13
/58
GENERAL SPECIFICATIONS
Model (R407C)
RCUE300AG1
RCUE330AG1
RCUE360AG1
RCUE400AG1
Cooling Capacity
kW
780
890
936
1.068
Total Power Input (R407C)
kW
296,5
341,8
355,8
410,1
COP
2,63
2,60
2,63
2.60
Height
mm
2.430
2.430
2.430
2,430
Width
mm
1.800
1.800
1.800
1,800
Outer Dimension
Depth
mm
9.250
9.250
11.050
11,050
Cabinet Colour
Natural Gray
Net Weight
kg
7.600
7.700
9.050
9.170
Compressor Type
-
Semi-Hermetic Screw Type
Model
-
5005SC-Z
6005SC-Z
5005SC-Z
6005SC-Z
Quantity
-
5
5
6
6
Oil Heater
W
150x5
150x5
150x6
150x6
-
Continuous Capacity Control
Capacity Control
%
12.5, 25~100
12.5, 25~100
12.5, 25~100
12.5, 25~100
Water Cooler Type
-
Brazing Plate Type
Condenser Type
-
Multi-Pass Cross Finned Tube
Fan Motor (Pole)
kW
0.4 (6)
0.4 (6)
0.4 (6)
0.4 (6)
Quantity
-
20
20
24
24
Refrigerant Type
R407C(Factory Charged)
Flow Control
-
Thermal Expansion Valve
Number of Independent Circuits
-
5
5
6
6
Oil Type
-
CASTROL ICEMATIC SW220HT (Ester)
Water Pipe Connection
Inch
4" Victaulic ( 3 x INLET / 3 x OUTLET )
Control System
-
Micro-Processor Control
Chilled Water Outlet Temperature
C
5
∼
15
Condenser Air Inlet Temperature
C
5~43 (Option:-15~43)
Permissible Water Pressure Max.
MPa
1.0
Safety and Protection Devices
-
Reverse Phase Protection Device, Fuse and Thermal Relay for Compressor,
Internal Thermostat for Compressor, Compressor Oil Heater,
Fuse and Internal Thermostat for Fan Motor, Control Circuit Fuse,
High Pressure Switch, Low Pressure Control, High Pressure Relief Valve,
Discharge Gas Temperature Control, Suction Gas Temperature Control,
Freeze Protection Control and Compressor Operation Hour Meter
Power Supply
-
3~,N/380-415V/50Hz
NOTE:
The nominal cooling capacities are based on the European Standard EN12055.
- Chilled Water Inlet/Outlet Temperature: 12/7 °C
- Condenser Inlet Air Temperature: 35 °C
- Cooling capacity and total power input data at 40~43ºC are available at distributor side