26
CCHBA-CCHA
HORIZONTAL CONDENSER UNITS
WITH COMPRESSOR AND CENTRIFUGAL FAN
IOM_CCHBA- CCHA_201a1201_208029_200201_EN
OPERATION
ADJUSTMENT OF FAN TRANSMISSION
Adjust transmission so that indoor fan-motor reaches its nominal value.
If consumption is lower than the nominal value, the airflow is too low.
MODELS
Outdoor
Indoo
r
Nominal
Pulley
Belt
Open
kW
A
Fixed
Variable
CCHBA 751
X
1,50
3,60
150 E25 1A
75/100 E24 1A
A-45
0
CCHBA 801
X
1,50
3,60
150 E25 1A
100/125 E24 1A
A-45
2
CCHBA
1001
X
2,20
4,70
150 E25 1A
100/125 E28 1A
A-46
1
CCHBA
1201
X
4,00
9,20
160 E30 2A
100/125 E28 2A
A-46
2
-
To change fan speed
:
1. Remove the belt. Move the motor along its track (or loosen the tensor set screw) in order to release it.
2. Loose the set screws of the motor pulley and turn the movable flange. Open or close depending on the
needs (Open: speed decreases).
3. Tighten set screws.
4. Place the belt in the pulley channel. The closure or opening of the pulley could void the size of the prior
belt. In this case, replace it for other belt of the same profile and with the appropriate length.
5.
Tighten the belt by using tensor screw or sliding the motor, depending on the case.
-
To align fan and motor pulleys
:
1. Loose fan pulley set screws.
2. Slide fan pulley along the shaft and align it with motor by using a ruler in order to ensure that is parallel
to the belt.
3. Tighten fan pulley set screws.
- Adjust belt tension
:
1. Loose motor mounting plate bolt and slide it.
2. Belt flexion millimeters is estimated by dividing S by 40.
1. Motor
2. Motor pulley
3. Transmission belt
4. Fan pulley
5. Tensor set screw
6. Set screw
WRONG
WRONG
WRONG ALIGNEMENT
CORRECT RULER POSITION