GENERAL INFORMATION

PMML0385 rev.2 - 12/2018

2

1.3.2 

Additional information about safety

!

D A N G E R

•  HITACHI is not able to foresee all the circumstances which may 

result in a potential danger.

•  Do not pour water in the indoor or outdoor unit. These products 

are fitted with electric components. If water comes into contact 

with  electric  components,  this  will  cause  a  serious  electric 

shock.

•  Do not handle or adjust the safety devices inside the indoor and 

outdoor units. The handling or adjustment of these devices may 

result in serious accident.

•  Do not open the service cover or access panel of the indoor and 

outdoor units without disconnecting the main supply.

•  In  the  event  of  fire,  switch  off  the  mains,  put  out  the  fire 

immediately and contact your service supplier.

•  Check that the earth cable is correctly connected.
•  Connect the unit to a circuit breaker of the specified capacity.

!

C A U T I O N

• 

Refrigerant leaks may hinder respiration as the gas displaces the air 

in the room.

•  Fit the indoor unit, the outdoor unit, the remote control and the cable 

at a minimum of 3 metres away from sources of strong radiation from 

electromagnetic waves, such as medical equipment.

•  Do not use sprays, such as insecticides, varnishes or enamels or any 

other inflammable gas within a metre of the system.

•  If the circuit breaker or supply fuse of the unit comes on frequently, 

stop the system and contact the service suppler.

•  Do not carry out maintenance or inspection work yourself. This work 

must be carried out by qualified service personnel with suitable tools 

and resources for the work.

•  Do not place any foreign material (branches, sticks, etc.) in the air 

inlet or outlet of the unit. These units are fitted with high speed fans 

and contact with any object is dangerous.

•  This  appliance  must  be  used  only  by  adult  and  capable  people, 

having received the technical information or instructions to handle this 

appliance properly and safely.

•  Children should be supervised to ensure that they do not play with 

the appliance.

?

N O T E

•  The air in the room should be renewed and the room ventilated every 

3 or 4 hours.

•  The  system  fitter  and  specialist  shall  provide  anti-leak  safety  in 

accordance with local regulations.

1.4  PURPOSE OF THIS MANUAL

This air conditioner has been designed for standard air 
conditioning for human beings. For use in other applications, 
please contact your HITACHI dealer or service contractor.

The air conditioning system should only be installed by qualified 
personnel, with the necessary resources, tools and equipment, 
who are familiar with the safety procedures required to 

successfully carry out the installation.
The supplementary information about the purchased products 
is supplied in a CD-ROM, which can be found bundled with the 
outdoor unit. In case that the CD-ROM is missing or it is not 
readable, please contact your HITACHI dealer or distributor.

PLEASE READ THE MANUAL AND THE FILES ON THE 

CD-ROM CAREFULLY BEFORE STARTING WORK ON THE 

INSTALLATION OF THE AIR CONDITIONING SYSTEM.

 

Failure to observe the instructions for installation, use and 
operation described in this documentation may result in 
operating failure including potentially serious faults, or even the 
destruction of the air conditioning system.

It is assumed that the air conditioning system will be installed 
and maintained by responsible personnel trained for the 
purpose. If this is not the case, the customer should include all 
the safety, caution and operating signs in the native language of 
the personnel responsible.
Do not install the unit in the following places, as this may lead to 

a fire, deformities, rusting or faults:
• 

Places where oil is present (including oil for machinery).

• 

Places with a high concentration of sulphurous gas, such as 
spas.

•  Places where flammable gases may be generated or 

circulate.

• 

Places with a saline, acidic or alkaline atmosphere.

Do not install the unit in places where silicon gas is present. Any 

silicon gas deposited on the surface of the heat exchanger will 

repel water. As a result, the condensate water will splash out 

of the collection tray and into the electrical box. Water leaks or 

electrical faults may eventually be caused.

Do not install the unit in a place where the current of expelled 

air directly affects animals or plants as they could be adversely 
affected.

Содержание RPI-0.4FSN5E

Страница 1: ...O E DE FUNCIONAMENTO INSTALLATIONS OG BETJENINGSVEJLEDNING INSTALLATIE EN BEDIENINGSHANDLEIDING INSTALLATION OCH DRIFTHANDBOK ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΚΑΙΛΕΙΤΟΥΡΓΙΑΣ РЪКОВОДСТВО ЗА ИНСТАЛИРАНЕ И ЕКСПЛОАТАЦИЯ NÁVOD K MONTÁŽI A OBSLUZE PAIGALDUS JA KASUTUSJUHEND TELEPÍTÉSI ÉS ÜZEMELTETÉSI ÚTMUTATÓ UZSTĀDĪŠANAS UN EKSPLUATĀCIJAS ROKASGRĀMATA MONTAVIMO IR NAUDOJIMO VADOVĄ INSTRUKCJA MONTAŻU I OBSŁUGI M...

Страница 2: ......

Страница 3: ...ile per eventuali errori di stampa che esulano dal proprio controllo Português As especificações apresentadas neste manual estão sujeitas a alterações sem aviso prévio de modo a que a HITACHI possa oferecer aos seus clientes da forma mais expedita possível as inovações mais recentes Apesar de serem feitos todos os esforços para assegurar que todas as especificações apresentadas são correctas quais...

Страница 4: ...āvāt jaunākās inovācijas Lai gan tiek pieliktas visas pūles nodrošinot ka visas specifikācijas ir pareizas drukāšanas kļūdas ir ārpus HITACHI kontroles HITACHI nevar būt atbildīga par šīm kļūdām Lietuvių Šio vadovo specifikacijos gali būti keičiamos be įspėjimo kad HITACHI galėtų pateikti savo klientams paskutines naujoves Nors dedamos visos pastangos siekiant užtikrinti kad visos specifikacijos b...

Страница 5: ...li effetti negativi sull ambiente e sulla salute e favorisce il riciclo dei materiali di cui è composta l apparecchiatura Non tentate di smontare il sistema o l unità da soli poichè ciò potrebbe causare effetti dannosi sulla vostra salute o sull ambiente Vogliate contattare l installatore il rivenditore o le autorità locali per ulteriori informazioni Lo smaltimento abusivo del prodotto da parte de...

Страница 6: ...ējošo vielu eļļu un citām sastāvdaļām kas atrodas gaisa kondicionētājā tā demontāža saskaņā ar piemērojamiem noteikumiem jāveic profesionālam uzstādītājam Sazinieties ar attiecīgajām iestādēm lai saņemtu plašāku informāciju ĮSPĖJIMAS Pasibaigus eksploatacijos laikui šis produktas neturi būti maišomas su buitinėmis atliekomis ir turi būti išmetamas laikantis aplinkosaugos požiūriu tinkamų vietinių ...

Страница 7: ... 115 3 DE UNITS INSTALLEREN 119 4 DE KOELMIDDELLEIDINGEN AANSLUITEN 124 5 AFVOERLEIDING 125 6 ELEKTRISCHE BEDRADING 126 INNEHÅLLSFÖRTECKNING 1 ALLMÄN INFORMATION 129 2 DELARNAS NAMN 131 3 INSTALLATION AV ENHETER 135 4 ANSLUTNING FÖR KYLRÖR 140 5 DRÄNERINGSRÖR 141 6 ELEKTRISK ANSLUTNING 142 ΕΥΡΕΤΗΡΙΟ 1 ΓΕΝΙΚΈΣ ΠΛΗΡΟΦΟΡΊΕΣ 145 2 ΟΝΟΜΑΤΑ ΕΞΑΡΤΗΜΑΤΩΝ 147 3 ΕΓΚΑΤΑΣΤΑΣΗ ΜΟΝΑΔΩΝ 151 4 ΣΥΝΔΕΣΗ ΣΩΛΗΝΩΣΗΣ Ψ...

Страница 8: ... Versta versija PL Polski Tłumaczenie wersji oryginalnej RO Română Versiune tradusă RU Русский Переведенная версия SPIS TREŚCI 1 INFORMACJE OGÓLNE 257 2 CZĘŚCI SKŁADOWE 259 3 MONTAŻ URZĄDZENIA 263 4 PRZYŁĄCZE PRZEWODU CZYNNIKA CHŁODNICZEGO 268 5 PRZEWÓD ODPŁYWU SKROPLIN 269 6 POŁĄCZENIA ELEKTRYCZNE 270 INDICE 1 INFORMAȚII GENERALE 273 2 DENUMIREA COMPONENTELOR 275 3 INSTALAREA UNITĂȚILOR 279 4 RAC...

Страница 9: ...mmelse mellan den engelska och den översatta versionerna skall den engelska versionen vara giltig EL Η αγγλική έκδοση είναι το πρωτότυπο και οι εκδόσεις σε άλλες γλώσσες μεταφράζονται από τα αγγλικά Σε περίπτωση που διαπιστωθούν διαφορές µεταξύ της αγγλικής και της μεταφρασμένης έκδοσης η αγγλική έκδοση είναι επικρατέστερη BG Английската версия е оригиналната други езици се превеждат от английски ...

Страница 10: ......

Страница 11: ... type indoor unit RPI Position separating hyphen fixed Capacity HP 0 4 6 0 FS SYSTEM FREE N R410A refrigerant 5 Series E Made in Europe XXX XX FS N 5 E 1 3 SAFETY 1 3 1 Symbols used During normal air conditioning system design work or unit installation greater attention must be paid in certain situations requiring particular care in order to avoid injuries and damage to the unit the installation o...

Страница 12: ...nd the room ventilated every 3 or 4 hours The system fitter and specialist shall provide anti leak safety in accordance with local regulations 1 4 PURPOSE OF THIS MANUAL This air conditioner has been designed for standard air conditioning for human beings For use in other applications please contact your HITACHI dealer or service contractor The air conditioning system should only be installed by q...

Страница 13: ...Fan 3 Fan motor 4 Heat exchanger 5 Header 6 Expansion valve 7 Air filter 8 Refrigerant gas pipe connection 9 Refrigerant liquid pipe connection 10 Electrical control box 11 Air inlet 12 Air outlet 13 Drain pump 14 Drain pipe connection 15 Filter fixing tabs upper side 16 Filter fixing tabs lower side ...

Страница 14: ...an motor 4 Heat exchanger 5 Header 6 Expansion valve 7 Air filter 8 Refrigerant gas pipe connection 9 Refrigerant liquid pipe connection 10 Electrical control box 11 Air inlet 12 Air outlet 13 Drain pump 14 Drain pipe connection 15 Filter fixing tabs upper side 16 Filter fixing tabs lower side ...

Страница 15: ...Fan motor 4 Heat exchanger 5 Header 6 Expansion valve 7 Air filter 8 Refrigerant gas pipe connection 9 Refrigerant liquid pipe connection 10 Electrical control box 11 Air inlet 12 Air outlet 13 Drain pump 14 Drain pipe connection 15 Filter fixing tabs upper side 16 Filter fixing tabs lower side ...

Страница 16: ...an motor 4 Heat exchanger 5 Header 6 Expansion valve 7 Air filter 8 Refrigerant gas pipe connection 9 Refrigerant liquid pipe connection 10 Electrical control box 11 Air inlet 12 Air outlet 13 Drain pump 14 Drain pipe connection 15 Filter fixing tabs upper side 16 Filter fixing tabs lower side ...

Страница 17: ...ed to install a electrical heater in the field Mount suspension bolts using M10 W3 8 as size as shown below Do not put any foreign material into the indoor unit and check to ensure that none exist in the indoor unit before the installation and test running Otherwise a fire or failure etc may occur CAUTION Do not install the indoor units in a flammable environment to avoid a fire or an explosion Ch...

Страница 18: ...sion bracket hook the suspension bracket of the other side to nut and washer Left side Suspension bolt Suspension bracket Inlet air Washer Nut Right side Washer Nut Drain pan level FRONT VIEW Condensate drain connection Make sure that the foundation is flat taking into account the maximum foundation gradient The unit should be installed so that one side of the unit is slightly approximately 5mm lo...

Страница 19: ...d Air filter factory supplied or adapted factory one Fig 1 Fig 2 It is recommended the following indications depending on the installation Keep the standard air filter in case of no suction duct is applied fig 1 In case of applying suction duct it is recommended to apply air filter at the inlet point of suction duct removing the standard air filter of the unit fig 2 Suction air filter servicing Do...

Страница 20: ...gram For RPI 0 4 1 5 FSN5E units the air inlet direction can be modified by adding and optional accessory specifically designed for this purpose 3 1 3 Fan performance curve These units provide three options for the installation High static pressure standard static pressure or Low static pressure conditions in each particular installation as shown below Fan Performance Curve RPI 0 4FSN5E RPI 0 6FSN...

Страница 21: ...r flow m3 min RPI 2 0FSN5E RPI 2 5FSN5E External static pressure Pa External static pressure Pa Air flow m3 min Air flow m3 min RPI 3 0FSN5E RPI 4 0FSN5E External static pressure Pa External static pressure Pa Air flow m3 min Air flow m3 min RPI 5 0FSN5E RPI 6 0FSN5E External static pressure Pa External static pressure Pa Air flow m3 min Air flow m3 min ...

Страница 22: ...re levels regulation depending on the installation requirements High Static Pressure Standard Static Pressure Factory setting and Low Static Pressure conditions are available Static Pressure setting shall be made from the Remote Control Switch For changing to High and Low Static Pressure level refer to Installation and Operation Manual remote control 4 REFRIGERANT PIPING CONNECTION Position of pip...

Страница 23: ...it This trap must be designed to good practice and be checked with water charged and tested for correct flow Do not tie or clamp the drain pipe and refrigerant pipe together After performing drain piping work and electrical wiring check to ensure that water flows smoothly as in the following procedure Checking with drain up mechanism and float switch Switch ON the power supply Pour approximately 1...

Страница 24: ... unit showed above and of the electrical box shown below 3 Connect the power supply and ground wires to the terminals in the electrical box as shown below 4 Connect the wires between the indoor unit and the outdoor unit to the terminals 1 and 2 in the electrical box 5 Connect the cable of the Remote Control Switch to the terminals A and B in electrical box 6 Tightly fix the wires with the cord cla...

Страница 25: ...IRING PMML0385 rev 2 12 2018 15 EN RPI 2 0 3 0 FSN5E PCB TB RPI 4 0 6 0 FSN5E PCB2 PCB1 TB 6 1 4 Terminal board connections Remote control PC ARFP 1 E Transmission wires Power supply wires single phase Earth Screw ...

Страница 26: ... the indoor unit type Indoor Unit Model DSW4 Setting RPI DSW5 and RSW2 Refrigerant system number setting Setting is required Setting position before shipment in DSW5 RSW2 Here is set DSW5 and RSW2 before shipment up to 63 can be set Example setting 5 system RSW2 All pins are OFF Fix to 5 DSW6 and RSW1 Indoor unit number setting The below figure indicates the position before shipment DSW6 RSW1 Here...

Отзывы: