TÜV-A 03 ATEX 0019X
♦
cbr2052a0600p_01
♦
36/7
3. TECHNICAL DATA
Rod probe
Light cable probe
Heavy cable probe
Range
0.2 ... 3 m
1 ... 20 m
Process connection
St.St. DIN 1.4571
Material of wetted
parts
Probe
Fully or partially PFA coated St. St.
(DIN 1.4301)
Fully or partially FEP coated St. St. cable
PE coated steel cable
Enclosure material
Aluminium casting, Plastic (PBT), glass fibre reinforced (PBT)
Medium temperature (See: temp. diagram)
standard: -30
°
C ... +130
°
C, high temperature: – 30
°
C ... +200
°
C
– 30
°
C ... +80
°
C
Pressure (See pressure diagram)
maximum 4 MPa (40 bar) +20
°
C
maximum 1.6 MPa (16 bar)
Ambient temperature (See temp. diagram
-25 °C ... + 70 °C
Maximum tensile load
–
7.7 kN
45 kN
Saturation capacitance of the probe
~600 pF/m
~200 pF/m
~600 pF/m
Analogue: 4 ... 20 mA. 2-wire (3.9 … 20.5 mA),
R
max
= U
t
– 11.4 V / 0.02 A isolated, protection against power supply transient
Test connection for loop current 2 mm-socket, output voltage: 1 mV / 1 mA
SAP-202 display module: 6-digit LCD, engineering units and bargraph
Output
HART feature, load resistance
≥
250 ohm
Voltage output for current test
Voltage measurement on serial resistance: 1 mV / 1 mA
Capacitance range
0 pF ... 5 nF
Range of transmitted capacitance
10 pF, or 10% (min. SPAN)
Damping
0, 3, 6, 10, 30, 60, 100, 300 s
Fault indication
Blinking of COM and VALID LED and
transmitting 3.8 or 22 mA fault indication current selected by programming
Power supply / current consumption
12 ... 36 V DC, maximum 22 mA / 48 … 800 mW
Accuracy
± 0.3 % (related to the length of the probe)
Temperature coefficient
± 0.02% / °C
Electric connection
Pg 16 cable gland or M 20 x 1.5 or 2 x ½” NPT thread for cable protection tube.
Cable diameters
∅
8 ...
∅
15 mm, or.
∅
6 ... 12 mm
∅
9.5...
∅
10 mm
wire cross section: 0.5 … 1.5 mm
2
shielded cable suggested
Process connection
1" NPT or BSP
1½" NPT or BSP
Ingress protection
Probe: IP 68, Enclosure: IP 67
Electric protection
Protection Class III
Mass
2.3 kg with 0.5 m probe
1.9 kg with 3 m probe
4.5 kg with 3 m probe
Содержание Nivelco Nivocap C-200
Страница 2: ...2 36 TÜV A 03 ATEX 0019X cbr2052a0600p_01 ...