DSW3: Capacity Code Setting
No setting is required, due to setting before shipment. This dip
switch is utilized for setting the capacity code which corresponds
to the Horse Power of the indoor unit.
HP
0.8
1.0
1.3
Setting Position
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1.5
1.8
2.0
Setting Position
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
2.3
2.5
2.8
Setting Position
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
DSW5 and RSW2: Refrigerant Cycle Number
Setting
Setting is required. Setting position before shipment in
DSW5
RSW2
1 2 3 4 5 6
ON
Here is set DSW5 and RSW2 before shipment up to 63 can be set.
Ex. Setting 5 system
RSW2
1 2 3 4 5 6
ON
All pins are OFF
Fix to 5
DSW4: Unit Model Code Setting
No setting is required. This switch is utilized for setting the
model code which corresponds to the indoor unit type.
Indoor Unit Model
DSW4 Setting
RPF(I)
1 2 3 4
ON
DSW7: Fuse Recover
In case of applying high voltage to the terminal 1,2
of TB1, the fuse on the PCB1(M) is cut. In such a
case, firstly correct the wiring to TB1 and then turn
ON #1 (as showing beside)
1 2
ON
DSW7: Remote Control Selection
No setting is required. Setting position before
shipment is all OFF (PC-ARFPE) Remote Control
Switch Selected).
1 2
ON
?
N O T E
The mark " " indicates position of dips switches. Figures show setting
before shipment or after selection.
ELECTRICAL WIRING
PMML0159A rev.3 - 05/2016
9