background image

Copyright HK Instruments 2019

www.hkinstruments.fi

Installation version 5.0 2019

INSTALLATION

INSTRUCTIONS

CARBON MONOXIDE TRANSMITTERS

CMT Series

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE 

ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS 
DEVICE.

•  Failure to observe safety information and comply with 

instructions can result in PERSONAL INJURY, DEATH AND/OR 

PROPERTY DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect 

power before installing or servicing and use only wiring with 
insulation rated for full device operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially 

flammable or explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered 

system whose specifications and performance characteristics 
are not designed or controlled by HK Instruments. Review 
applications and national and local codes to assure that the 
installation will be functional and safe. Use only experienced and 
knowledgeable technicians to install this device.

SPECIFICATIONS

Thank  you  for  choosing  an  HK  Instruments  CMT  series  carbon 
monoxide  transmitter.  CMT  is  an  easy-to-use,  reliable  transmitter 
for detecting CO gas. It is commonly used to control ventilation in 
areas  where  high  concentrations  of  CO  may  cause  serious  health 
problems. 

CMT devices are commonly used in places where air includes CO gas 
emissions, such as:
• Commercial parking garages
• Apartment garages
• Tunnels and terminals
• Car and bus maintenance garages
• Warehouses and factories
• Car service centers

SPECIFICATIONS

Performance

Measurement range:

0...300 ppm CO

Linearity:

≤2 % on 300 ppm CO

Cross sensitivity:

≤2 % on 300 ppm CO

Reproducibility:

≤3 ppm

Technical Specifications

Response time:

<60 s

Gas entry:

by diffusion

Measuring element:

Electro-chemical

Environment:

Operating temperature: -10...40 °C

Humidity: 15 to 95 % rH

Physical

Case: 

Dimensions: 90 x 95 x 36 mm

Weight: 87 g

Materials: 

Case: ABS

Lid: PC

Protection standard: 

IP54

Electrical connections:

2-pole screw terminal, max 1.5 mm

2

Cable entry:

M16

Electrical

Supply voltage:

14...28 VDC

Output signal:

4...20 mA, maximum load 300 Ω

Conformance

Safety for sensor:

TÜV-approval according to VDI 2053

R.F.I according to EN 50 081-1 resp. EN 50 082-2 B

Meets the requirements for CE marking:

EMC Directive: 2014/30/EU

RoHS Directive: 2011/96/EU

WEEE Directive: 2012/19/EU

INTRODUCTION

WARNING

APPLICATIONS

COMPANY WITH

MANAGEMENT SYSTEM

CERTIFIED BY DNV GL

= ISO 9001 = ISO 14001 =

RoHS 2

2011/65/EU

The recommended transmitter calibration interval is one year.