Installation version 6.0 2018
Figure 2a - Wiring diagram: Tout & Vout
Figure 2b - Wiring diagram: relay output
For CE compliance a properly grounded shielding cable is
required.
1) Unscrew the strain relief and route the cable(s). Use the strain
relief on the left for power in and signal out (Tout/vout) and the
strain relief on the right for relay.
2) Connect the wires as shown in figure 2a and 2b.
3) Tighten the strain relief.
1) Select the desired measurement range (see step 3).
2) Select the desired measurement mode (see step 4).
3) Configure the relay (optional) (see step 5).
The device is now ready to be used.
Configure the outputs:
• Temperature output (Tout)
• Velocity output (vout)
Select the output mode, current (mA) or voltage (V), by installing
jumpers as shown in Figure 4. Both outputs, temperature (T)
and velocity (v), are configured separately.
SELECTING THE MEASUREMENT RANGE
CONTINUED
Tout
vout
24 V
GND
+
Power supply
24 VDC / 24 VAC
V
A
V
A
Output 0...10 V / 4...20 mA (temperature)
Output 0...10 V / 4...20 mA (velocity)
r
d
No jumper
Circuit open
Jumper stored
Jumper installed
Cicuit closed
(Grey colour indicates that a jumper is installed)
Figure 3b - Jumper installation
J1 Jumper (J1): Installed
J2 Jumper (J2): Not installed
Range 2 (0–2 m/s)
J1 Jumper (J1): Not installed
J2 Jumper (J2): Installed
Range 10 (0–10 m/s)
J1 Jumper (J1): Installed
J2 Jumper (J2): Installed
Range 20 (0–20 m/s)
V
Temperature output (Tout): T = voltage (V)
Velocity output (vout): v = voltage (V)
T
v
mA
V
Temperature output (Tout): T = current (mA)
Velocity output (vout): v = current (mA)
T
v
mA
Temperature output (Tout): T = voltage (V)
Velocity output (vout): v = current (mA)
T
v
V mA
Temperature output (Tout): T = current (mA)
Velocity output (vout): v = voltage (V)
T
v
V mA
NC
COM
NO
STEP 2: WIRING DIAGRAMS
Select the measurement range by installing jumpers as shown in
Figure 3a. (See Figure 3a-3b – Jumper settings)
CONFIGURATION
STEP 3: SELECTING THE MEASUREMENT RANGE
STEP 4: SELECTING THE MEASUREMENT MODE
Figure 3a
Figure 4