4. Failure phenomenon: The fan motor will not stop.
>
Situation
@
I have conducted the stop operation on the product by remote control, but the indoor fan motor will not stop.
(It stopped about 10 minutes later.)
>
Estimated failure locations
@
·
Indoor fan motor
·
Fan motor drive circuit
>
Diagnosis flow
@
Initiating troubleshooting
Yes
Replace the "indoor fan motor".
No
Replace the "indoor electrical parts".
Run the product by remote control and then stop it.
(Reproduce the failure phenomenon.)
Is the voltage between pins
ĺ
and
ļ
of the fan motor
connector (CN2) below 1.5 V? (Take measurements
while the failure phenomenon is present.)
83
Содержание RAK-15QPC
Страница 2: ... DANGER 2 ...
Страница 24: ...24 ...
Страница 25: ...RAK 15QPC RAK 18RPC RAK 25RPC 25 ...
Страница 26: ...RAK 35RPC RAK RPC RAK 15QPC RAK 18RPC RAK 25RPC 50 26 ...
Страница 27: ...27 ...
Страница 28: ...28 ...
Страница 31: ...WIRING DIAGRAM RAK 15QPC RAK 18RPC RAK 25RPC 31 ...
Страница 33: ...CIRCUIT DIAGRAM MODEL 5 5 027 21752 6 1 RAK 15QPC POWER FOR CLEANNESS 33 ...
Страница 34: ...CIRCUIT DIAGRAM MODEL 5 5 027 21752 6 1 RAK 18RPC RAK 25RPC POWER FOR CLEANNESS 34 ...
Страница 57: ...10 10 10 10 10 R901 R904 R641 R907 R908 R694 R902 R695 R741 R740 R642 DSW1 DSW1 R903 R905 R906 57 ...
Страница 67: ...68 67 ...
Страница 70: ...37 and page 38 70 ...
Страница 71: ...Please set the DIP switch No 6 to ON accordingly Refe to page r RAR 6N1 RAR 6N2 RAR 6N3 RAR 6N4 RAR 6N5 57 71 ...
Страница 72: ...5 72 7 ...
Страница 73: ...73 ...
Страница 74: ... 䇭䇭 䇭䇭 䇭䇭 䇭䇭 䇭䇭 䇭䇭 B C E F 㺢 F 䌖 B GH E H C J E 74 ...
Страница 75: ... 䇭䇭 G FK 㺢 F L M C B C M C E C B H C E B M C E C B M C 75 ...
Страница 90: ...RAK 15QPC HHAW NO 0099E RAK 18RP RAK 25RP C C 90 ...