Media compatibility:

Dry air or non-aggressive gases

Measuring units:

Pa

Measuring element:

Piezoresistive

Enviroment:

Operating temperature: -10...50 °C

Storage temperature: -20...70 °C

Humidity: 0 to 95 % rH, non condensing

Physical

Dimensions:  

Case: 90.0 x 95.0 x 36.0 mm

Weight:   

150 g

Mounting: 

2 each 4.3 mm screw holes, one slotted

Materials:

Case: ABS

Lid: PC

Duct connectors: ABS

Tubing: PVC

Protection standard:

IP54 

Display: (Optional)

3 1/2 digit LCD display

Size: 45.7 mm W x 12.7 mm H

Electrical connections:

2 screw terminal block

Wire: 12–24 AWG (0.2–1.5 mm

2

)

Cable entry:

Strain relief: M16

Conduit knockout: 16 mm

Pressure fittings:

Male 5.0 mm and 6.3 mm 

Electrical

Voltage:

Circuit: 2-wire

Supply: 10–35 VDC

Supply (Current): 32 mA maximum

Output: 4–20 mA loop

Zero/Span output calibrated within ±0.08 mA

Maximum load =  

Supply - 10 V

 

 

 

    0,020 A

Minimum load: 20 Ω

Power consumption: <1.2 W

Conformance

Meets requirements for CE marking:

EMC Directive 2014/30/EU

RoHS Directive 2011/65/EU

WEEE Directive 2012/19/EU

INTRODUCTION

APPLICATIONS

WARNING

COMPANY WITH

MANAGEMENT SYSTEM

CERTIFIED BY DNV GL

= ISO 9001 = ISO 14001 =

RoHS 2

2011/65/EU

Содержание DPT-2W-2500-R8

Страница 1: ...onitoring pressure and flow monitoring valve and damper control pressure monitoring in cleanrooms SPECIFICATIONS Performance Accuracy 1 5 FS over operation temperature range 10 50 C FS from highest pressure range including general accuracy temperature drift linearity hysteresis and repetition error Long term stability Typical 1 year 8 Pa DPT 2W 2500 Thermal effects Temperature compensated across t...

Страница 2: ... relief and connect the wires to the terminal block s see step 2 3 The device is now ready for configuration WARNING Apply power only after the device is properly wired 1 Select the mounting location duct wall panel 2 Use the device as a template and mark the screw holes 3 Mount with appropriate screws Jumpers Terminal block Pressure sensor Connection for optional display LED Zero button J3 J2 J1 ...

Страница 3: ...2500 Model DPT 2W 2500 R8 Chart 1 R8 ranges Chart 2 R8 jumpers Range 7 Range 8 Range 1 Range 2 Range 3 Range 4 Range 5 Range 6 Jumper J1 Jumper J2 Jumper J3 Grey colour indicates that a jumper is installed B For R4 models 1 Find the required model and measurement range and determine the range number in the header of Chart 3 2 Install jumpers on J2 and J3 in device as shown in Chart 4 Grey colour i...

Страница 4: ...t least one hour prior to zero point adjustment 2 Disconnect both pressure tubes from the pressure ports labeled and 3 Push the zero button at least 4 seconds until the LED light red shows one long blink see Figure 4 4 The zeroing of the device will proceed automatically Zeroing is complete when the LED turns off 5 Reinstall the pressure tubes ensuring the high pressure tube is connected to the po...