Front Panel
Unit Body
Any gap will lead to leak or frost.
model
Liquid pipe
Gas pipe
0.8/1.0/1.3/1.5
10
Stoppers
1.8/2.0/2.3
unit:mm(in.)
(4) Slightly lift the front panel upward in order
to release the combined parts of upper side of the
front pane
(3) There are three stoppers inside of the front
panel.Check to ensure that there is no gap between
front panel and unit body.
4.3.4 Install Front Panel
(1) Firstly, put the two joints of the front panel
back into the grid, and then push inside to make the
two one tightly fasten.
(2) Press front panel down , make the two joints of the
front panel tightly fasten.
5.1 Piping Materials
(1) Prepare locally-supplied copper pipes.
(2) Select the piping size from the following table.
(3) Select clean copper pipes making sure there
is no dust and moisture inside the tubes. Before
connecting pipes,blow the inside of the pipes with
nitrogen or dry air,to remove any dust or foreign
materials.
15.88(5/8)
When removing front panel, do not
forces by hitting, etc.
It may break the unit body.
apply strong
R410A