Do not use any sprays such as insecticide, lacquer, hair spray or other flammable gases within approximately one (1) 

meter from the system.

If the earth leakage breaker (ELB) is frequently activated, please stop the system and contact your local dealer or 

customer services.

Make sure the ground wire is securely connected. The improper grounding of machine may lead to electrical failure. 

Please don't connect the ground wire to gas pipes, tap water pipes, lightning rods or phone ground wires.

Make sure there are no flammable materials around during brazing operation. Please wear leather gloves to prevent 

frostbite when filling refrigerant.

Prevent rats or other small animals damaging the wiring and electrical components. Bitten unprotected parts may cause 

a fire.

Firmly fix the connection wires. The external force of terminal may result in looseness of terminal that may cause a fire.  

Please follow the installation instructions and related regulations and standards for electrical construction; otherwise, 

electrical failure or fire may occur due to inadequate capacity or inconsistent specifications.

Never fail to use specified wiring and select correct wiring, since failure to do so may cause electrical failure or fire. 

Please make sure the outdoor unit is not covered with snow or ice before use.

This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or 

mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning 

use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. 

Cleaning and user maintenance shall not be made by children without supervision.

The A-weighted emission sound pressure don't exceed 70 dB(A) .

Do not stamp on the machine or place sundries thereon.

Do not put extra materials on or in the machine.

Rooms are recommended to be ventilated once every 3-4 hours.

NOTE:

Heat pump air conditioners may malfunction under the following conditions:

* The power available from power transformer is less than or equal to the electrical power of air conditioner.

* The excessively short distance from the power cord of air conditioner to any high-power electrical equipment results in

extremely high inductive surge voltage in the power cord of air conditioner.

This air conditioner must be serviced by professional maintenance personnel.

CHECKING PRODUCT RECEIVED

Upon receipt of this product, check it for any shipping damage.

Claims for damage, either apparent or concealed, should be filed immediately with the shipping company.

Check the model number, electrical parameters (power supply, voltage, and frequency) and accessories to

determine if they are correct.

The standard operation method for the machine is described in the present manual. Please contact local

dealer when problem arises.

Our company shall not be held responsible for any consequence of the modification to machine performed

without its written consent.

WARNING 

CAUTION


Содержание RPIH-3.0HNAUB1Q

Страница 1: ...Q RPIM 2 0HNAUB1Q RPIM 2 3HNAUB1Q RPIM 2 5HNAUB1Q RPIH 3 0HNAUB1Q RPIH 3 3HNAUB1Q RPIH 4 0HNAUB1Q RPIH 5 0HNAUB1Q RPIH 6 0HNAUB1Q This manual is exclusively prepared for R410A indoor unit Please read this manual in conjunction with corresponding manual for outdoor unit P01974Q ORIGINAL INSTRUCTIONS ...

Страница 2: ......

Страница 3: ...iculties when the area near the ground is filled with this gas If that s the case please turn off the main switch immediately cut off the power supply and open the doors and windows for ventilation Put out any open flame and contact your service dealer Performing leak detection and gas tightness test with oxygen acetylene or other flammable and toxic gases may cause explosion so nitrogen is recomm...

Страница 4: ...sory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall not be made by children without supervision The A weighted emission sound pressure don t exceed 70 dB A Do not stamp on the ...

Страница 5: ... 2 Remote Control Before Operation Operation Mode Auto Control Cleaning of Filter 7 1 Removing Filter 7 2 Cleaning Filter 7 3 Resetting Filter Indicator 8 1 If Trouble Still Remains 8 2 No Operation 8 3 Not Cooling or Heating Well 8 4 This is Not Abnormal ...

Страница 6: ...6 6 7 7 7 7 7 8 8 10 10 11 12 13 13 13 14 14 14 15 16 15 Section 2 Installation Maintenance Manual Wiring for Static Pressure Protection and Control Devices Field Operation ...

Страница 7: ... can consist of one outdoor unit and several indoor units Detailed configurations are stated in the corresponding installation maintenance manual for outdoor unit This heat pump type air conditioner is applicable for refrigeration heating dehumidification and air supply etc These features are controlled with a remote control option 3 Part Name 3 1 Indoor Unit Refer to Fig 3 1 Ceiling Ducted Indoor...

Страница 8: ...Models 0 8 2 5 Models 3 0 6 0 Fig 3 1 Ceiling Ducted Indoor Unit ...

Страница 9: ...ompressor that runs for less than 3 minutes can be brought out of service with the remote control Oil Return Operation When an indoor unit is out of service for more than 2 hours during refrigeration it will run for a few minutes automatically to prevent the detention of refrigeration oil in the indoor unit in stopped state 3 Freeze Protection during Refrigeration When the outlet air temperature o...

Страница 10: ...t water of which the temperature is above approx 40 C Step 2 Whisk the water off and air dry the filter in a space exposed to no sunlight 7 3 Resetting the Filter Indicator Press the Reset key after the cleaning of filter The filter indicator FILTER disappears while the time of next cleaning of filter is set automatically 8 1 If Trouble Still Remains If the trouble still remains even after checkin...

Страница 11: ...8 4 5 ...

Страница 12: ...e failure to use specified materials and tools may result in explosion personal injury refrigerant leakage electrical failure or fire 6 No Tool No Tool Handsaw Phillips Screwdriver Vacuum Pump Refrigerant Gas Hose Megohmmeter Copper Pipe Bender Water Pump Pipe Cutter Brazing Kit Hexagon Wrench Spanner Charging Cylinder Gauge Manifold Cutter for Wires Gas Leak Detector Leveller Clamper for Solderle...

Страница 13: ...7 2 5 Install the indoor unit as per national standard Please contact the dealer if the accessories are not delivered with machine possible ...

Страница 14: ... so positioned that the indoor temperature is distributed evenly There should be no obstruction that blocks air flow indoors and at air vent Install suspension bolts as shown in Fig 4 2 For Concrete Slab 150 to 160mm Steel Insert 100 to150kg Concrete Anchor Bolt W3 8 or M10 For Steel Beam Suspension Bolt W3 8 or M10 l Beam For Wooden Beam Wooden Rib 60 to 90mm square timber Wooden Beam Suspension ...

Страница 15: ...3 Installation of Indoor Unit Indoor unit is installed as shown in Fig 4 4 Installation of Field Supplied Parts Suspension Bolt Nut Washer 4 M10 or W3 8 8 M10 or W3 8 8 M10 or W3 8 Suspension Bolt 4 M10 or W3 8 Field Supplied Nut and Washer 4 M10 or W3 8 Field Supplied Support Leg Fig 4 4 Installation of Indoor Unit 1 How to Install Suspension Bolt and Nut Mount nuts to the four bolts as shown in ...

Страница 16: ...er the machine with plastic cloth during installation so as to keep it clean 4 3 5 Air Duct Connection Air duct is connected to indoor unit via canvas hose to effectively isolate noise and vibration Indoor unit is designed with flange with hole connectible to air duct Example Canvas Air Duct Canvas Air Duct Plenum Chamber Volume Damper Plenum Chamber Outside Air Service Access Return Air Inlet For...

Страница 17: ...3 3 Fig 5 2 Pipe Size 4 0 6 0 Since the nut cap connected at gas pipe is designed exclusively for R410A the piping flaring connected for off factory installation is adjusted as compared with R22 and R407C Please perform the processing operation based on the dimensions shown below See Fig 5 3 Pipe Diameter a Flaring Diameter D Fig 5 3 Flaring 2 As shown in Fig 5 4 two spanners shall be used for tig...

Страница 18: ...t Elevated Portion Incorrect 1 25 1 100 Downward Inclination Connecting Drain Pipe Shared Drain Pipe Drain pipes shall be separated from other pipes Correct Fig 6 1 Drain Pipe Where the relative humidity of air inlet or ambient air exceeds 80 an auxiliary drain pan shall be fabricated at installation site and placed under the indoor unit as shown in Fig 6 2 Indoor Unit Auxiliary Water Pan Field Su...

Страница 19: ...acity or otherwise too low capacity may cause fire The system shall not be started until all inspections have been performed properly Wrap the accessory packing around the wires and plug the wiring connection hole with the seal material to protect the product from any condensate water or insects Secure the cable of the remote control switch using the cord clamp inside the electrical box Tighten sc...

Страница 20: ...ber 1 Socket Motor line Fig 7 3 Switching of External Static Pressure AC CONTACTOR Capacity of Fuse on Indoor Unit Control Circuit Temperature Control on Fan Motor of Indoor Unit Cut out Cut in Cut out Cut in Freeze Protection Temperature Set Temperature Difference RPIM 0 8 2 5HNAUB1Q RPIH 3 0 6 0HNAUB1Q Static Pressure Pa Plug Wording Static Pressure Pa Plug Wording RPIM 0 8 1 5 HNAUB1Q RPIM 1 8 ...

Страница 21: ...at can ensure all pole disconnection shall be installed between power supply and air conditioning unit in such a manner that the contact spacing shall not be less than 3mm 7 Once the power cord is damaged the dealer or the professionals from designated maintenance department must be contacted in a timely manner for repair and replacement 8 For the installation of power cord the ground wire must be...

Страница 22: ...delivery H LINK II H LINK II In the case of applying high voltage to terminals 1 and 2 of TB2 the fuse on the PCB is cut In such a case firstly connect the wiring to TB2 and then turn on NO 1 pin The indoor unit numbers of all indoor units are not required The indoor unit numbers are set by the auto address function If the indoor unit number setting is required set the unit numbers of all indoor u...

Страница 23: ......

Страница 24: ...g Systems Co Ltd Add No 218 Qianwangang Road Economic and Technological Development Zone Qingdao China The Company is committed to continuous product improvement We reserve the right therefore to alter the product information at any time and without prior announcement ...

Отзывы: