1.
Set
FunctionMode
=
CB Pos
.
2.
Apply input signal for CB closed to relevant input or inputs CBCLDL1, CBCLD2 or CBCDL3.
3.
Apply the input signal, or signals for the start of CCRBRF.
4.
Verify that phase selection re-trip and backup trip are achieved after set times.
5.
Disconnect the start signal(s). Keep the CB closed signal(s).
6.
Apply input signal(s), for start of CCRBRF.
7.
Arrange disconnection of CB closed signal(s) well before set backup trip time
t2
8.
Verify that backup trip is not achieved.
11.4.9.9
Verifying the case RetripMode = Contact
M12104-213 v10
It is assumed that re-trip without current check is selected,
RetripMode
=
Contact
.
1.
Set
FunctionMode
=
Contact
2.
Apply input signal for CB closed to relevant input or inputs CBCLDL1, CBCLD2 or CBCDL3.
3.
Apply the input signal, or signals for the start of CCRBRF.
4.
Verify that phase selection re-trip and back-up trip are achieved after set times.
5.
Disconnect the start signal(s). Keep the CB closed signal(s).
6.
Apply input signal(s), for start of CCRBRF.
7.
Arrange disconnection of CB closed signal(s) well before set back-up trip time
t2
.
8.
Verify that back-up trip is not achieved.
11.4.9.10
Verifying the caseFunctionMode = Current or CB Pos
M12104-237 v7
To be made only when
FunctionMode
=
Current or CB Pos
is selected. It is suggested to make the
tests in one phase only, or at three-phase trip applications for just three-phase tripping.
Checking the case with fault current above set value IP>
M12104-241 v8
The operation shall be as in
RetripMode
=
UseFunctionMode
.
1.
Set
FunctionMode
=
Current
or
CB Pos
.
2.
Leave the inputs for CB close inactivated. These signals should not influence.
3.
Apply the fault condition, including the start of CCRBRF, with the current above the set
IP>
value.
4.
Check that the re-trip, if selected, and back-up trip commands are achieved.
Checking the case with fault current below set value I>BlkCBPos
M12104-281 v11
The case shall simulate a case where the fault current is very low and operation will depend on CB
position signal from CB auxiliary contact. It is suggested that retrip without current check is used,
setting
RetripMode
=
UseFunctionMode
Check.
1.
Set
FunctionMode
=
Current
or
CB Pos
.
2.
Apply input signal for CB closed to the relevant input or inputs CBCLDL1 (2 or 3).
3.
Apply the fault condition with input signal(s) for start of CCRBRF. The value of current should
be below the set value
I>BlkCBPos
.
4.
Verify that phase selection re-trip (if selected) and back-up trip are achieved after set times.
Failure to trip is simulated by keeping the signal(s) CB closed activated.
5.
Disconnect the input signal and the START signal(s). Keep the CB closed signal(s).
6.
Apply the fault and the start again. The value of current should be below the set value
I>BlkCBPos
.
7.
Arrange disconnection of CB closed signal(s) well before set back-up trip time
t2
. It simulates a
correct CB tripping.
8.
Verify that back-up trip is not achieved. Re-trip can appear for example, due to selection
RetripMode
=
Always
.
Section 11
1MRK 511 403-UEN Rev. L
Testing functionality by secondary injection
102
Bay control REC670
Commissioning manual
© 2017 - 2022 Hitachi Energy. All rights reserved
Содержание REC670
Страница 1: ...Relion 670 SERIES Bay control REC670 Version 2 2 IEC Commissioning manual ...
Страница 2: ......
Страница 28: ...22 ...
Страница 54: ...48 ...
Страница 60: ...54 ...
Страница 66: ...60 ...
Страница 90: ...84 ...
Страница 212: ...206 ...
Страница 218: ...212 ...
Страница 232: ...226 ...
Страница 240: ...234 ...
Страница 241: ...235 ...