Installation diagram

Installation must be performed in accordance with the 
national wiring standards by authorized personnel only.

Above figure is only a simple presentation of the unit, it may 
not match the external appearance of the unit you purchased.

air outlet distance from the wall 

should be over 500mm

Distance from ceiling

 

over 200 mm

should be 

Distance from the obstacle  
should be over 3000mm. 

Distance from floor  
 over 2500mm. 

should be

Distance from wall

 

should be over 
50mm

Distance from 
the wall

 

be over 50mm

should 

Distance from the 
obstacle should be 
over 500mm. 
 

Air intake distance 
from

 

the wall 

should be

 

over 250mm

Air intake

 

distance from 
 the wall

 

should be 
over 250mml

over 250mm

Installation instructions

3

Select the installation  locations

Location for Installing Indoor Unit

1. Where there is no obstacle near 
the air outlet and air can be easily 
blown to every corner.    
2. Where piping and wall hole can
 be easily arranged. 
3. Keep the required space from 
the unit to the ceiling and wall 
according to the installation 
diagram on previous page.
4. Where the air filter can be easily 
removed. 
5. Keep the unit and remote controller 1m or more 
apart from television, radio etc. 
6. Keep as far as possible from fluorescent lamps.
7. Do not put anything near the air inlet to obstruct it
 from air absorption. 
8. Install on a wall that is strong enough to bear the 
weight of the unit.
9. Install in a place that will not increase operation
noise and vibration.
10. Keep away from direct sunlight and heating 
sources.  Do not place flammable materials or 
combustion apparatuses on top of the unit. 

Pipe length
is 15 meters 
         Max.

Height  should 

 be less than 5m 

Indoor unit

Outdoor 
unit

Location for Installing Outdoor Unit

1. Where it is convenient to install and well ventilated.
2. Avoid installing it where flammable gas 
could leak.
3. Keep the required distance 
apart from the wall.
The pipe length between indoor and 
outdoor unit should be not more than 
5 meters in factory default status, but it 
can go up to maximum 15 meters with 
additional refrigerant charge.
6. Keep the outdoor unit away 
from greasy dirt, vulcanization
 gas exit.
7. Avoid installing it by the 
roadside where there is a  risk
 of muddy water.
8. A fixed base where it is not subject to increased
 operation noise.
9. Where there is not any blockage of  the air outlet.
10. Avoid installing under direct sunlight, in an aisle 
or sideway, or near heat sources and ventilation fans.
 Keep away from flammable materials, thick oil fog, 
and wet or uneven places.   

If the height or pipe length is out of the scope of the
table, please consult the dealer.

Outdoor unit

Indoor unit

Pipe length is
15 meters Max.

 b

e less than 5m 

Height  should

Model

5K~18K

5

15

Max. allowed pipe
length without additional
 refrigerant (m)

Limit of 
length (m)

pipe 

21K 25K

~

28K~36K

5

15

5

15

5

20

Limit of Elevation 
Difference H (m)

  

Required amount of 
additional refrigerant
 (g/m)

5

30

5

40

Indoor unit installation

1. Installing the Mounting Plate
  

Decide an installing location for the mounting plate 

  according to the indoor unit location and pipe 
  direction.
  Keep the mounting plate horizontally with a 
  horizontal ruler or level.
  Drill holes of 32mm in depth on the wall for fixing 
  the plate.
  Insert the plastic plugs to the hole, fix the mounting
  plate with tapping screws.
  Inspect if  the mounting plate is well fixed. Then 
  drill a hole for pipe.

Mounting plate

Tapping screw

Note: The shape of your  mounting plate may be different 
from the one above, but the installation method is similar.
Note: As the above figure shown, the six holes matched with
 tapping screw on the mounting plate must be used to fix the 
mounting plate, the others are prepared.

Содержание RAK-AJ10PCASV

Страница 1: ...HI2022480HA INSTALLATION OPERATION MANUAL MODEL RAK AJ10PCASV RAC AJ10PCASV RAK AJ13PCASV RAC AJ13PCASV RAK AJ18PCASV RAC AJ18PCASV RAK AJ24PCASV RAC AJ24PCASV ...

Страница 2: ...ion will be further specified in following pages Signal transmit Dry indicator Fan only indicator Heating indicator Cooling indicator Higher fan speed High fan speed Medium fan speed Low fan speed Lower fan speed Display temperature Display set timer Display current time Auto fan speed Smart indicator ON OFF Used to adjust the room temperature and the timer also real time Sleep indicator 16 15 MUT...

Страница 3: ...le TEMP Airflow direction control Vertical airflow Horizontal airflow is automatically adjusted to a certain angle in accordance with the operation mode after turning on the unit The direction of airflow can be also adjusted to your own requirement by pressing the SWING button of the remote controller Operation mode Direction of airflow COOLING DRY HEATING FAN ONLY horizontal downward Do not turn ...

Страница 4: ... it is convenient to install and well ventilated 2 Avoid installing it where flammable gas could leak 3 Keep the required distance apart from the wall The pipe length between indoor and outdoor unit should be not more than 5 meters in factory default status but it can go up to maximum 15 meters with additional refrigerant charge 6 Keep the outdoor unit away from greasy dirt vulcanization gas exit ...

Страница 5: ...t pipes power Cord and drain pipe should be thermal insulated and fixed onto the back of the unit with a pipe fixer A Insert the pipe fixer to the slot B Press to hook the pipe fixer onto the base Base Base Base Pipe fixer Pipe fixer Hook here Insert here drain hose drain hose large pipe large pipe small pipe small pipe Piping Connection If you don t hear the exhaust noise please contact with the ...

Страница 6: ... obtaining access to terminals all supply circuits must be disconnected Make sure that the color of the wires in the outdoor unit and terminal No are the same as those of the indoor unit the details please refer to the wiring diagram which is near the terminal inside the unit Cable Specifications Outdoor unit installation 1 Install Drain Port and Drain Hose for heat pump model only Drain hose prep...

Страница 7: ...fter using it for about 100 hours Protection Operating condition note The protective device maybe trip and stop the appliance in the cases listed below The temperature of some products is allowed beyond the range In specific situation please consult the merchant If the air conditioner runs in COOLING or DRY mode withdoor or window opened for a long time when relative humidity is above 80 dew may d...

Страница 8: ...The unit is shifting from heating mode to defrost The indicator will lights off within ten minutes and returns to heating mode The symbols may be different from these models but the functions are similar Example 8 1 2 3 4 Display introduction NO Display Introduction 7 9 11 12 13 14 1 5 8 6 3 4 10 2 Temperature indicator Display set temperature It shows FC after 200 hours of usage as reminder to cl...

Отзывы: