2 SPECIFICATIONS
2-2
2.1 Use
Before using the IR.LINK module (type: LQE046), make sure that the IR.Station module (LQS021)
is connected. It communicates digital or analog data with the IR.Station. It also supports a
function that starts up a task upon the detection of a change in digital input.
2.2 Specifications
2.2.1 System
specifications
Item Specifications
Type LQE046
Number of networks
1 network/module
Maximum number of IR.LINK module
that can be mounted in the CPU
1 (install from the leftmost slot)
Mass 260
kg
2.2.2 Line
specifications
Item Specifications
Transmission method
Serial transmission (bit serial transmission)
Electrical interface
RS-485
Number of stations
Up to 31 stations
Line type
Two pairs of shielded twisted-pair cables
Recommended cable: KPEV_SB 2P 0.5 mm
2
(Hitachi Cable, Ltd.)
Distance
The distance depends on the transmission rate as follows:
Transmission rate
≤
1.0 Mbps: Up to 240 m
Transmission rate
≤
0.5 Mbps: Up to 480 m
Transmission rate
≤
0.25 Mbps: Up to 800 m
Transmission rate
≤
0.125 Mbps: Up to 1000 m
Connection cable
Terminal
block
6-point terminal block (M3
×
6)
Содержание S10mini IR.LINK
Страница 1: ......
Страница 2: ......
Страница 13: ...1 BEFORE USE ...
Страница 17: ...2 SPECIFICATIONS ...
Страница 19: ...3 NAMES AND FUNCTIONS OF EACH PART AND CABLING ...
Страница 25: ...4 USER GUIDE ...
Страница 36: ...5 OPERATION ...
Страница 46: ...6 MAINTENANCE ...
Страница 60: ...APPENDIX ...