CONTROLLER
CHILLERS and HEAT PUMPS Air-Water
13
USM_CONTROL_KRONO 3-MINI KRONO 3_208064_220501_EN
ALARM MESSAGES
ACTION
DIN - Compressor 3 Overload
Does not apply to that compressor
DIN - Compressor 4 Overload
Does not apply to that compressor
DIN - Fans 1 Overload
Stops Circuit nº1
DIN - Fans 2 Overload
Stops Circuit nº2
DIN - FlowSwitch - Pump ON no flow
Stops the whole unit
DIN - FlowSwitch - Pump OFF flow
Does not allow the unit to start.
DIN - High Press. Pressostat Circ.1
Stops Circuit nº1, proceed to resetting the pressure switch physically
DIN - High Press. Pressostat Circ.2
Stops Circuit nº2, proceed to resetting the pressure switch physically
ENV. - High discharge pres. Circ.1
Stops Circuit nº1
ENV. - High discharge temp. Circ.1
Stops Circuit nº1
ENV. - Low discharge pres. Circ.1
Stops Circuit nº1
ENV. - High motor current Circ.1
Stops Circuit nº1
ENV. - High pressure ratio Circ.1
Stops Circuit nº1
ENV. - Low delta pressure Circ.1
Stops Circuit nº1
ENV. - Low pressure ratio Circ.1
Stops Circuit nº1
ENV. - High suction pres. Circ.1
Stops Circuit nº1
ENV. - Low suction pres. Circ.1
Stops Circuit nº1
ENV. - High discharge pres. Circ.2
Stops Circuit nº2
ENV. - High discharge temp. Circ.2
Stops Circuit nº2
ENV. - Low discharge pres. Circ.2
Stops Circuit nº2
ENV. - High motor current Circ.2
Stops Circuit nº2
ENV. - High pressure ratio Circ.2
Stops Circuit nº2
ENV. - Low delta pressure Circ.2
Stops Circuit nº2
ENV. - Low pressure ratio Circ.2
Stops Circuit nº2
ENV. - High suction pres. Circ.2
Stops Circuit nº2
ENV. - Low suction pres. Circ2
Stops Circuit nº2
EVD1 - Battery discharge
Stops the whole unit
EVD1 - EEPROM alarm
Stops the whole unit
EVD1 - Incomplete closing
Stops the whole unit
EVD1 - Emergency closing
Stops the whole unit
EVD1 - Firmware not compatible
Stops the whole unit
EVD1 - Configuration error
Stops the whole unit
EEVA - Low SuperHeat Circ.1
Stops Circuit nº1
EEVA - LOP Circ.1
Stops Circuit nº1
EEVA - MOP Circ.1
Stops Circuit nº1
EEVA - Motor error Circ.1
Stops Circuit nº1
EEVA - Low suction temp. Circ.1
Stops Circuit nº1
EEVA - High condensing temp.
Stops Circuit nº1
EEVB - Low SuperHeat Circ.2
Stops Circuit nº2
EEVB - LOP Circ.2
Stops Circuit nº2
EEVB - MOP Circ.2
Stops Circuit nº2
EEVB - Motor error Circ.2
Stops Circuit nº2
EEVB - Low suction temp. Circ.2
Stops Circuit nº2
EEVA - Ineffective adaptive control
Stops Circuit nº1
EEVA - Emergency closing alarm
Stops Circuit nº1
EEVA - Parameter range error
Stops Circuit nº1
EEVB - High condensing temp.
Stops Circuit nº2
EEVB - Ineffective adaptive control
Stops Circuit nº2
EEVB - Emergency closing alarm
Stops Circuit nº2
EEVB - Parameter range error
Stops Circuit nº2
Antifreeze Alarm
Stops the whole unit, pump is maintained and resistances are
started up
Antifreeze warning
Warning with the unit stopped, start-up of pump and resistances
Antifreeze Alarm Circ.1
Stops Circuit nº1, pump is maintained and resistances are started up
Antifreeze Alarm Circ.2
Stops Circuit nº1, pump is maintained and resistances are started up
High Pres. Alarm Circ.1
Stops Circuit nº1
Low Pres. Alarm Circ.1
Stops Circuit nº1
Minimum Pres. Alarm Circ.1
Stops Circuit nº1