HITACHI SPLIT-UNIT AIR CONDITIONER 

INSTALLATION MANUAL

Indoor Unit 

         Outdoor Unit

RAS-AJ18CMT RAC-AJ18CMT

THE CHOICE OF MOUNTING SITE 

 (Please note the following matters and obtain permission from customer before installation).

WARNING

!

 The unit should be mounted at stable, non-vibratory location 

which can provide full support to the unit.

WARNING

  The outdoor unit must be mounted at a location which can support 

heavy weight. Otherwise, noise and vibration will increase.

CAUTION

 No nearby heat source and no obstruction near the air outlet is 

allowed.

 The clearance distances from top, right and left are speci

fi

 ed  in 

fi

 gure  below.

 The location must be convenient for water drainage and pipe 

connection with the outdoor unit.

 To avoid interference from noise please place the unit and its 

remote controller at least 1m from the radio, television and inverter 
type 

fl

 uorescent  lamp.

  To avoid any error in signal transmission from the remote controller, 

please put the controller far away from high-frequency machines 
and high-power wireless systems.

 The installation height of indoor unit must be 2.3m or more.

INDOOR UNIT

Figure showing the Installation of Indoor and Outdoor Unit.

OUTDOOR UNIT

FOR SERVICE PERSONNEL ONLY

Direction of Piping

There are 6 directions  
allowed, namely, horizontally 
perpendicular to the unit, 
vertically down from right, 
horizontally out from right, 
horizontally out to left,
horizontally out to right, 
vertically down from left.
Don’t form the piping downward 
at the left of the unit.

 Carefully read through the procedures of proper 

installation before starting installation work.

 The sales agent should inform customers regarding 

the correct operation of installation.

Tools Needed For Installation Work

Screw for Mounting Plate

( 4 . 1 x 3 2 )

Names of Indoor Components

Screw for holder of 
Remote Controller

                  (3.1x16)

AAA Size Battery

Remote Control Holder

Mounting Plate

Qty

No.

Component’s Name

1

6

1

2

2

Remote Controller

1

2

3

4

5

6

1

<

IA1994: A 

>

Installation of Hanger, Wall Penetration and Installation of Protection Pipe

1

CAUTION

!

  The draining of the water container inside the indoor unit can be done from the left. 

Therefore the mounting plate must be 

fi

 xed horizontally or slightly tilted towards the 

side of drain hose. Otherwise, condensed water may over

fl

 ow the water container.

Direct Mounting On The Wall

 Please use hidden beams in the wall to hold the mounting plate.

Wall Penetration and Installation of Protection Pipe

 Drill a ø 65mm hole on 

wall which is slightly tilted 
towards the outdoor side. 
Drill the wall at a small 
angle.

 Cut the protection pipe 

according to the wall 
thickness.

 Empty gap in the sleeve 

of protection pipe should 
be completely sealed with 
putty to avoid dripping of 
rain water into the room.

INSTALLATION OF REFRIGERATING PIPES AFTER CONNECTION

  The refrigerating pipes should be adjusted to 

fi

 t into the hole 

on the wall and then ready for further connection.

  The terminals of 2 connected pipes must be covered with insulator 

used for terminal connection. Then the pipes are wrapped with 
insulation pipe.

 Connect the connecting cord after removing electrical cover. 

(Refer to “CONNECTION OF POWER CORD”)

 After adjustment, 

fi

 t the connecting cord and pipes into the 

space available under the indoor unit. 

 When connection is at left side, refrigerating pipe and cabinet 

shall be tied together.

  Failing to do so may cause the unit bottom side become warping.
  Excess binder shall be cut to prevent abnormal sound and water 

dripping.

!

CAUTION

  The rubber strap used for 

fi

 xing 

the insulator should not be tied 
with great force. Otherwise, this 
will damage heat insulation and 
causes water condensation.

THE CONNECTION OF REFRIGERATING PIPE DURING THE 
INSTALLATION OF INDOOR UNIT

Preparation To Install Refrigerating Pipes

!

CAUTION

 Please 

fi

 x in the plastic core 

after 

fl

 aring to avoid copper 

chips entering the pipes.

Be sure that the wire is not 
in contact with any metal 
in the wall. Please use 
the protection pipe as wire 
passing through the hollow 
part of the wall so as to 
prevent the possibility of 
damaged by mouse.
Unless it seals completely, 
any air with high humidity 
flows from outdoor and 
dew may drop.

!

WARNING

 The refrigerating pipes and connecting cord 

arrangement are attached.

 The end of the refrigerating pipes are at locations 

marked with “ 

 

” symbol.

   Installation of Drain Hose

3

INDOOR UNIT

Heat insulation pipe

Connecting
cord

Refrigerating pipe

Pull this to the front 
during the connection 
of refrigerating pipes 
to ease task.

Procedures of Installation and Precautions

 Procedures to 

fi

 x the mounting plate.

1. Drill holes on wall.  2. Push plug into the holes.  3. Fix the mounting plate on wall
  (As shown below) 

  (As shown below) 

  with 4.1 x 32 screw

    

   

  (As shown in 

fi

 gure  below)

 Procedures to 

fi

 x the holder of remote control.

1. Drill holes on wall. 

2. Push plug into the holes.

  (As shown below) 

  (As shown below)

   Installation of the Indoor Unit

2

VERTICALLY DOWNWARD PIPING

  Preparation

 Connect connecting cord.

 Pull out the pipe, connecting cord and drain hose.

  Installation

 The upper part of the indoor unit is hanged on the mounting plate.

 The projection at the lower part of the indoor unit is hooked onto the mounting plate.

Please pull the lower part of 
the indoor unit outwards to 
check if the unit is hooked 
onto the mounting plate. 
Improper installation may 
cause vibration and noise.

!

CAUTION

HORIZONTAL PIPING

  Preparation

Change of Drain Hose and Installation Procedures.

  Exchange the location of drain hose and drain cap during horizontal piping as shown in 

fi

 gure below. Be sure to plug in the drain hose until the insulating material folds upon itself.

 Please use pliers to pull 

out the drain cap.

  (This is an easier way to 

remove the drain cap).

!

CAUTION

Condensed water 
may leak out if not 
inserted properly.

 mark is tool exclusive use for R32)

 

   

 +   –  Screwdriver 

   

   

 Measuring Tape 

   

 

 Knife   

 Saw  

 

 Pipe Cutter 

 Hexagonal Wrench Key (

 4mm)

 

 Power Drill (ø 65mm ~ ø 80mm)   

 Vacuum Pump 

 Pliers or Wrench   

 Torque Wrench  

 Vacuum Pump 

Adaptor   

 Flare Tool    

 Gas Leakage Detector 

 Manifold Valve 

     

 Charge Hose  

Dimension of Mounting Stand

of the outdoor unit

(unit : mm)

 

 The difference in 

height between the 
indoor and outdoor 
unit should be kept 
max 10m.

 The connecting 

pipe, no matter big 
or small, should 
all be insulated 
with insulation pipe 
and then wrapped 
with plastic tape. 
(The insulator will 
deteriorate if it is not 
wrapped with tape).

The connection of 
insulated drain hose.

Please use insulated 
drain hose for the 
indoor piping (commer-
cial product).

The indoor piping 
should be insulated 
with the enclosed 
insulation pipe. 
(If the insulator is 
insuf

fi

 cient,  please 

use commercial 
products).

Be sure to 
completely 
seal any 
gap with 
putty.

HOW TO REMOVE INDOOR UNIT

  Push up the (PUSH) sections at the bottom of the indoor unit and 

pull the bottom plate towards you. Then the claws are released from 
the stationary plate.

 

(The (PUSH) sections are indicated by 2 arrows in the right 

fi

 gure)

     

Installation

Hang the Indoor unit onto the mounting plate. Use the temporary stand 
at the back of the Indoor unit to push its lower part 15cm forwards.

 Place the drain hose through the hole on the wall.

 Wrap the refrigerating pipes with insulation pipe after connecting 

refrigerating pipe.

  Connect the connecting cord after removing electrical cover. (Refer 

to “Connection of Power Cord”)

 After adjustment, the connecting cord and refrigerating pipes are 

placed into the space available under the Indoor unit.

 The projection of Indoor unit must hook to the mounting plate.

!

!

CAUTION

 Selecting the installation location: Suitable location that will reduce the 

impact from rain and direct sun that may affect the unit performance. 
Besides that, ventillation must be good and clear of obstruction.

  The air blown out of the unit should not point directly to animals or plants.

  The clearances of the unit from top, left, right, front and back are speci

fi

 ed 

in 

fi

 gure below. At least 3 of the above sides must be open air.

 Be sure that the hot air blown out of the unit and noise do not disturb 

the neighbourhood.

  Do not install at a location where there is 

fl

 ammable gas, steam, oil and 

smoke.

 The location must be convenient for water drainage.

  Place the outdoor unit and its connection wire at least 1m away from the 

antenna or signal line of television, radio or telephone. This is to avoid 
noise interference.

 Do not install outdoor unit facing strong wind direction. It may damage 

the fan motor.

   

Do not install the outdoor unit in a place where small animals may build 
their nests. If small animal goes inside the unit and touches the electrical 
parts, failure of the unit, smoke or 

fi

 re may be caused. Request your 

customer to keep the surrounding of the unit is clean.

  Remove the cap for 

drain hose installation

Drain cap

Drain cap shall 
be fully tightened 
by pushing with 
Hexagonal wrench 
key when changing 
location.

!

CAUTION

!

You are free to choose the side (left or right) for the installation of drain 
hose. Please ensure the smooth 

fl

 ow of condensed water of the Indoor 

unit during installation. (Carelessness may result in water leakage.)

!

CAUTION

Be sure that the 
drain hose is not 
loosely connected 
or bend.

Above
100mm

CAUTION

  Do not guide the drain hose to places where corrosive gases (sulfur, 

ammonia, etc.) are generated, such as septic tanks and sewer.

  Corrosive gas may 

fl

 ow backward from the drain hose to the indoor unit, 

corrode the copper pipe, or it may cause offensive odors in the room.

  Cut the drain hose at a position 100 mm higher than the 

fl

 oor surface. It 

may cause water leakage due to air lock or clogging of foreign matter.

!

0.85m

SAFETY PRECAUTION

  Read the safety precautions carefully before operating the unit.

  The contents of this section are vital to ensure safety. Please pay special attention to the following sign.

  

WARNING ........ Incorrect methods of installation may cause death or serious injury.

  

CAUTION ......... Improper installation may result in serious consequence.

  Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of 

operating the unit as described in the user’s guide.

!
!

  Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. 

Any un

fi

 t method or using incompatible material may cause product damage, burst and serious injury.

 The appliance/pipe-work shall be stored in a well ventilated room with 

fl

 oor area larger than A

min

(m

2

) [refer to 

fi

 gure 

installation] and without any continuously operating ignition source. Keep away from open 

fl

 ames, any operating gas 

appliances or any operating electric heater. Else, it may explode and cause injury or death.

 The appliance/pipe-work shall be installed, and/or operated in a room with 

fl

 oor area larger than A

min

(m

2

) [refer to 

fi

 gure installation] and keep away ignitioon sources, such as heat/spark/open 

fl

 ame or hazardous areas such as gas 

appliances, gas cooking, reticulated gas supply systems or electric cooking appliances, etc.

 Do not pierce or burn as the appliance is pressurized. Do not expose the appliance to heat, 

fl

 ame, sparks, or other 

sources of ignition. Else, it may explode and cause injury or death.

  Flare nut must use a torque wrench without fail. Tighten with the speci

fi

 ed tightening torque. If the 

fl

 are nut is tightened too 

much, after a long period of time, the 

fl

 are nut breaks, Gas leakage, stagnation, touching 

fi

 re, rarely cause ignition.

  Sharp bending of the pipe use the polyethylene rod, bend not crushed the pipe. Gas leakage from the crushed part, stagnation, 

touching 

fi

 re, rarely cause ignition.

  Please request your s

ales ag

ent or quali

fi

 ed technician to install your unit. Water leakage, short circuit or 

fi

 re may occur if 

you do the installation work yourself.

  Please observe the instructions stated in the installation manual during the process of installation. Improper installation may 

cause water leakage, electric shock and 

fi

 re.

  Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the 

units may collapse and impose danger.

  Please ensure smooth 

fl

 ow of water when installing the drain hose.

  Piping shall be suitable supported with a maximum spacing of 1m between the supports. 

  Please use the speci

fi

 ed components for installation work. Otherwise, the units may collapse or water leakage, electric shock 

and 

fi

 re may occur.

  Be sure to use the speci

fi

 ed piping set for R32. Otherwise, this may result in broken copper pipes or faults.

  When installing or removing an air conditioner, only speci

fi

 ed refrigerant (R32) shall be allowed, do not allow air or moisture 

to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a 
rupture may be caused.

  Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with 

fi

 re,  a  poisonous 

gas may occur. Be aware that refrigerants may not contain an odour.

  After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks 

into the room, coming into contact with 

fi

 re in the fan-driven heater, space heater, etc., a poisonous gas may occur.

 Unauthorized modi

fi

 cations to the air conditioner may be dangerous. If a breakdown occurs please call a quali

fi

 ed air conditioner 

technician or electrician. Improper repairs may result in water leakage, electric shock and 

fi

 re,  etc.

WARNING

WARNING

!

!

This symbol shows that this equipment 
uses a 

fl

 ammable  refrigerant.

If the refrigerant is leaked, together 
with an external ignition source, there 
is a possibility of ignition.

This symbol shows that the Operation 
Instructions should be read carefully.

This symbol shows that a service 
personnel should be handling this 
equipment with reference to the 
Installation Manual.

This symbol shows that there is 
information included in the Operation 
Manual and/or Installation Manual

WARNING

CAUTION

CAUTION

CAUTION

CAUTION

 A brazed, welded or mechanical 

connection shall be made before 
opening the valves to permit 
refrigerant to 

fl

 ow between the 

refrigerating system parts. A vacuum 
valve shall be provided to evacuate 
the interconnecting pipe and/or any 
uncharged refrigerating system.

 Mechanical connectors used indoor 

shall comply with ISO 14903. 
When mechanical connectors are 
reused indoors, sealing parts shall 
be renewed. When 

fl

 are joints are 

reused indoors, the 

fl

 are part shall 

be re-frabricated.

 Refrigerant tubing shall be protected 

or enclosed to avoid damage.

!

RAC-AJ18CMT

––

1.20kg

Model

Maximum

charge R32

Additional 

R32

1.20kg

0.84m

2

20m

Factory 

charge R32

Indoor

A

min

 (m

2

)

Chargeless 

up to

 Flare connection only at outside of building

WARNING

!

Refrigerant piping 
must be protected 
from physical 
damage. Install a 
plastic cover or 
equivalent.

In case the pipe length is more than the recommended length for chargeless, 
add refrigerant R32 as below. Do not exceed the maximum pipe length.

CAUTION

!

Purifying Filter

7

2

Содержание RAS-AJ18CMT

Страница 1: ...erating pipes are placed into the space available under the Indoor unit The projection of Indoor unit must hook to the mounting plate CAUTION Selecting the installation location Suitable location that will reduce the impact from rain and direct sun that may affect the unit performance Besides that ventillation must be good and clear of obstruction The air blown out of the unit should not point dir...

Страница 2: ...cal cover Remove the screw and electrical cover Insert the connecting cord 1 2 3 from the back of unit Fixed the wire to terminal wires firmly as shown as below Connecting cord Electrical cover Screw Indoor Unit Procedures of Wiring CAUTION A circuit breaker must be installed Without a circuit breaker or fuse the danger of electric shock exists A main switch with a contact gap of more than 3mm has...

Страница 3: ... างชินส วนระบบ ทําความเย นได ต องมีวาล วสุญญากาศ สําหรับปลดท อทีเชือมต อระหว างกัน และ หรือระบบทําความเย นทีไม ได ชาร จ คอนเนคเตอร เชิงกลทีใช ในร มต องตรงตาม มาตรฐาน ISO 14903 เมือมีการใช คอน เนคเตอร เชิงกลซําในร ม จะต องเปลียนชิน ส วนกันรัว เมือใช ขัวต อแฟร ซําในร ม จะ ต องประกอบชินส วนแฟร ใหม ท อสารทําความเย นจะต องได รับการ ป องกันหรือหุ มเพือหลีกเลียงความเสียหาย ใช การเชือมต อด วยแฟร ทีภายนอกอ...

Страница 4: ...ีมีอํานาจใน ประเทศของคุณ คุณต องใช สายไฟทีระบุในการเชือมต อตัวเครืองปรับอากาศ กับตัวเครืองภายนอกอาคาร โปรดตรวจสอบให แน ใจว าการ เชือมต อมีความแน นหนา หลังจากทีเสียบลวดตัวนําสาย ไฟลงในขัวไฟฟ าแล ว การเสียบอย างผิดวิธีและจุดสัมผัสที หลวมอาจทําให เกิดความร อนสูงและเพลิงไหม ได ขันตอนในการเดินสายไฟ คําเตือน อุปกรณ นีต องเดินสายดิน ตัวเครืองปรับอากาศ ตัวเครืองภายนอกอาคาร สายไฟเชือมต อ สายไฟ รายละเอียดขอ...

Отзывы: