– 49 –
6. Microcpomputer's Peripheral Circuits
6-1. Overload control circuit (OVL control circuit)
Overload control is to decrease the speed of the compressor and reduce the load when the load on
the air conditioner increases to an overload state, in order to protect the compressor, electronic
components and power breaker.
Overloads are judged by comparing the DC current level and set value.
Fig.6-1 shows the overload control system configuration and Fig. 6-4 is a characteristic diagram on
overload judgement values. There are two types of control which has named IS OVL and ID OVL.
IS OVL is limiting the whole input of this room air conditioner system through the current sensor CT1
in order to keep the maximum rating of components by reading total operating current.
ID OVL is watching and limits the compressor current through the detection resistor, which is built in
IPM in order to control the compressor reliability. Since the compressor reliability is related with its
speed, the ID OVL value is also linked with the compressor speed. Fig. 6-2 shows an ID OVL limitation
curve.
All of OVL operation values were programmed into EEPROM memory.
Compressor
Microcomputer
EEPROM
Motor current (ID)
Whole current (IS)
Fig. 6-1 Overload Control System
Detection
resistor
A-D
converter
ID OVL
value
IS OVL
value
Motor
control
process
A-D
converter
Detection
transformer CT1
Amplifier
Smoother
Содержание Summit RAC-35YH6
Страница 17: ... 15 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAS 35FH6 INDOOR UNIT ...
Страница 22: ...RAS 35FH6 CIRCUIT DIAGRAM 20 08A392_05_RAS_35FH6_20 21_A2_E 2008 2 22 18 40 20 ...
Страница 25: ... 23 button 25 26 26 27 28 26 RAS 35FH6 08A392_07_RAS_35FH6_23_A3_E 2008 3 7 10 07 23 ...
Страница 92: ... 90 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAS 35FH6 ...
Страница 96: ...HITACHI AW NO 0025E RAS 35FH6 RAC 35YH6 ...