Hitachi RAS-S10CZ Скачать руководство пользователя страница 2

OUTDOOR UNIT

  Please mount the outdoor unit on stable ground 

to prevent vibration and increase of noise level.

 Decide the location for piping after sorting out 

the different types of pipe available.

Procedure to remove the cover 

of wiring terminals

 Remove the screw (1 

piece).

 Hold the projected part 

at the lower left of the 
cover and push the cover 
upwards to remove it.

 To close the cover, insert 

the upper part of the 
cover into the body of 
outdoor unit, then be sure 
that the hook below the 
cover is plugged in before 
screwing.

   Removal Of Air From The Pipe And Gas Leakage Inspection

   Preparation of Pipe

1

 Use a pipe cutter to cut the copper pipe.

 Jagged edge will cause leakage.

 Point the side to be trimmed downwards during trimming to prevent copper chips from 

entering the pipe.

 Before  aring, please put  

  on the hexagon screw cap.

   Pipe Connection

2

 Please be careful when bending the copper pipe.

 Applied frozen grease to the connection points and then screw in manually. After that, 

use a torque wrench to tighten the connection.

INST

ALLA

TION OF COOLANT PIPES 

AND 

AIR REMOV

AL

Procedures of using Vacuum Pump for Air Removal

3

AIR REMOV

AL

CAUTION

!

As shown in  gure on the right, remove 
the cap of valve head and valve core 
and then connect them to the vacuum 
pump and  sub-division valve.

Fully tighten the “Hi” shuttle of the sub-
division valve and completely unscrew 
the “Lo” shuttle. Run the vacuum pump 
for about 10–15 minutes, then completely 
tighten the “Lo” shuttle and switch off the 
vacuum pump.

2

Completely unscrew the spindle of 
the service valve (at 2 places) in anti-
clockwise direction to allow the  ow of 
coolant (using Allen key).

3

Remove the connection pipe and tighten 
the cap of valve head. The task is then 
completed.

4

Gas Leakage Inspection

Please use gas leakage detector to check if leakage occurs at 
the connection of hexagon screw nut as shown on the right.

If gas leakage occurs, further tighten the connection to stop 
leakage.

1

<

IA694: A 

>

FINAL

 ST

AGE OF INST

ALLA

TION

Insulation And Maintenance Of Pipe Connection

1

 The connected terminals should be completely sealed with 

heat insulator and then tied up with rubber strap.

 Please tie the pipe and power line together with vinyl tape 

as shown in the  gure showing the installation of Indoor and 
Outdoor units. Then  x their position with holders.

 To enchance the heat insulation and to prevent water 

condensation, please cover the outdoor part of the drain hose 
and pipe with insulation pipe.

 Completely seal any gap with putty.

  Installation Of Remote Controller

2

  Power Source And Operation Test

3

 The remote controller can be placed in its holder which is 

 xed on wall or beam.

 To operate the remote controller at its holder, please ensure 

that the unit can receive signal transmitted from the controller 
at the place where the holder is to be  xed. The unit will beep 
when signal is received from the remote controller. The signal 
transmission is weaken by the  uorescent  light.  Therefore, 
during the installation of the remote control holder, please 
switch on the light, even during day time, to determine the 
mounting location of the holder.

Power Source

CAUTION

!

 Please use a new socket. Accident may occur due to the 

use of old socket because of poor contact.

 Please plug in and then remove the plug for 2 – 3 times. 

This is to ensure that the plug is completely plugged into 
the socket.

 Keep additional length for the power cord and do not 

render the plug under external force as this may cause 
poor contact.

 Do not  x the power cord with U-shape nail.

Operation Test

 Please ensure that the air conditioner is in normal operating 

condition during the operation test.

 Explain to your customer the proper operation procedures 

as described in the user’s manual.

WARNING

 If you cannot attach the side cover 

due to the connecting cord, press 
the connecting cord in direction to 
the front panel to  x it.

 Be sure that the hooks of the side 

cover is  xed in certainly. Otherwise 
water leakage may occur and this 
causes short circuit or faults.

 The naked part of the wire core should be 10 mm and  x it to the terminal tightly. Then 

try to pull the individual wire to check if the contact is tight. Improper insertion may burn 
the terminal.

 Be sure to use only power cables approved from the authorities in your country. For 

example in Germany: Cable type: NYM 3x2.0mm

2

.

 Please refer to the installation manual for wire connection to the terminals of the units. 

The cabling must meet the standards of electrical installation.

 There is an AC voltage drop between the L and N terminals if power is on. Therefore, 

before servicing, be sure to remove the plug from the AC outlet or switch off the main 
switch.

  THIS APPLIANCE MUST BE EARTHED.

Procedures of Wiring

Wiring of The Outdoor Unit

 Please remove the side cover for wire connection.

!

WARNING

!

CONNECTION OF POWER CORD

WARNING

!

Connecting cord

GRN + YEL

Wiring Of The Indoor Unit

  For wire connection of the Indoor unit, you need to remove Low Cover and Indicator Cover.

The controller should 
be insert from top into 
bottom side of the 
holder as shown in 
 gure  below.

TIME DELAY FUSE USAGE

Outer

Diameter (ø)

6.35 (1/4")

9.52 (3/8")

Imperial  aring tool

0.8 – 1.5

1.0 – 2.0

Rigid  aring tool

0 – 0.5

0 – 1.0

A (mm)

TEMPORARY
S ITCH

3

4

Valve head cap

Valve core cap

Torque N.m

(kgf 

 cm)

13.7 – 18.6 (140 – 190)

34.3 – 44.1 (350 – 450)

19.6 – 24.5 (200 – 250)

12.3 – 15.7 (125 – 160)

Small dia. side

Big dia. side

Outer

dia. of pipe

9.52 (3/8")

6.35 (1/4")

10A

RAC-S10CZ, RAC-5115CZ

 

Please  x back the electrical 
plate after wiring work is 
complete. Otherwise if short 
circuit occur it may cause 
unit burn.

WARNING

!

CABLE SIZE ød

1-25mm

RAS-S10CZ, RAS-5115CZ

  Pull the cover at  

 and  

2   

in the 

directions as shown by arrows to 
remove the low cover.

After unscrew and remove 
electrical plate, unscrew the 
terminal band to put connecting 
cords. Fix back the band screw 
and electrical plate.

Outdoor

Unit

Indoor

Unit

Strip wires

GRN + YEL

INS RAS-S10CZ-5115CZ (2).indd   1

6/24/10   4:37 PM