4
2
8. Safety and Control Device Setting
The compressor is protected by the following devices and their combinations.
(1) High Pressure Switch: This switch cuts out the operation of the compressor when the discharge
pressure exceeds the setting.
(2) Crankcase Heater: This band type heater protects against oil foaming during cold starting, as it is
energized while the compressor is stopped.
Model
RAS-3.0~
4.0HNSKQ
RAS-4.5~
7.0HNSKQ
High Pressure Switch
Automatic Reset, Non-Adjustable
Cut-Out MPa
4.15
4.15
Cut-In MPa
3.2
3.2
Breaker
A
40
5
0
Crankcase Heater
W
24
28
CCP Timer
Setting Time
Min
Non-Adjustable
3
Non-Adjustable
3