Installation version 2.0 2017

Figure 2c - Wiring diagram: relay

NC

COM
NO

Figure 3 - Jumper installation

STEP 2: WIRING DIAGRAMS

CAUTION!

•  For CE compliance, a properly grounded shielding cable is 

required.

•  Use copper wire only. Insulate or wire nut all unused leads.
•  Supply a separate cable for relay and signal out when using line 

voltage to power the relay.

•  Any wiring may carry the full operating line voltage current based 

on field installation. The cover locking screw must be installed if 
the line voltage is supplied to the relay.

•  Care should be used to avoid electrostatic discharge to the 

device.

•  This unit has configuration jumpers. You may need to reconfigure 

this device for your application.

1) Route the cables through the square opening in the back plate or 

for surface wiring select a knockout on the top or bottom of the 
wall plate, as shown in Figure 2a.

2) Connect the wires as shown in Figure 2b and 2c.

Figure 2b - Wiring diagram: 

Power input and signal out

24 V
GND
CO

2

rH
Temp

+

Output 0/2–10 V / 4–20 mA

Output 0/2–10 V / 4–20 mA

Output 0/2–10 V / 4–20 mA

WIRING DIAGRAMS 

CONTINUED

Figure 2a - Routing the cables

Wires can be routed through the square opening in the back plate

Wires can be routed through the top knockouts

Wires can be routed through the bottom knockouts

STEP 3: CONFIGURATION

NOTE! When using long connection wires it may be necessary 
to use a separate GND wire for voltage output current to prevent 
measurement distortion. The need for an extra GND wire depends 
on the cross section and length of the used connection wires. If long 
and/or small cross section wires are used, supply current and wire 
resistance may generate a voltage drop in the common GND wire 
resulting in a distorted output measurement.

Configuration of the CDT series device consists of:
1) Configuring the jumpers (see step 4).
2) Configuration menu options.
(Display versions only. See the user manual for further details.)

          (Grey colour indicates that a jumper is installed)

No jumper

Circuit open

Jumper installed

Circuit closed

Jumper stored

Содержание CDT Series

Страница 1: ...lative Humidity Thermoset polymer capacitive sensing element Environment Operating Temperature 32 122 F 0 50 C Storage Temperature 4 158 F 20 70 C Humidity 0 to 95 rH non condensing Physical Case Dimensions 3 93 x 3 57 x 1 26 99 87 x 90 75 x 31 99 mm Weight 4 82 oz 150 g Mounting 3 screw holes slotted 11 64 ø 3 8 mm Materials Case ABS UL 94 V 0 Approved Protection standard IP20 Display Optional To...

Страница 2: ... the wires see step 2 3 The device is now ready for configuration WARNING Apply power only after the device is properly wired STEP 1 MOUNTING THE DEVICE 1 Select a mounting location on the wall at 4 ft 1 2 m above the floor Locate the unit in an area with good ventilation and an average temperature where it will be responsive to changes to the room conditions The CDT may be mounted on a flat surfa...

Страница 3: ... as shown in Figure 2b and 2c Figure 2b Wiring diagram Power input and signal out 24 V GND CO2 rH Temp Output 0 2 10 V 4 20 mA Output 0 2 10 V 4 20 mA Output 0 2 10 V 4 20 mA WIRING DIAGRAMS CONTINUED Figure 2a Routing the cables Wires can be routed through the square opening in the back plate Wires can be routed through the top knockouts Wires can be routed through the bottom knockouts STEP 3 CON...

Страница 4: ...THE PRODUCT PURCHASED f FURTHER LIMITATIONS The warranty herein does not cover damage caused by lightning flood or other natural phenomenon normal wear and tear accident improper or careless handling abnormal use overloading improper storage or abuse incorrect installation care or reconstruction or alteration calibration reconfiguration maintenance or installation work done by unqualified personne...

Отзывы: