4. Preparation of Pipe

 Use a pipe cutter to cut the copper pipe.

 Before  aring, please put on the  are  nut.

Outer
Diameter (Ø)

6.35 (1/4”)

9.52 (3/8”)

12.7 (1/2”)

Imperial  aring tool

~

 0.5mm

~

 0.5mm

~

 0.5mm

Rigid  aring tool

A (mm)

 Please use exclusive 

tool

1.0mm

1.0mm

1.0mm

Outer diameter of pipe (Ø)

Torque N·m (kgf · cm)

Small diameter side

 Please be careful when bending the copper pipe.

 Screw in manually while adjusting the center. After that, use of torque wrench to tighten the connection.

Large diameter side

6.35 (1/4”)

13.7-18.6 (140-190)

9.52 (3/8”)

34.3-44.1 (350-450)

12.7 (1/2”)

44.1-53.9 (450-550)

Small diameter side

Large diameter side

6.35 (1/4”)

19.6-24.5 (200-250)

9.52 (3/8”)

19.6-24.5 (200-250)

12.7 (1/2”)

29.4-34.3 (300-350)

Valve head 
cap

12.3-15.7 (125-160)

Valve core cap

CAUTION

!

 In case of removing  are nut of a indoor unit,  rst remove a nut of small diameter side, or seal cap of 

large diameter side will  y out. Free from water into the piping when working.

 During connection, keep away from water.

 Be sure to tighten the  are nut to the speci ed torque using a torque wrench. If the  are nut is tightened 

excessively, it may crack as time elapses, causing refrigerant leakage.

 Install the unit in a stable place to minimize vibration or noise.

 After arranging the cords and pipes, secure them in place.

Gas leakage inspection

Please use gas leakage detector to check if leakage 
occurs
at connection of  are nut as shown on the right.
If gas leakage occurs, further tighten the connection to 
stop leakage. (Use the detector provided for R410A)

Tighten all the way by hand.

Do not tighten all at once, but tighten it while 
 tting the  ared surface to the pipe.

CAUTION

!

5. Pipe Connection

5.1   Pipe connection
 

Connecting the pipe to outdoor unit

 
 

(1) Remove the  are nut and seal cap from the service valve.

 (2) 

Apply refrigerator oil to the service valve and the  ared portion

 

 

of the pipe.

 

(3) Using a wrench, security tighten.

 Jagged edge will cause leakage.

 Point the side to be trimmed downwards during trimming 

to prevent copper chips from entering the pipe.

7. Operation test

 Please ensure that the air conditioner is in normal operating condition during the operation test.

 Explain to your customer the proper operation procedures as described in the user’s manual.

 If the indoor unit does not operate, check to see that the connections are correct.

CAUTION

●  

Trial run should be conducted on one unit at a time to check for incorrect 
wiring of connecting cord.

!

6. Removal Of Air From The Pipe And Gas Leakage Inspection

6.1   Air purging by using vacuum pump

<

IA1030: A 

>

INS RAM-130NP6A (EN)   2

3/30/13   9:34 AM