Make sure air tightness test is performed.

Refrigerant R410A is non-flammable, non-toxic, and odorless, and may produce toxic gases when exposed to

open  flame.  Since  this  refrigerant  gas  is  heavier  than  air,  it  may  result  in  lack  of  oxygen,  thereby  leading  to

breathing difficulties when the area near the ground is filled with this gas. If that's the case, please turn off the

main switch immediately, cut off the power supply, and open the doors and windows for ventilation. Put out any

open  flame,  and  contact  your  service  dealer.  Performing  leak  detection  and  gas  tightness  test  with  oxygen,

acetylene or other flammable and toxic gases may cause explosion, so nitrogen is recommended for this test.

The standards for safe refrigerant leakage in construction and system operation are determined based on local

regulations or standards.

Use ELB with medium or higher sensing speed (ELCB with an operating time of 0.1 seconds or less), or

electric shock or fire may arise.

For installation, the refrigerant piping must be firmly connected before the operation of compressor. For repair,

the refrigerant piping must be moved, handled and removed after the stop of compressor.

Please don't short-circuit the protective device (e.g., 

the 

pressure switch, etc.) during operation, since this

may

 

cause fire or explosion.

Do not use any sprays such as insecticide, lacquer, hair spray or other flammable gases within approximately 

one (1) meter from the system.

If the earth leakage breaker (ELB) is frequently activated, please stop the system and contact your local dealer 

or customer services.

Make sure the ground wire is securely connected. The improper grounding of machine may lead to electrical 

failure. Please don't connect the ground wire to gas pipes, tap water pipes, lightning rods or phone ground 

wires.

Make sure there are no flammable materials around during brazing operation. Please wear leather gloves to 

prevent frostbite when filling refrigerant.

Prevent rats or other small animals damaging the wiring and electrical components. Bitten unprotected parts 

may cause a fire.

Firmly fix the connection wires. The external force of terminal may result in looseness of terminal that may 

cause a fire.

Make sure the air conditioner is installed with enough strength of fixation; otherwise, the air conditioner may 

fall or topple over, which may bring about machine damage or personal injury.

Please follow the installation instructions and related regulations and standards for electrical construction; 

otherwise, electrical failure or fire may occur due to inadequate capacity or inconsistent specifications. 

Neve

r

 fail to use specified wiring and select correct wiring, since failure to do so may cause electrical failure or 

fire.
Please make sure the outdoor unit is not covered with snow or ice before use.

Please don't perform installation works such as refrigerant piping connection, drain pipe connection, and 

wiring connection. Violations may result in system leakage, electrical failure or fire. In the case of fire, please 

turn off the power immediately; please don't touch electrical parts with the hands, or electric shock may arise. 

Do not pour water into the indoor or outdoor unit. This machine is an electric product that may develop serious 

electric failure when exposed to water.

Do not open the service cover of indoor or outdoor units without turning OFF the main power supply; 

otherwise, this may bring about serious safety accident.

Do not touch or adjust safety devices inside the indoor or outdoor units. If they are touched or readjusted, 

serious accident may arise.

Refrigerant leakage may bring about oxygen deficit-induced respiratory difficulty. In case refrigerant leakage is 

detected, please turn off the main switch immediately, extinguish any naked flame, and contact service dealer.

DANGER

WARNING 

Please turn off power supply as soon as possible when a fire breaks out.

Please don't touch electrical components since this may result in electric shock.

This appliance can be used by children aged from 8 years and above and persons with reduced physical, 

sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or 

instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall 

not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.

The A-weighted emission sound pressure don't exceed 70 dB(A) .

Содержание RPIZ-0.8HNDTS1Q

Страница 1: ...IZ 0 8HNDTS1Q RPIZ 1 0HNDTS1Q RPIZ 1 3HNDTS1Q RPIZ 1 5HNDTS1Q RPIZ 1 8HNDTS1Q RPIZ 2 0HNDTS1Q RPIZ 2 3HNDTS1Q RPIZ 2 5HNDTS1Q This manual is exclusively prepared for R410A indoor unit Please read this manual in conjunction with corresponding manual for outdoor unit ...

Страница 2: ......

Страница 3: ...ded that these are used in accordance with our instructions following the provisions of Directives as amended Manufacturing number and manufacturing year refer to model Nameplate Notes This declaration becomes invalid if technical or operational modifications are introduced without the manufacturer s consent Johnson Controls Hitachi Air Conditioning Europe SAS is authorized to compile technical fi...

Страница 4: ......

Страница 5: ...il Places with inflammable gases Places with sulfurated gases or silicon e g hot spring etc Coastal areas with much salt or places exposed to strong acids or bases that may cause corrosion to machine IMPORTANT NOTICE Signal words DANGER WARNING and CAUTION are used to indicate hazard seriousness Definitions of the hazard levels are provided below with respective signal words Do not have the air ou...

Страница 6: ...inal may result in looseness of terminal that may cause a fire Make sure the air conditioner is installed with enough strength of fixation otherwise the air conditioner may fall or topple over which may bring about machine damage or personal injury Please follow the installation instructions and related regulations and standards for electrical construction otherwise electrical failure or fire may ...

Страница 7: ...ioner to any high power electrical equipment results in extremely high inductive surge voltage in the power cord of air conditioner This air conditioner must be serviced by professional maintenance personnel CAUTION CHECKING PRODUCT RECEIVED This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and ...

Страница 8: ......

Страница 9: ...5 5 6 6 6 6 7 7 6 10 10 10 11 Section2 Installation Maintenance Manual Unit Description Part Name 3 1 Indoor Unit 3 2 Remote Control Before Operation Automatic Control 6 1 6 2 6 3 6 4 4 ...

Страница 10: ...12 12 12 13 13 14 14 15 v Protection and Control Devices Field Operation 10 3 Setting of External Static Pressure 16 ...

Страница 11: ...ve been left unused for a long period of time shall be electrified for more than 12 hours before startup Do not start the machine immediately after power on since this may cause damage to compressor due to inadequate warm up of lubricating oil Please check if the outdoor unit is covered with ice or snow If yes please remove the ice or snow with warm water However the water temperature shall not ex...

Страница 12: ...2 Fig 3 1 Low height ceiling Ducted Indoor Unit Models 0 8 1 3 Model 1 5 Models 1 8 2 5 ...

Страница 13: ...od of time to avoid frosting on indoor heat exchanger Cold Air Prevention To prevent the output of cold air from indoor unit in heating mode the fan runs at low speed The fan speed is set based on outlet air temperature of indoor unit Control of Indoor Fan during Defrosting The indoor fan is out of service during automatic defrosting of outdoor unit Surplus Heat Output from Indoor Unit Upon comple...

Страница 14: ...6 4 ...

Страница 15: ...ntial to remove the moisture dust other refrigerants or refrigerant oils from the refrigeration system Hence the failure to use specified materials and tools may result in explosion personal injury refrigerant leakage electrical failure or fire DANGER Note When in immediate contact with refrigerant please use the installation tools and instruments dedicated to the new refrigerant ...

Страница 16: ...2 5 Install the indoor unit as per national standard Please contact the dealer if the accessories are not delivered with machine 6 Magnet Ring ...

Страница 17: ...nt manner Indoor unit must be so positioned that the indoor temperature is distributed evenly There should be no obstruction that blocks air flow indoors and at air vent Install suspension bolts as shown in Fig 4 2 For Concrete Slab 150 to 160mm Steel Insert 100 to150kg Concrete Anchor Bolt W3 8 or M10 For Steel Beam Suspension Bolt W3 8 or M10 l Beam For Wooden Beam Wooden Rib 60 to 90mm square t...

Страница 18: ... 4 3 a Suspension Bolt Size 410 Suspension Bolt Size Outgoing Direction Top View Fig 4 3 Suspension Bolt 4 3 3 Installation of Indoor Unit Indoor unit is installed as shown in Fig 4 4 Installation of Field Supplied Parts Suspension Bolt 4 M10 or W3 8 Nut 8 M10 or W3 8 Washer 8 M10 or W3 8 Fig 4 4 Installation of Indoor Unit 1 How to Install Suspension Bolt and Nut Mount nuts to the four bolts as s...

Страница 19: ...oor unit is slightly lower than its front part by 0 5mm so as to facilitate drainage 3 Tighten the suspension nut upon completion of adjustment It s essential to apply thread locking agent to avoid nut looseness Please cover the machine with plastic cloth during installation so as to keep it clean 4 3 5 Air Duct Connection Air duct is connected to indoor unit via canvas hose to effectively isolate...

Страница 20: ...ng flaring connected for off factory installation is adjusted as compared with R22 and R407C Please perform the processing operation based on the dimensions shown below See Fig 5 3 As shown in Fig 5 4 two spanners shall be used for tightening the nut Fig 5 4 Nut Tightening Torque Insulate the refrigeration piping with field supplied insulating pipe as shown in Fig 5 5 upon completion of refrigeran...

Страница 21: ...l be fabricated at installation site and placed under the indoor unit as shown in Fig 6 2 Indoor Unit Auxiliary Drain Pan Field Supplied Drain Outlet Fig 6 2 Water pan Power on Fill the water pan with 2L or 2 5L of water Check and ensure the water flows without obstruction and no leakage exists Pour 2L of water if no water flows out of pipe end Drain Lift Pipe PVC Pipe VP25 Field Supplied Field Su...

Страница 22: ...d thereby cause fire Do not use the power terminal strip used for the air conditioner to sub connect any power cable but use power branch box to sub connect power wire at indoor unit side instead and be sure to calculate wire capacity or otherwise too low capacity may cause fire The system shall not be started until all inspections have been performed properly Wrap the accessory packing around the...

Страница 23: ... 50 60Hz Indoor Unit Indoor Unit Capacity HP Capacity of Fuse on Indoor Unit Control Circuit Freeze Protection Temperature Cut out Cut in Set Temperature Difference 220 240V 50 60Hz Terminal Block TB Entwine the magnetic ring 3 turns at wires L and N of power cord The View of D Direction Communication Wire Remote Controller Wire Cord Clamps Power Wire ...

Страница 24: ...ication circuit shall not be lower than that for RVV S P shielded wires or equivalent and the shielding layer shall be grounded 6 A switch that can ensure all pole disconnection shall be installed between power supply and air conditioning unit in such a manner that the contact spacing shall not be less than 3mm 7 Once the power cord is damaged the dealer or the professionals from designated mainte...

Страница 25: ...witch must be set with power sources of the indoor and outdoor units in OFF state Otherwise the settings are invalid 2 DIP switch positions are shown in the figure below 3 a c Model code setting DSW4 No setup is required The code is set before delivery d b e ...

Страница 26: ... 00 Default 01 0 8 1 5 1 8 2 5 The static pressure can be changed by setting the external static pressure C5 on the wired remote control Please refer to the installation and maintenance manual for wired remote control Indoor Unit Capacity HP External Pressure Settings of Wired Remote Control ...

Страница 27: ......

Страница 28: ...g Systems Co Ltd Add No 218 Qianwangang Road Economic and Technological Development Zone Qingdao China The Company is committed to continuous product improvement We reserve the right therefore to alter the product information at any time and without prior announcement ...

Отзывы: