Caution:
Storage system fans rotate at high speed. Exercise extreme caution
to avoid getting anything caught in the fan and to prevent injury.
Procedure
1.
Gain access to the inside of the rack.
2.
Open the front bezel of the storage system.
3.
Confirm that the storage system fans are rotating
4.
Close the front bezel, and then close the rack.
Battery replacement guidelines
Each controller contains a sealed battery that provides backup power to
cache memory. You must replace the battery every three years.
Note:
Do not disassemble the battery; otherwise, you could get burned or
receive a shock.
If the storage system does not receive power for more than six months, the
battery can become discharged and possibly damaged. To avoid this
situation, charge the battery for more than three hours at least once every
six months.
Checking for loose or damaged cables or connectors
It is good practice to check cables for damage on a periodic basis. Confirm
that all cables and cable connectors are in good condition and connected
securely to the appropriate interfaces.
Restarting the storage system
Before restarting the storage system, wait at least one minute with the main
switch off (amber
POWER
LED is off).
Storing the storage system
If the storage system does not receive power for more than six months, the
battery can become discharged and possibly damaged. To avoid this
situation, charge the battery for more than three hours at least once every
six months.
Note:
Do not store the equipment in an environment with temperatures of
104ºF (40ºC) or higher because battery life will be shortened.
General maintenance
311
Service Guide for VSP Gx00 and VSP Fx00 Models
Содержание Virtual Storage Platform F400
Страница 4: ...4 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 22: ...22 Preface Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 106: ...106 Replacing storage system components Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 140: ...140 Replacing a fan Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 146: ... CBLM CBLH 146 Replacing a power supply Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 160: ...160 Replacing a power supply Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 198: ...6 Click Block 198 Replacing cache memory Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 222: ...222 Replacing a small form factor pluggable SFP Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 250: ...250 Replacing a SAS cable Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 260: ...260 Replacing cache flash memory Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 268: ...268 Replacing a LAN blade Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 278: ...278 Replacing a backup module Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 284: ...284 Replacing a PCIe module Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 296: ...296 Replacing a PCIe cable connector Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 302: ...302 Replacing a PCIe cable Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 312: ...312 General maintenance Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 395: ...CBSS CBSSD controller Warning labels on the storage system 395 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 396: ...CBSL CBSLD controller 396 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 397: ...Warning labels on the storage system 397 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 398: ...CBLM controller CBLH controller 398 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 401: ...Flash module drive tray Warning labels on the storage system 401 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 402: ...Dense intermix drive tray 402 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 405: ...Warning labels on the storage system 405 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 410: ...PCIe switch board 410 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 411: ...NAS module Warning labels on the storage system 411 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 412: ...412 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 417: ...Service Guide for VSP Gx00 and VSP Fx00 Models ...