Hitachi RAK-15QPB Скачать руководство пользователя страница 2

2

Wiring of  The Indoor Unit

For wire connection of the Indoor unit, you need  to remove the front 
cover, the low  cover under the  body of the unit and terminal cover.

Remove the cover from the terminal base and screw the cable. 

Method to remove the low cover

Pull at the 

1

 and 

2

 

in

the directions as shown
by arrows to remove the
cover.

1

2

Detail of Cutting the Connecting Cord

70mm

10mm

10mm

45mm

1

2

3

Strip 

wires

Connecting cord

Green + Yellow 

(ground)

Indoor Unit

Connecting 

cord

Cord band

After remove the screw
and terminal cover, and
put the connecting cords
and fix the terminal cover
with screw.

Earth

PIPING FROM THE LEFT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)

Preparation

Changed of Drain Hose and Installation Procedures.

Exchange the location of drain hose and drain cap while installing the pipe from the left side as
shown in below. Be sure to plug in the drain hose until the insulating material folds upon itself.

Please use pliers to pull out the drain cap.
(This is an easier way to remove the drain
cap).

 CAUTION

Insufficient  insert  may
result in water leakage.

Drain Hose

Drain cap

Remove low cover

Insert drain cap up to the
location  securely till the
cap stops.

Push  the  pipe  deeply  until  the  insulating
section of the drain hose end gets over the
rib at the indoor unit side.

 CAUTION

The rubber strap used for fixing the insulator should not

e

b  ied with great force. Otherwise,this will damage heat 

insulation and causes water condensation.

Please pull the lower part of the Indoor unit outwards to 
check if the unit is hooked onto the hanger. Improper 

installation may cause vibration and noise.

Transform the piping while holding down the lower portion 

of pipe-support by hand.

Pipe

Rubber strap tied

with great force

INSTALLATION  AFTER CONNECTION OF REFRIGERATING PIPES

The refrigerating pipe should be adjusted to fit into
the  hole  on  the  wall  and  then  ready  for  further
connection.

The terminals of 2 connected pipes must be covered
with insulator used for terminal connection. Then the
pipes are wrapped with insulation pipe.

Connect  the  connecting  cord  after  removing  low
cover.
(Refer to "CONNECTION OF POWER CORD")

After adjustment, fit the connecting cord and pipes
into the space available under the unit. Use holder to
hold them tight.

Holder  can  be  attached  at  the  either  of  2  places.
Please select the easier position.

THE CONNECTION OF REFRIGERATING PIPE DURING

THE INSTALLATION OF INDOOR UNIT

  Preparation To Install Refrigerating Pipes

The  refrigerating  pipes  and  connecting  cord
transform and are attached.

Please bend at a small
radius to form an arc

   Installation

Hang the indoor unit onto the hanger. Use the temporary stand
at  the  back  of  the  Indoor  unit  to  push  its  lower  part  15cm
forwards.

Place the drain hose through the hole on the wall.

Wrap  the  refrigerating  pipes  with  insulation  pipe  after
connecting refrigerating pipe.

Connect the connecting cord after removing low cover.
(Refer to "Connection of Power Cord")

After adjustment, the connecting cord and refrigerating pipes
are placed into the space available under the Indoor unit.

The projection of Indoor unit must hook to the hanger.

4 Installation of Drain Hose

 CAUTION

Be sure that the drain hose is
not loosely connected bend or
proper condition like left figure.

CAUTION

You are free to choose the side (left or right) for the installation of drain
hose. Please ensure the smooth flow of condensed water of the Indoor
unit during installation. (Careless may result in water leakage.)

The connected terminals should be completed sealed

with heat insulator and then tied up with rubber strap.

Do not tie the terminals with the tape too tight.

If  any  clearance  or  over-tightening  may  cause

condensation.

Please tie the pipe and power line together with vinyl

tape as shown in the figure showing the installation of

Indoor and Outdoor units.

To enhance the heat insulation and to prevent water

condensation,  please  cover  the  outdoor  part  of  the

drain hose and pipe with insulation pipe.

Completely seal any gap with putty.

Insulation material for pipe
connection

Sleeve of
protection pipe

Putty

Putty

The end of the refrigerating pipes are at
locations marked with “ ” symbol.

3 Heat Insulation and Finish of the Piping

Drain cap

Pipe

support

Transform after

bending downward.

Holder

Pipe

Connecting
cord

Drain hose

Insulation pipe (must be wrapped with
vinyl tape at every 120 mm)

5mm

below

pond

Bending upwards Condensed water

Ditch

about 15cm

Hook

Projection

pond

Condensed water

Remove burr and jagged edge will cause leakage.

Point  the  side  to  be  trimmed  downwards  during 
trimming  to  prevent  copper chips from entering the pipe.

Copper pipe

Trimming tool

Before flaring, please put on the flare nut.

A

Die

Die

Copper pipe

Please use
exclusive tool for
refrigerant R410A.

Outer                           A (mm) Rigid Flaring Tool
Diameter (Ø)

For R410A tool

For R22 tool

6.35 (1/4")

0 - 0.5

1.0

9.52 (3/8")

0 - 0.5

1.0

2 Pipe Connection

 CAUTION

In case of removing flare nut of a indoor unit, first remove

a nut of small diameter side, or a seal cap of big diameter

side  will  fly  out.  Free  from  water  into  the  piping  when

working.

Be sure to tighten the flare nut to the specified torque with

a torque wrench.

If the flare nut is overtightened, the nut may be split after a

long period has passed, and may cause a refrigerant  leak.

Please be careful when bending the copper pipe.

Screw  in  manually  while  adjusting  the  center. 
After  that,  use  a  torque  wrench  to tighten the  
connection.

Torque
wrench

Flare nut

Wrench

   Gas leakage inspection

Please use gas leakage detector to check if

 leakage occurs  at  connection  of  Flare  nut 

as  shown  in  below. If gas leakage occurs, 

further tighten the connection to stop leakage.

1 Preparation of Pipe

Use a pipe cutter to cut the copper pipe and remove burr.

 CAUTION

For  cable  connection  to  control  P.W.B.,  you  need  to
remove front cover and electrical box cover.

    Each connecting location is as below.

H-LINK  RAC  Adapter

CN7

Wired Remote Control  : CN20

Please  check  and  confirm  manuals  attached  to  each
optional parts for more connection details.

You can refer to this installation manual how to remove
and re-attach the front cover.

Please be careful not to damage lead wires by edge of
plate when connecting the optional parts.

CN7

CN20

CN6

CN6

CN7

CN21

Push up the [PUSH] sections at the bottom of the indoor unit  
and pull the bottom plate towards you. Then the claws are  
released from the stationary plate.
(The [PUSH] sections are indicated by 2 arrows in the right  
figure)

HOW TO REMOVE INDOOR UNIT

[PUSH] mark positions

How to remove the front cover

How to Attach the Front Cover

Check that the drain pan is securely attached.

After installing the front cover onto the unit, hook three claws
at upper side of the cover securely. Then, push the center of
the front cover to lock the claws.
Tighten the two screws.

Install the filter.

Slide the shafts of the right and left arms on the front panel
along the steps to insert the shafts into the holes till they stop.
After checking that the shafts are securely inserted, close the
panel.

1 Remove the front panel

Please remove and attach the front panel by 
both hands.

After opening the front panel by both hands.

1

Undo the right arm while pushing it inside.

2

Slide the front panel to right as shown in figure. 
Then remove while pulling it to front.
Remove the filters.
After removing two screws, pull the center of 
the front cover towards you and release the claws.
Pull the side faces (lower sections) of the front 
cover towards you as shown in the figure and 
remove the cover.

1

1

2

3

2

3

4

5

2

2

3

4

1
2

3

 WARNING

FINAL STAGE OF INSTALLATION

WARNING

THIS APPLIANCE MUST BE EARTHED.

Leave some space in the connecting cord for
maintenance purpose and be sure to secure
it with the cord band.
Secure the connecting cord along the coated part of the wire using 
the cord band. Do not exert pressure on the wire as this may cause 
overheating or fire.

INSTALLATION OF REFRIGERATING PIPES AND AIR REMOVAL

RAK-15QPB/RAK-18_25RPB_IM_English

D

R

O

C

 

R

E

W

O

P

 

F

O

 

N

O

I

T

C

E

N

N

O

C

6.35 (1/4")
9.52 (3/8")
6.35 (1/4")
9.52 (3/8")

13.7-18.6 (140 - 190)
34.3-44.1 (350 - 450)
19.6-24.5 (200 - 250)
19.6-24.5 (200 - 250)
12.3-15.7 (125 - 160)

Small diameter side 

Outer diameter 

of pipe (ø)

Large diameter side 

Small diameter side 
Large diameter side 

Valve core cap

Torque N·m 

(kgf·cm)

Valve

head cap 

How to connect the optional parts

(H-LINK  RAC Adapter, Dry contact, Wired Remote 
Controller)

Dry contact: CN6

ler

Pull this to the front during 
the connection of refrigerating
pipe to ease task.

Wall hole

Pipe

Drain 

hose

Cable

Drain layout of   

backward piping  

from left 

Protection

pipe

Connecting cord

Connected

section

Drain hose

Heat
insulation pipe

Refrigerating

pipe

Connecting

cord