Installation
Technical Catalogue
6
33
TCGB0051 rev 0 - 09/2009
CAUTION:
In case of connecting some units to the same water piping, design the water piping so that the water distribution to each unit
is equal (refer to figure below) Imbalance of water distribution may cause a serious damage like a water freezing in the heat-
exchanger.
6.3. Minimum internal system water volume
To ensure the cooling operation at least 5 minutes without interruption, the internal chilled water volume in the piping
system should be greater than the minimum volume as shown below.
NOTE:
Minimum internal system water volume written above is for standard ON/OFF differential, minimum internal system water volume
shall be increased by the setting of differential.
Model RCUE - CLG2
40
50
60
80
100
120
Chilled Water Flow Range
Min.
m
3
/h
15.5
18.7
23.2
31.0
37.4
46.4
Max.
m
3
/h
34.4
41.6
51.6
68.8
83.2
103.2
Minimum Internal Water Volume
m
3
0.38
0.46
0.57
0.76
0.92
1.15
Internal Water Volume of Cooler
litre
13.7
15.2
19.5
32.4
40.8
40.8
Chiller Unit
Water Pump
Heat Load Side
Содержание SAMURAI CLG2
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 10: ......
Страница 12: ......
Страница 46: ......
Страница 62: ......
Страница 66: ......
Страница 82: ......
Страница 94: ...Drawings Technical Catalogue TCGB0051 rev 0 09 2009 94 14 2 4 Main printed circuit board ...
Страница 95: ...Drawings Technical Catalogue 14 95 TCGB0051 rev 0 09 2009 14 2 5 Relays printed circuit board ...
Страница 98: ......
Страница 112: ......
Страница 116: ......
Страница 117: ......