background image

4.3.3 Hanging Indoor Unit

Install the indoor unit and the support

board  using bolts (M12)as shown in Fig
4.4.
Adjust the indoor unit installed to the 

preconcerted  height.
Hook the suspendion bracket to the nut

and washer of rach hanging bolt.

Check to ensure  the indoor unit is
horizontally.

If the indoor unit is not horizontal,it may 

cause a  leakage.
Adjust theangle of the  indoor unit  using 
the gradienter or polyethylene pipe .

Screw down the nuts.

Tighten the bolts of the sling nuts with  
]the suspension brackets after 
Adjustment is completed.
Special plastic paint must be applied to 
the bolts in order to prevent them  from 

Loosening.

7

Polyethylene Pipe

Drain Pipe Sleeve

Polyethylene Pipe

A   B

Drain Pipe

Sleeve

Setscrew(M12)

(Field Supply)

Nut(Field Supply)

Suppord Board

(Field Supply)

Washer(Field Supply)

Nut×2(Field Supply)

Sling Bolt

Bolt:M12

A:0-14mm, B:0-36mm

Fig4.5 Install

a

tion Methods

Fig4.4 Hanging Methods

Содержание RPI-16 0KFNQH

Страница 1: ...本号 签字区 签字区 签字区 签字区 签名 签名 签名 签名 日期 日期 日期 日期 设计 潘翠连 2013 12 05 审核 陈 林 2013 12 09 标准化 霍艳萍 2013 12 06 批准 前田宪作 2013 12 10 变更履历 变更说明书时 请填写 标记 管理编号 日期 更改 审核 批准 2 BZ KF1412 027 14 12 08 赵怀杰 陈 林 前田宪作 2 本次变更 内容简述 变更内容简要描述 涉及页码 备注 担当联络方式 0532 8087 5223 邮箱 hanqin2 hisensehitachi com BZ KF 1804 216 18 04 08 张利娜 陶友淘 邓玉平 说明书大批量清洗 核查并修改低级错误 目录 内容字母掉字勘误 内容字母漏掉空格 P7 P8 BZ KF 1909 027 19 09 17 韩芹 张利娜 陶友淘 3 ...

Страница 2: ...RPI 16 0KFNQL RPI 16 0KFNQH RPI 20 0KFNQL RPI 20 0KFNQH RPI 20 0KFNQLF RPI 20 0KFNQHF P00682Q IN THE CEILING TYPE ...

Страница 3: ......

Страница 4: ...EU Directives as amended Manufacturing number and manufacturing year refer to model Nameplate Notes This declaration becomes invalid if technical or operational modifications are introduced without the manufacturers consent Johnson Controls Inc is authorised to Compile the Technical Construction File Add Westendhof 3 45143 Essen Germany Name Surname Position Title Director Date April 15 2016 Qingd...

Страница 5: ...I 20 0KFNQHF 7 43 21 43 7 15 7 The indoor unit has been designed for the following emperatures Running Cooling Operation Heating Operation The indoor unit will stop when the temperature outside is lower than The indoor unit can be only used with the outdoor unit as follows Indoor Unit Outdoor Unit ...

Страница 6: ...ng to the appropriated local or national regulations in an environmentally correct way Due to refrigerant oil and other components contained in the Air Conditioner its dismantling must be done by a professional installer accordingly to the applicable Contact the Customer Care for more information regulations HITACHI ...

Страница 7: ...1 2 2 3 4 3 3 3 6 5 4 9 8 8 10 11 11 12 14 14 15 ...

Страница 8: ...d by thunder may bring a mechanical failure Make sure the refrigerant as stated Do not charge the air or other gases into the refrigerant cycle These types of gases can cause unwonted high pressure or an explosion Do not install the indoor unit outdoor unit remote controlswitch and cable within approximately 3 meters from strong electromagnetic wave radiatoes such as medical equipment Do not touch...

Страница 9: ...2 MODEL Refrigerant Gas Pipe Connection A Refrigerant Liquid Pipe Connection B Indoor unit 16 0 20 0 ...

Страница 10: ...3 R410A ...

Страница 11: ...4 Including Two Remote Temperature Sensors 2 5 ...

Страница 12: ...door unit and components as far as practical or at least 3meters from the electromagnetic wave radiator C Prepare a steel box and install the remote control switch in it Prepare a steel conduit tube and wire the remote control cable in it Thenÿconnect the ground wire with the box and the tube D Install a noise filter when the power supply emits harmful noises To avoid any corrosive action to the h...

Страница 13: ...ough to support the indoor unit Plase reinforce the ceiling before installation if it is not safe 3 Install the indoor unit 2 5 meters higher from the floor level when exposed outdoor 4 Strainer Field Supply must be installed in the pipeline Make sure the the outdoor air through the strainer A B C 520 635 130 620 735 230 Ceiling Anchor Bolt Long Nut or Thread Take Up Suspension Bolts Indoor Unit F...

Страница 14: ...t theangle of the indoor unit using the gradienter or polyethylene pipe Screw down the nuts Tighten the bolts of the sling nuts with the suspension brackets after Adjustment is completed Special plastic paint must be applied to the bolts in order to prevent them from Loosening 7 Polyethylene Pipe Drain Pipe Sleeve Polyethylene Pipe A B Drain Pipe Sleeve Setscrew M12 Field Supply Nut Field Supply S...

Страница 15: ...e duct as follows Air Inlet Connect the duct with flange inlet together Seal the pontes between the flange inlet and duct using the aluminous adhesive Tape Air Outlet Connect the duct with flange outlet together Seal the pontes between the flange outletand duct using the aluminous adhesive tape Connect the flange outlet with the indoor unit together using screws unit mm in The Wall Ooutside Therma...

Страница 16: ...ss or a shortage of refrigerant is the main cause of trouble to the units Charge the correct refrigerant quantity 5 2 5 3 Discharge gas inside And remove the cap Gas Pipe Cool by a wet cloth Liquid Pipe unit mm ...

Страница 17: ...ows smoothly Make sure the drain pipe thermal insulated Install a trap at the drain outlet because it will bring splash or smell without it Keep the drain pipe flat in order to clean the sediment Seal another drain pipe do up it using thermal insulation Do not connect the drain pipe with sanitary or sewage piping or any other drainage piping When the common drain piping is connected with other ind...

Страница 18: ... connect diffent standard wires to the same terminal Use appointed wires and ensure the terminal fixed Do not connect cable of remote control switch and operating wires with power supplyand earth wires together Keep 50MM away from each other Cut out the center of the rubber bushing in the wiring connection holeÿas shown in Fig 7 1 Connect the cable of the remote control switch to the connectors in...

Страница 19: ...nside Rubber Bushing Electrical Box Bolts Electrical Box Cover Power supply Cable of Remote Control Switch Operating Wires ELB Electrical Parameter Model Power Supply Indoor Motors 380 415V 3N 50Hz 380V 3N 60Hz ...

Страница 20: ... 4 64 5 40 Rated Current Power Supply 380 415V 3N 50Hz 380V 3N 60Hz EN 60335 1 1 EN 60335 1 1 above FFRUGLQJ WR EN 60335 1 1 Q WKH FDVH WKDW FXUUHQW H FHHGV GR QRW FRQQHFW FDEOHV LQ VHULHV XUUHQW LUH 6L H PP i 6 6 i 10 10 i 16 16 i 25 25 i 32 32 i 40 40 i 63 63 i 1 1 ...

Страница 21: ...14 Model 16 0 20 0 ...

Страница 22: ...10 15 DSW6 RSW1 8 3 4 4 DSW5 RSW2 Optional Function Setting DSW8 Fuse Recover DSW7 1 2 a b c d e f 34567 16 0 20 0 ...

Страница 23: ...tor NO FUNCTION Indicator ABNML Alarm Indicator FILTER Indicator When opening the cover pull the cover toward the arrow direction B Operation Switch Section RUN STOP Switch FAN SPEED Fan Speed Selection Switch MODE Operation Mode Selection Switch Up Down Panel Operation Switch This function is not available VENT I Ventilator Operation Switch LOUVER Swing Louver Operation TIME Time Setting Switch T...

Страница 24: ......

Страница 25: ...P00682Q 2019 09 V04 Qingdao Hisense Hitachi Air conditioning Systems Co Ltd Add 218 Qianwangang Road Economic Technical Development Zone Qingdao P R China 1042123 ...

Отзывы: