Hitachi RAM-90NP5A Скачать руководство пользователя страница 2

4. Preparation of Pipe

 Use a pipe cutter to cut the copper pipe.

 Before 

fl

 aring, please put on the 

fl

 are  nut.

Outer
Diameter (Ø)

6.35 (1/4”)

9.52 (3/8”)

12.7 (1/2”)

15.88 (5/8”)

Imperial 

fl

 aring  tool

~

 0.5mm

~

 0.5mm

~

 0.5mm

~

 0.5mm

Rigid 

fl

 aring  tool

A (mm)

 Please use exclusive tool

1.0mm

1.0mm

1.0mm

1.0mm

 Please be careful when bending the copper pipe.

 Screw in manually while adjusting the center. After that, use of torque wrench to tighten the connection.

CAUTION

!

 In case of removing 

fl

 are nut of a indoor unit, 

fi

 rst remove a nut of small diameter side, or seal 

cap of large diameter side will 

fl

 y out. Free from water into the piping when working.

 During connection, keep away from water.

 Be sure to tighten the 

fl

 are nut to the speci

fi

 ed torque using a torque wrench. If the 

fl

 are nut is 

tightened excessively, it may crack as time elapses, causing refrigerant leakage.

 Install the unit in a stable place to minimize vibration or noise.

 After arranging the cords and pipes, secure them in place.

Tighten all the way by hand.

Do not tighten all at once, but tighten it while 

fi

 tting the 

fl

 ared surface to the pipe.

CAUTION

!

5. Pipe Connection

5.1   Pipe connection
 

Connecting the pipe to outdoor unit

 
 

(1) Remove the 

fl

 are nut and seal cap from the service valve.

 

(2) Apply refrigerator oil to the service valve and the 

fl

 ared  

 

 

portion of the pipe.

 

(3) Using a wrench, security tighten.

 Jagged edge will cause leakage.

 Point the side to be trimmed downwards during trimming 

to prevent copper chips from entering the pipe.

6. Removal Of Air From The Pipe And Gas Leakage Inspection

This system integrates 5 sub-systems of piping with 1 pair of service valves installed. That pair will be used for air purging and 
pumping down operations. Furthermore, due to valves are not installed to cover up the connecting mouths, there is a need for 
all unutilized connecting mouths to be tightly covered up by seal caps and 

fl

 ared  nuts.

CAUTION:

  Should all unutilized connecting mouths are not tightly covered up by seal caps and 

fl

 ared nuts, there will be 

potential gas leaks occurring.

6.1   Air purging by using vacuum pump

Fig. 6-1

Fig. 6-2

Fig. 6-3

<

IA1022: C 

>

Outer diameter of pipe (Ø)

Torque N·m (kgf 

·

 cm)

Small diameter side

Large diameter side

6.35 (1/4”)

13.7-18.6 (140-190)

9.52 (3/8”)

34.3-44.1 (350-450)

12.7 (1/2”)

44.1-53.9 (450-550)

Small diameter side

Large diameter side

6.35 (1/4”)

19.6-24.5 (200-250)

9.52 (3/8”)

19.6-24.5 (200-250)

12.7 (1/2”)

29.4-34.3 (300-350)

Valve head 
cap

12.3-15.7 (125-160)

Valve core cap

15.88 (5/8”)

49.0-58.8 (500-600)

15.88 (5/8”)

29.4-34.3 (300-350)

7. Operation test

 Please ensure that the air conditioner is in normal operating condition during the operation test.

 Explain to your customer the proper operation procedures as described in the user’s manual.

 If the indoor unit does not operate, check to see that the connections are correct.

CAUTION

●  

Trial run should be conducted on one unit at a time to check for incorrect wiring of connecting cord.

!

Fig. 6-4

8.  Recovery of refrigerant during relocation or uninstalling of unit

(1)  Switching on the outdoor unit’s service switch will run the forced cooling 

operation. 

(2)  After operating for around 5 minutes, rotate the service valve spindle 

located at the side of the small pipe rim, in a clockwise direction to 
achieve a full shut off.

(3)  After operating for around 2~3 minutes, rotate the service valve spindle 

located at the side of the large pipe rim, in a clockwise direction to 
attain a full shut off.

(4)  Immediately stop the forced cooling operation and switch off the power 

supply.

(5)  Use a spanner or similar tools to tighten fully all valve cap and valve 

core cap to their speci

fi

 ed torque values.

(6)  Install and tighten the seal caps and 

fl

 ared nuts on all connecting 

mouths of each and every piping installed.

9. Forced Cooling Operation

Pressing the outdoor unit’s service switch for 1 second will start the forced 
cooling operation.
Please run this operation whenever there is a need to perform trouble-shooting 
or recovery of outdoor unit’s refrigerant.

CAUTION:

  In the event that the service valve spindle had been closed, do not operate it for more than 5 minutes.

Remove the valve cap from the service valves located at both the large 
and small pipe rims

After removing the valve cap of the valve core of the service valves 
located at the large pipe rim, connect the charging hose A.

After connecting the vacuum suction pump adaptor, connect the charging 
hose B to the adaptor.

During relocation or at any one time when the air conditioner unit 
is removed and re-installed, there is a possibility of getting a closed 
electric-powered valve. Should the electric-powered valve be closed, 
even with air purging being conducted, certain amount of air is still 
trapped within that area, hence, there is a need to open up the electric-
powered valve to do an air purging. Under such circumstances, before 
using the vacuum-suction pump, the main power supply (LN terminal) 
should be connected to enable a complete opening up of the valve. 
After connecting the power supply for approximately 90 seconds, the 
valve will be fully opened up, after which disconnect the power supply 
and start using the vacuum suction pump.
(Refer to “Power Supply Terminal Connections” in regards to the LN 
terminal)
CAUTION: Ingress of air during the operating cycle may cause increase 
in pressure and other breakdowns.

Switch off the outdoor unit’s power supply

Shutting off via the manifold valve handle Hi, the handle Lo will open 
up and operate the vacuum pump that will run a vacuum suction for 
approximately 60 minutes.

Upon a full shut off via the manifold valve handle Lo, the vacuum pump 
will stop operating.

Check to ensure that there is no gas leakage.

After removing the charging hose A, rotate the service valve spindles 
(2 units on both sides) in an anti-clockwise direction to fully open up.

Reinstall the cap nuts to their original positions and tighten them to their 
speci

fi

 ed torque values.

Disconnect the charge hose from the service valve.

Tighten the valve cap of valve core.
 [Torque 12.3 - 15.7 N·m (125 - 160 kgf·cm)]

Attach the valve cap to the spindles of each large and small dia. pipe 
side service valves.

Tighten the valve cap of the spindle.
[Torque 19.6 - 24.5 N·m (200 - 250 kgf·cm)]

Gas leakage inspection

Please use gas leakage detector to check if leakage occurs
at connection of 

fl

 are nut as shown on the right.

If gas leakage occurs, further tighten the connection to stop leakage. (Use the detector provided 
for R410A)

!

INS RAM-90NP5A   2

2/11/14   5:55 PM

Отзывы: