background image

Copyright HK Instruments, Inc. 2017

www.hkinstrumentsinc.com

Installation version 2.0 2017

INSTALLATION

INSTRUCTIONS

CARBON DIOXIDE TRANSMITTERS

CDT Series

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO 

INSTALL, OPERATE OR SERVICE THIS DEVICE.

•  Failure to observe safety information and comply with instructions can result in 

PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect power before 

installing or servicing and use only wiring with insulation rated for full device 
operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially flammable or 

explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered system whose 

specifications and performance characteristics are not designed or controlled 
by HK Instruments. Review applications and national and local codes to assure 
that the installation will be functional and safe. Use only experienced and 
knowledgeable technicians to install this device.

Thank you for choosing an HK Instruments CDT2000 series carbon 
dioxide transmitter. The CDT2000 series is intended for use in com-
mercial environments in HVAC/R applications.

The CDT2000 series measures carbon dioxide (CO

2

), utilizing the in-

dustry standard NDIR measurement principle, and temperature (T). 
Optional relative humidity (rH) measurement is also available in the 
same device. Each measurement parameter (CO

2

, rH, T) has a sepa-

rate field configurable output.

The CDT2000 series carbon dioxide transmitters are available with 
Modbus configuration, relay, touchscreen display, and NIST standard 
calibration certificates.

The CDT2000 series transmitters calibrate themselves automatically 
using ABC

TM

 logic. The ABC

TM

 logic requires that the space in which 

the transmitter is used needs to to be unoccupied for four hours per 
day so that the indoor CO

2

 concentration drops to the outside level. 

CDT2000-DC is a dual channel model with a measuring channel and 
a reference channel that makes a continuous comparison and the 
necessary adjustment accordingly. CDT2000-DC is also suitable for 
buildings that are continuously occupied.

SPECIFICATIONS

Performance

Measurement range:

CO

2

: 400–2,000 ppm

Temperature: 32−122 °F
Relative Humidity: 0–90 %

Accuracy:

CO

2

: ±40 ppm + 2 % of reading, DC model: 75 ppm or 

10 % of reading (whichever is greater)
Temperature: <0.9 °F
Relative Humidity: ±4 % max @32−122 °F
and 0–90 % rH
Total error band includes accuracy, hysteresis and
temperature effect over 41–122 °F and
10–90 % rH.

Technical Specifications

Media Compatibility:

Dry air or non-aggressive gases

Measuring units:

ppm, °F and %

Measuring element:

CO

2

: Non Dispersive Infrared (NDIR)

Temperature: Pt1000
Relative Humidity: Thermoset polymer capacitive
sensing element

Environment:

Operating Temperature: 32−122 °F (0−50 °C)
Storage Temperature: -4−158 °F (-20−70 °C)
Humidity: 0 to 95 % rH, non condensing

Physical

Case:

Dimensions: 3.93” x 3.57” x 1.26”
 

  (99.87 x 90.75 x 31.99 mm)

Weight: 4.82 oz (150 g)
Mounting: 3 screw holes slotted, 11/64” ø (3.8 mm)
Materials: Case: ABS (UL 94 V-0 Approved)
Protection standard: IP20

Display 

(Optional)

Touchscreen
Size: 3.05” W x 2.06” H
        (77.4 x 52.4 mm)

Electrical Connections:

Power Supply: 5-screw terminal block
 

(24 V, GND, CO

2

, rH, Temp)

 

12–24 AWG (0.2–1.5 mm

2

)

Relay Out: 3-screw terminal block
 

(NC, COM, NO)

 

12–24 AWG (0.2–1.5 mm

2

)

Electrical

Input: 24 VAC or VDC, ±10 %

Current consumption: max 90 mA (at 24 V) + 10 mA for 
each voltage output or 20 mA for each current output

CO

2

 Output signal:  

0–10 V, R>1 kΩ
2–10 V, R>1 kΩ
4–20mA, R<500 Ω

Temperature Output signal:

0–10 V, R>1 kΩ
2–10 V, R>1 kΩ
4–20 mA, R<500 Ω

Relative Humidity Output Signal: 

0–10 V, R>1 kΩ
2–10 V, R>1 kΩ
4–20 mA, R<500 Ω

Relay Out:  

3-screw terminal block
(NC, COM, NO)
12–24 AWG (0.2–1.5 mm

2

)

SPDT Relay, 250 VAC / 30 VDC / 6 A

Conformance

Meets requirements for CE marking:
EMC Directive: 2014/30/EU
RoHS Directive: 2011/65/EU
LVD Directive: 2014/35/EU
WEEE Directive: 2012/19/EU

INTRODUCTION

WARNING

AVERTISSEMENT

• LISEZ ATTENTIVEMENT CES INSTRUCTIONS AVANT DE PROCÉDER À 

L’INSTALLATION, LA MISE EN SERVICE OU L’ENTRETIEN DE CET APPAREIL.

• Le non-respect des informations et instructions de sécurité peut entraîner DES 

DOMMAGES CORPORELS, LA MORT ET/OU DES DÉGÂTS MATÉRIELS.

• Afin d’éviter les chocs électriques et les dommages matériels, déconnectez 

l’alimentation électrique avant l’installation ou l’entretien, et utilisez uniquement du 
câblage avec isolement assigné pour une tension d’alimentation optimale.

• Afin de prévenir les risques d’incendie et/ou d’explosion, n’utilisez pas l’appareil 

dans des environnements potentiellement inflammables ou explosifs.

• Conservez ces instructions à titre de référence.
• Une fois installé, ce produit fera partie d’un système technique dont les 

spécifications et les caractéristiques de performance ne sont ni conçues ni 
contrôlées par HK Instruments. Consultez les applications et les codes nationaux 
et locaux pour garantir le fonctionnement correct et sûr de l’installation. Ne faites 
appel qu’à des techniciens expérimentés et compétents pour installer cet appareil.

APPLICATIONS

•  humidity in various industrial applications
•  temperatures in HVAC/R environment
• CDT2000-DC series devices can also be used in applications 

where there is a constant source of carbon dioxide present (for 
example hospitals and greenhouses)

CDT series devices are commonly used to monitor:
•  CO

2

 and humidity levels in offices, public spaces, meeting 

rooms and classrooms

•  CO

2

 levels of extract air in ventilation systems

• supply air and extract air humidity levels in ventilation system

RoHS 2

2011/65/EU

COMPANY WITH

MANAGEMENT SYSTEM

CERTIFIED BY DNV GL

= ISO 9001 = ISO 14001 =

Содержание CDT Series

Страница 1: ...lative Humidity Thermoset polymer capacitive sensing element Environment Operating Temperature 32 122 F 0 50 C Storage Temperature 4 158 F 20 70 C Humidity 0 to 95 rH non condensing Physical Case Dimensions 3 93 x 3 57 x 1 26 99 87 x 90 75 x 31 99 mm Weight 4 82 oz 150 g Mounting 3 screw holes slotted 11 64 ø 3 8 mm Materials Case ABS UL 94 V 0 Approved Protection standard IP20 Display Optional To...

Страница 2: ... the wires see step 2 3 The device is now ready for configuration WARNING Apply power only after the device is properly wired STEP 1 MOUNTING THE DEVICE 1 Select a mounting location on the wall at 4 ft 1 2 m above the floor Locate the unit in an area with good ventilation and an average temperature where it will be responsive to changes to the room conditions The CDT may be mounted on a flat surfa...

Страница 3: ... as shown in Figure 2b and 2c Figure 2b Wiring diagram Power input and signal out 24 V GND CO2 rH Temp Output 0 2 10 V 4 20 mA Output 0 2 10 V 4 20 mA Output 0 2 10 V 4 20 mA WIRING DIAGRAMS CONTINUED Figure 2a Routing the cables Wires can be routed through the square opening in the back plate Wires can be routed through the top knockouts Wires can be routed through the bottom knockouts STEP 3 CON...

Страница 4: ...THE PRODUCT PURCHASED f FURTHER LIMITATIONS The warranty herein does not cover damage caused by lightning flood or other natural phenomenon normal wear and tear accident improper or careless handling abnormal use overloading improper storage or abuse incorrect installation care or reconstruction or alteration calibration reconfiguration maintenance or installation work done by unqualified personne...

Отзывы: