OUTDOOR UNIT
●
Please mount the outdoor unit on stable ground to prevent
vibration and increase of noise level.
●
Open the side plate by unscrewing the screws as shown below.
Gas Leakage Inspection
Please use gas leakage detector to check if leakage occurs
at the connection of Flare nut as shown on the right.
If gas leakage occurs, further tighten the connection to
stop leakage.
<
IA811: A
>
Preparation of Pipe
1
●
Use a pipe cutter to cut
the copper pipe.
●
Jagged edge will cause leakage.
●
Point the side to be trimmed downwards during trimming to prevent copper
chips from entering the pipe.
●
Before fl aring, please
put on the fl are nut.
Pipe Connection
2
INST
ALLA
TION OF REFRIGERA
TING PIPES
AND
AIR REMOV
AL
CAUTION
!
CAUTION
!
In case of removing Flare nut of an indoor unit, fi rst remove a nut of
small diameter side, or else seal cap of big diameter side will fl y out.
Please face this side (suction
side) of the unit to the wall.
Please remove side cover
when connecting the piping
and connecting cord.
Pull downward
CAUTION
!
Please make sure to remove all spacers inside the unit.
●
Open the Top, Back and Side cover of the unit.
●
Pull out the spacers inside.
(Spacers are only for transportation purpose).
If not remove, vibration and noise will occur.
Top cover
Back cover
Side cover
Removal Of Air From The Pipe And Gas Leakage Inspection
3
Proced res of sing ac
P
p for Air Re o al
AIR REMOV
AL
When the meter reaches - 101KPa
(-76cmHg) during pumping, fully
tighten the shuttle.
Lo
Hi
Meter showing pressure
Closed
R410A
Manifold valve
Vacuum
pump
Valve
Charge hose
Valve
Vacuum pump
adapter
When pumping starts, slightly loosen the
fl are nut to check of air sucked in. Then
tighten the fl are nut.
As shown in right fi gure, remove the cap of
valve core. Then, connect the charge hose.
Remove the cap of valve head. Connect the
vacuum pump adapter to the vacuum pump
and connect the charge hose to the adapter.
Fully tighten the “Hi” knob of the manifold
valve and completely unscrew the “Lo” knob.
Run the vacuum pump for about 10~15
minutes, then completely tighten the “Lo” knob
and switch off the vacuum pump.
2
Completely unscrew the spindle of the
service valve (at 2 places) in anti-clockwise
direction to allow the fl ow of refrigerant (using
Hexagonal Wrench key).
Re-cap the service valve and tighten using
wrench. Check the cap’s periphery if there is
any gas leakage. The task is then completed.
Remove the charge hose and tighten the cap
of valve core. Check the cap’s periphery if
there is any gas leakage.
4
5
1
3
Outer
Diameter (mm)
6.35 (1/4)
9.52 (3/8)
12.70 (1/2)
15.88 (5/8)
1.0 ~ 1.5
1.0 ~ 1.5
1.0 ~ 1.5
1.0 ~ 1.5
Clutch type
A (mm)
1.5 ~ 2.0
1.5 ~ 2.0
1.5 ~ 2.5
1.5 ~ 2.5
Wing nut type
Thickness
(mm)
0.8
0.8
0.8
1.0
0.0
~
0.5
0.0
~
0.5
0.0
~
0.5
0.0
~
0.5
Flare tool for R410A
Clutch type
Conventional fl are tool
●
You may not be able to close the side
cover due to the connecting cord, under
such situation, please press against the
wall of side cover to fi x it.
●
Be sure that the hooks (6 places) are
plugged in.
Otherwise, water leakage may occur and
this causes short circuit or faults.
Checking for the electric source and the voltage range
●
Before installation, the power source must be checked and necessary wiring work must be completed. To make the proper
wiring capacity, use the wire gauges list below for the lead-in from a pole transformer and for the wiring from a switch board
of fuse box to the outlet in consideration of the locked rotor current.
●
Investigate the power supply capacity and other electrical conditions at the installation location.
Depending on the model of room air conditioner to be installed, request the customer to make arrangements for the necessary
electrical work etc.
The electrical work includes the wiring work up the outlet. In localities where electrical conditions are poor, use of a voltage
regulator is recommended.
Wiring Of The Outdoor Unit
●
Please remove the side cover for wire connection.
CONNECTION OF POWER CORD
Cable length
up to 15m
up to 25m
Wire cross-section
2.5mm
2
4.0mm
2
IMPORTANT
Fuse Capacity
20A time delay fuse
WARNING
●
THIS APPLIANCE MUST
BE EARTHED.
Procedures of Wiring
Power is supplied from Outdoor Unit
●
The naked part of the wire core should be 10 mm and
fi x it to the terminal tightly. Then try to pull the individual
wire to check if the contact is tight. Improper insertion
may burn the terminal.
●
Be sure to use only power cables approved from the
authorities in your country. For example in Germany:
Cable type: NYM 3x1.5mm
2
, (fuse = 20A time delay)
●
Please refer to the installation manual for wire connection
to the terminals of the units. The cabling must meet the
standards of electrical installation.
●
There is a AC voltage of 220V between the L and N
terminals. Therefore, before servicing, be sure to remove
the plug from the AC outlet or switch off the main switch.
WARNING
Wiring Of The Indoor Unit
●
For wire connection of the Indoor unit, you need to remove
front panel and electrical cover.
Method to remove front panel
●
Refer to “How to Remove The Front Cover”.
Method to remove electrical cover
●
Remove the screw and electrical cover.
●
Insert the connecting cord (A,B,C,D) from the bottom of
unit.
●
Fixed the wire to terminal wires fi rmly as shown in Figure
1 at right side.
AUTO
RESTART
SWITCH
Screw
Power line
Control line
GRN + YEL
Indoor Unit
GRN + YEL
Outdoor Unit
Strip wires
How To Connect The Optional Parts
(RAC Adapter, Weekly Timer, Wired Remote Control)
[For all optional part, please refer catalog for part number]
Connection to the electrical box:
●
Remove the cover of electrical box.
●
Connect the connector of Weekly Timer/wired remote
controller to CN1102.
●
Assemble back the cover of electrical box.
●
Please refer to the respective user manual of Weekly Timer/
wired remote controller for further details.
●
Please be careful not to damage lead wires by edge of
plate when connecting the optional parts.
[For all optional part, please refer catalog for part number]
As for connecting to H-Link, a separately purchased
RAC Adapter is required.
●
To install the wiring the electrical box cover must be opened.
●
Connect the connector of RAC adapter to CN1101.
●
Assemble back the cover of electrical box.
●
Please refer to the respective user manual of RAC Adapter
for further details.
●
Please be careful not to damage lead wires by edge of
plate when connecting the optional parts.
WEEKLY TIMER / WIRED REMOTE CONTROLLER
H-LINK
A
B
C
D
Connect the
earth cord
After remove the screw
and band, put the
connecting cords and fi x
the band with screw.
Earth
terminal
N
L
C D
A B
Weekly timer / Wired
remote controller
CN1102
RAC
Adaptor
cord
CN1101
Figure 1
FINAL
ST
AGE OF INST
ALLA
TION
Ins lation And Maintenance Of Pipe Connection
1
●
The connected terminals should be completed sealed with
heat insulator and then tied up with rubber strap.
●
Please tie the pipe and power line together with plastic tape
as shown in the fi gure of installation of both the indoor and
outdoor units. Then fi x their position with holders.
●
To enhance the heat insulation and to prevent water
condensation, please cover the outdoor part of the drain hose
and pipe with insulation pipe.
●
Completely seal any gap with putty.
Installation Of Remote Control
2
Earth Line And Circuit Breaker
3
Power Source And Operation Test
4
●
The remote controller can be placed in its holder which is
fi xed on wall or beam.
●
To operate the remote controller at its holder, please ensure
that the unit can receive signal transmitted from the controller
at the place where the holder is to be fi xed. The unit will beep
when signal is received from the remote controller. The signal
transmission is weaken by the fl orescent light. Therefore,
during the installation of the remote control holder, please
switch on the light, even during day time, to determine the
mounting location of the holder.
CAUTION
●
The earth line terminal of the outdoor unit is below the
service valve.
●
To avoid short circuit, it is necessary to install circuit breaker
depending on the mounting location of the unit.
●
Do not place earth line near the following objects:
(1) Water
pipe
(2) Gas pipe – There is danger of catching fi re.
(3) The earth line of lightning conductor and telephone —
short circuit may occur during lightning.
Power Source
WARNING
●
Do not alter the plug of power cord.
Do not make extension to the power cord.
CAUTION
●
Please use a new socket. Accident may occur due to the
use of old socket because of poor contact.
●
Please plug in and then remove the plug for 2 – 3 times.
This is to ensure that the plug is completely plugged into
the socket.
●
Keep additional length for the power cord and do not
render the plug under external force as this may cause
poor contact.
●
Do not fi x the power cord with U-shape nail.
Operation Test
●
Please ensure that the air conditioner is in normal operating
condition during the operation test.
●
Explain to your customer the proper operation procedures
as described in the user’s manual.
How to Remove the Front Cover
●
Open the cap and remove the screw .
●
Open the front panel.
●
Remove the fi lter, release the axis by pulling the center
portion of front cover in the direction of arrow .
●
Push vertical air defl ector handle to the right or left side.
●
After raise the front cover from bottom side as , release
the front cover by pull the right or left sides as .
How to Install the Front Cover
●
Insert the two hooks at the upper side certainly.
●
Open Front Panel, push the center down in the direction
of the arrow as
to insert the axis at the center of the
front cover into the hook at the outlet frame.
●
Fixed the screw and cap .
1
2
3
4
5
1
The controller should
be insert from top into
bottom side of the
holder as shown in
fi gure below.
●
How to check pipe bending.
– Compare bended pipe with the picture below.
– If bended pipe is not good enough, cut bended area
and bend it again.
a all areas are smooth, no notching area
b no scratch or mark inside
c all have the same length
d phase of bending is too long
e slanting
f there are scratches around bending area
g crack
h different
length
i sample of bending pipe cannot be used
!
!
WARNING
!
!
!
!
6
Outer
diameter
of pipe
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
Valve core cap
Torque N.m
(kgf
●
cm)
13.7 ~ 18.6 (140 ~ 190)
34.3 ~ 44.1 (350 ~ 450)
44.1 ~ 53.9 (450 ~ 550)
19.6 ~ 24.5 (200 ~ 250)
19.6 ~ 24.5 (200 ~ 250)
29.4 ~ 34.3 (300 ~ 350)
12.3 ~ 15.7 (125 ~ 160)
Small dia. side
Large dia. side
Valve
head cap
Small dia. side
Large dia. side
●
Recommend to use
R410A fl aring tool.
CAUTION
!
In case of removing fl are nut of an Indoor unit, fi rst remove a nut of
small diameter side, or a seal cap of big diameter side will fl y out.
Prevent water from entering into the piping when working.
Electrical cover