CCHBA-CCHA

 

HORIZONTAL CONDENSER UNITS 
WITH COMPRESSOR AND CENTRIFUGAL FAN

 

 

IOM_CCHBA- CCHA_201a1201_208029_200201_EN

 

INSTALLATION 

REFRIGERATION CONNECTIONS

 

Damages caused by a wrong installation of the refrigeration connections between the 

indoor and the outdoor units will not be covered by the warranty. 

A wrong installation may entail the following sources of problems: 

Penetration of air, water or any type of object or animal. 

Pipes that are too thick or too thin. 

Strangled or poorly brazed tubes. 

Not complying with the current local laws because of a wrong layout and problems of aestheticism of the 
façades, etc. 

Likewise, the above mentioned consequences may have an impact on: 

Speed of the refrigerant inside the pipe (too high or too low). 

Migration and no return of the compressor oil. 

Noises. 

Explosive breaks of the pipes. 

Contamination due to refrigerant leakage (greenhouse gas). 

Break of the solenoid valves or the expansion valves. 

Increased electrical consumption and decreased performance and capacity. 

Decreased operation limits. The unit might even become completely inoperative. 

Breakage of the compressor or shortening of its operation lifetime.  

Guidelines for the correct installation of the refrigeration connections 

1.  Select a suitable place and prepare the correct settlement of the units. Determine the length of the refrigeration lines 

between the units.   

2.  Calculate the dimensions of the pipes (diameters, lengths) and the necessary couplings for the installation.  

Use as a reference the nº 207682 document (REFRIGERATION LINES DESIGN (R410a)). 

3.  Before starting installation, control that the inside part of the tubes are clean and humidity proof. Use preferably long 

radius curves, do not produce throttles when handling the tube. 

4. Pipe installation: 

-  Cut the tube with a tubbing cutter and then remove the burr and recalibrate the 

diameter  that  has  been  reduced.  Recalibrate  with  interior  gauge  or  tube 
expander. Do not use file, knife, or any other non-specialized tool that could leave 
particles inside the pipe.  

-  Reduce  the  number  of  brazing  and  remember  that  it  should  always  be  of  the 

strong type. In compliance with local laws, the welder must be an authorized person. A bad weld can cause dirt inside 
the pipe, more or less explosive blowouts that may cause third-party damage, pipe obstruction, refrigerant leakage, 
etc.  Remember  that  the  tubes  to  be  brazed  must  be  clean  without  oil  and  refrigerant.  Do  not  forget  to  make  dry 
nitrogen circulate in the interior without pressurizing and heat the male pipe primarily to ensure a good penetration.    

5.  The connection of the pipes to the machines can be threaded or brazed. Check the tightness after the connections. 
6.  The most common threaded connections in small pipes are the Flare type (flared) connections. A bad Flare connection 

will  entail  leaks  and/or  blowouts. When  doing  the flare,  it  is  essential  to  clean the  burr  of  the tube  properly  to  avoid 
cracks, and do not leave the pipe wall very thin and without consistency by tightening too much. 

 

 

 

 

 

 

 

Correct 

Too big 

Very small 

Sloped 

Cracked 

Very 

thin 

or 

uneven wall 

Internal 
scratches 

7.  Make the vacuum to the installation and the units that are not charged with refrigerant. Once the vacuum 

pump  stops,  check  that  the  vacuum  remains  during  20  min.,  a  proper  vacuum  will  be  at  an  absolute 
pressure of 2 hPa (2 mbar) or less. 
Humidity or water in the installation may cause irreversible damages to the compressor and other devices 
of the circuit. Liquid water cools and boils when the vacuum reaches its vapor pressure and does not allow 
it to do so correctly until it freezes, once the water is frozen it does not boil but it is much more difficult to 
remove and detect. To avoid the freezing of the water, it is advisable to make a soft and prolonged vacuum 
and not make a fast vacuum with very powerful pumps. 

8.  Open  all  the  keys  and  load  with  the  refrigerant  indicated  on  the  nameplate.  If  it  is  not  included  in  the 

machine, add the additional load due to the length and thickness of the pipes. Follow current legislation 
regarding who and how can handle the refrigerant.  
 

9.  Check for leaks during the first operation hours and schedule maintenance after the first month. 

 

 

Содержание CCHBA/CCHA 1001

Страница 1: ...1a1201_208029_200201_EN CCHBA CCHA HORIZONTAL CONDENSER UNITS WITH COMPRESSOR AND CENTRIFUGAL FAN Models 201 251 351 371 401 501 701 721 751 801 1001 1201 Cooling Capacities from 5 6 kW to 33 5 kW Hea...

Страница 2: ...oning and cooling installations for over 35 years Our approach is based on efficiency flexibility and on practical solutions This has been the hallmark of our product catalogue The versatility of our...

Страница 3: ...del 12 CCHBA CCHA 251 model 12 CCHBA CCHA 351 model 13 CCHBA CCHA 371 401 501 models 13 CCHBA CCHA 701 721 751 801 models 14 CCHBA CCHA 1001 model 14 CCHBA CCHA 1201 model 15 WEIGHT DISTRIBUTION KG 16...

Страница 4: ...of the Th Tune internal temperature probe 27 Operation modes 27 Indoor Fan 28 Alarms 29 TH TUNE CONTROL 30 ALARMS DIAGNOSIS 30 TH TUNE Description of the alarm codes 30 PGD1 OR MINI PGD THERMOSTAT 31...

Страница 5: ...ating the Data The continuous improvement in design and performance to which we are committed to gives us the right to modify the specifications of our products without prior notice Electrical Supply...

Страница 6: ...orized manipulation reparation or modification of the unit will automatically invalidate the warranty Packaging and Replacement of Equipment The material of the package plastic bags insulating materia...

Страница 7: ...ill carry out basic tasks only such as cleaning and replacement of filters or filter cleaning excluding the refrigerant filters etc Prevent access to children to avoid that they play with the equipmen...

Страница 8: ...0 400 Fin Spacing mm 1 8 Tube Diameter mm 3 8 FAN Type Centrifugal double suction Model 9 9 DD 10 10 DD 10 10 DD 12 9 DD 12 9 DD 12 9 DD Motor Power kW 0 37 0 37 0 44 0 55 0 55 1 10 Voltage V 230 1 23...

Страница 9: ...0 605 0 900 1 190 Fin Spacing mm 1 8 Tube Diameter mm 3 8 FAN Type Centrifugal of Double Suction Model 12 12 DD 12 12 DD 12 12 SS 12 12 SS 12 12 SS 12 12 SS Motor Power kW 1 1 1 1 1 5 1 5 2 2 4 0 Vol...

Страница 10: ...the one shown below Be sure to hoist the machine through the points indicated in the diagram Make sure that the unit is balanced stable and without any deformations during the lifting operations STORA...

Страница 11: ...the transmission of noise and vibration Check that the direction of the sound level will not disturb anybody The standard version of this equipment has been designed for installation inside a building...

Страница 12: ...l LEGEND 1 Motor 2 Fab 3 Indoor drainage 3 4 4 Heat exchanger 5 Compressor 6 Electrical Panel 7 Refrigerant connections 8 External Pressure Tap for Monitoring 9 Power supply LEGEND 1 Motor 2 Fan 3 Ind...

Страница 13: ...ptional Legend 1 Motor 2 Fan 3 Drainage 3 4 4 Heat Exchanger 5 Compressor 6 Electrical Panel 7 Refrigerant Connections 8 External Pressure Tap for Monitoring 9 Main Switch 10 Power Supply Standard Opt...

Страница 14: ...Heat Exchanger 3 Turbine 4 Turbine Motor 5 Electrical Panel 6 Drainage 3 4 7 Main Switch 8 Electrical Connections 9 External Pressure Tap for Monitoring 10 Refrigerant Connections Standard Optional L...

Страница 15: ...1201_208029_200201_EN INSTALLATION DIMENSIONS CCHBA CCHA 1201 model Standard Optional Legend 1 Compressor 2 External Heat Exchanger 3 External Pressure Tap for Monitoring 4 Electrical Panel 5 Turbine...

Страница 16: ...es below 0 degrees thermal insulation or electrical heating wires shall be used to prevent the water from freezing and avoid the possible following tube damages Install a siphon with the appropriate d...

Страница 17: ...e line pressure drop The refrigerant circulation speed The refrigerant mass in the system The length of the interconnection pipes please contact Hitecsa for lines longer than 50 meters Discharge lines...

Страница 18: ...The indoor unit is installed at the same level as the outdoor unit raise the suction line to a higher level than the indoor heat exchanger in order to avoid refrigerant return into the compressor dur...

Страница 19: ...17 2 647 22 9 808 28 6 1 3 8 24 853 120 4 3 241 8 5 481 17 1 722 25 6 963 34 1 1204 42 6 1 5 8 34 1219 172 6 1 344 12 2 688 24 4 1033 36 6 1377 48 8 1721 60 9 2 1 8 61 2149 303 10 7 607 21 5 1213 43...

Страница 20: ...could leave particles inside the pipe Reduce the number of brazing and remember that it should always be of the strong type In compliance with local laws the welder must be an authorized person A bad...

Страница 21: ...devices must be installed by the installer according to the current local laws The interconnecting wires shall be protected by a tube or an electrical cable conduit cable tray etc ELECTRICAL DATA CCHB...

Страница 22: ...power supply 2 single phase wires 230V 1 N 4 three phase wires 400V 3 N 1 Ground 2 Ground wire can go by main power supply 3 Curve D thermal circuit breaker differential 4 Main switch 5 Available powe...

Страница 23: ...RIFUGAL FAN IOM_CCHBA CCHA_201a1201_208029_200201_EN INSTALLATION ELECTRICAL CONNECTION DIAGRAM pGD1 control or Mini pGD options Connection to pGD1 with 6 wire telephone cable for lines longer than 50...

Страница 24: ...will not covered by Hitecsa s warranty The unit must not be supplied with any other voltage than that indicated on the serial plate The power supply to the unit must be within 10 of the voltage indica...

Страница 25: ...ours of operation Observe at least 3 cooling cycle operations Due to the unit has frequency converters it is essential that the protection be at least 300mA to prevent power cuts caused by the activat...

Страница 26: ...se the set screws of the motor pulley and turn the movable flange Open or close depending on the needs Open speed decreases 3 Tighten set screws 4 Place the belt in the pulley channel The closure or o...

Страница 27: ...ive or negative that shall be added to the value of the probe A value equal to zero will not change the value of the probe Press keys FAN ON OFF and keep them pressed until a password is required Ente...

Страница 28: ...ral button to select the desired schedule type Select if you want a different schedule day by day the same schedule for all week displays all days or one from Monday to Friday and other from Saturday...

Страница 29: ...cheaper Setpoint value 8 30 t3 Start up or return to the normal setpoing 13 15 t4 Stop due to absence or setting down to a cheaper Setpoint value 15 30 t5 Start up or return to the main Setpoint valu...

Страница 30: ...essure switch alarm circuit 1 Air air ALF7 Thermal alarm of the indoor fan Air air ALF6 Thermal alarm of the external fan compressor Air air ALPM Minimum pressure switch alarm Air air ALRF Lack of ref...

Страница 31: ...n retrocedes un nivel en la pantalla principal muestra la ayuda FLECHA ARRIBA Movimiento en los men s o modificaci n de valores de los par metros de regulaci n TECLA ENTER Confirmaci n de los valores...

Страница 32: ...y Day Time schedule pGD1 models as standard HIT005 You will have 4 types of start in time schedule and when the time schedule is ON the screen will display the word PHASE A Manual type by selecting th...

Страница 33: ...tpoint that it is inside the section and the external out from the section Example From Monday to Thursday the program num 1 is activated internal Setpoint from 6 30 to 11 00 etc D ON OFF schedule typ...

Страница 34: ...r set back one hour form 03 00 to 02 00 Example DST of 60 min Enabled from the first Monday of February at 10 00 goes off at 11 00 until the last Sunday of October at 3 00 goes back at 2 00 Time sched...

Страница 35: ...he three keys until the screen of the next image right is displayed change the value Display address setting from 32 to 00 3 Remove the voltage of the board 4 Press the two keys alarm UP and give volt...

Страница 36: ...cription pGD1 Optional HITSAA01 ALARM MESSAGES pGD1 Optional HITSAA01 Displayed message Type Alarms Clock card error or not connected Warning Alarms Probe B01 broken or disconnected Warning Alarms ThT...

Страница 37: ...Alarm General Alarm of the Burner Alarm Severe Damaged Memory indication Warning Missing Clock or not working Alarm Maintenance of the unit Only indication Warning Alarms Severe Return Temperature Pr...

Страница 38: ...important components of the system and register them on the maintenance sheet compressor discharge and aspiration expansion valve exchangers inlet and outlet etc Compressor Check regularly the lubric...

Страница 39: ...st once a year Take into account the meteorological conditions e g in areas where falling leaves or the flight of seeds may obstruct the drain trap it will also be necessary to clean them at mid and l...

Страница 40: ...cuum pump If leakage symptoms appear during operation proceed to a leak test A HCF detector is necessary in case of small leaks If a gas leak is detected proceed to removing and recuperating the entir...

Страница 41: ...edly lethal There is risk of suffocation at higher concentrations due to the oxygen content reduction at the atmosphere Remove victim to fresh air keep it warm and at rest Supplemental oxygen if it is...

Страница 42: ...mage Keep a temperature below 50 C Protective Clothing Wear overalls protective waterproof gloves and protective goggles or a mask Accidental Release Measures It is important to wear protective clothi...

Страница 43: ...43 IOM_CCHBA CCHA_201a1201_208029_200201_EN CCHBA CCHA HORIZONTAL CONDENSER UNITS WITH COMPRESSOR AND CENTRIFUGAL FAN We reserve the right to add modifications without prior notice...

Отзывы: