Carefully  read  through  the  procedures  of  proper
installation  before  starting  installation  work.
The sales agent should inform customers regarding
the  correct  operation  of  installation.

THE CHOICE OF MOUNTING SITE 

 (Please note the following matters and  obtain permission  from  customer before  installation).

The unit should be mounted at stable, non-vibratory location which can provide
full support to the unit.

TI

N

R

O

O

D

NI

Figure  showing  the  Installation
of  Indoor  and  Outdoor  Unit.

TI

N

R

O

O

D

T

U

O

Indoor  Unit

Outdoor  Unit

19/10/07, 9:44 AM

1

WARNING

SAFETY PRECAUTION

•  Read the safety precautions carefully before operating the unit.
•  The contents of this section are vital to ensure safety. Please pay special attention to the following sign.

 WARNING ...... Incorrect methods of installation may cause death or serious injury. 

  This sign indicates prohibition. 

 CAUTION ....... Improper installation may result in serious consequence. 

Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of the unit 
as described in the user’s guide. Ask customers to keep this installation manual together with the instruction manual.

The  Length  of  Indoor  Unit

Power  Cord

Do  not  alter  the  power  cord.

Direction  of  Piping

about 1.2m

about
0.4m

Cut away shaded
portion, and finish
the edge of the
opening so that
there is no burr.

 No nearby heat source and no obstruction near the air outlet is allowed. 

 The installation height should be at least 2.3m or more from the floor. 

 The air blown out of the unit should not point directly to animals or plants. 

 Do not install at a location where there is flammable gas, steam, oil and smoke.

Dimension  of  Mounting  Stand

of  the  outdoor  unit

(unit  :  mm)

Screw  for  Mounting  Plate

( 4 . 1 x 3 2 )

Names  of  Indoor  Components

AAA  Size  Battery

Mounting  Plate

Qty

No      Component’s  Name

1

2

Remote  Controller

1

2

3

4

1

10

Horizontally 

backward

Piping  configuration  may  be

  in  six  different directions:

 direct rear piping,  left or right

 downward  piping and left 

or right sideways piping.

200mm

For outdoor unit installation, allow at least 

2 sides of space around the unit to ensure 

ventilation flue. 

Installation of Mounting Plate, Wall Penetration and Installation of Protection Pipe

1

Direct  Mounting  On  The  Wall

Please  use  hidden  beams  in  the  wall  to  hold  the  mounting  plate.

Wall  Penetration  and  Installation  of  Protection  Pipe

Drill a ø 65mm hole on wall
which  is  slightly  tilted
towards  the  outdoor  side.
Drill the wall at a small angle.
Cut  the  protection  pipe
according  to  the  wall
thickness.
Empty  gap  in  the  sleeve  of
protection  pipe  should  be
completely sealed with putty
to  avoid  dripping  of  rain
water  into  the  room.

Procedures  of  Installation  and  Precautions

Procedures  to  fix  the  mounting  plate.

1.Drill  holes  on  wall.

(As  shown  below)

      Installation  of  the  Indoor  Unit

2

VERTICALLY  DOWNWARD  PIPING

    Preparation

Connect  power  cord.
Pull out the pipe, power cord and drain hose.

    Installation

The upper part of the indoor unit is hanged
on  the  mounting  plate.
The projection at the lower part of the indoor
unit  is  hooked  onto  the  mounting  plate.

Please pull the lower part
of  the  indoor  unit
outwards  to  check  if  the
unit  is  hooked  onto  the
mounting plate. Improper
installation  may  cause
vibration  and  noise.

HORIZONTAL PIPING

    Preparation

Change  of  Drain  Hose  and  Installation  Procedures.

Exchange the location of drain hose and drain cap during horizontal piping as shown
in figure below. Be sure to plug in the drain hose until the insulating material folds upon
itself.

Please  use  pliers  to  pull  out  the  drain  cap.
(This is an easier way to remove the drain cap).

HORIZONTAL  &  DOWNWARD  PIPING  –  MAKING  OPENINGS

During horizontal or downward piping, use a knife to cut
openings as shown in figure. Then smoothen the edges
of  openings  with  a  file.

INSTALLATION  OF  COOLANT  PIPES  AFTER  CONNECTION

The  coolant  pipes  should  be  adjusted  to  fit  into  the
hole on the wall and then ready for further connection.
The terminals of 2 connected pipes must be covered
with  insulator  used  for  terminal  connection.
Connect  the  power  cord.
After  adjustment,  fit  the  power  cord  and  pipes  into
the  space  available  under  the  indoor  unit.

The  rubber  strap  used  for
fixing  the  insulator  should
not be tied with great force.
Otherwise, this will damage
heat insulation and causes
water  condensation.

THE CONNECTION OF COOLANT PIPE DURING THE
INSTALLATION  OF  INDOOR  UNIT

    Preparation  To  Install  Coolant  Pipes

Please  fix  in  the  plastic
core  after  flaring  to  avoid
plastic  chips  entering  the
pipes.

CAUTION

You are free to choose the side (left or right) for the installation of drain
hose. Please ensure the smooth flow of condensed water of the indoor
unit  during  installation.  (Carelessness  may  result  in  water  leakage.)

Be  sure  that  the
drain  hose  is  not
loosely connected
or  bent.

Be sure that the wire is not
in  contact  with  any  metal
in the wall. Please use the
protection  pipe  as  wire
passing through the hollow
part  of  the  wall  so  as  to
prevent  the  possibility  of
damaged  by  mouse.

Coolant pipes and power cord must be tied together.
The front part of the coolant pipes are at locations
marked  with  “    ”  symbol.

      Installation  of  Drain  Hose

3

Pull  this  to  the  front
during the connection
of  coolant  pipes  to
ease  task.

    Installation

Hang the indoor unit onto the mounting plate. Use the temporary
stand at the back of the indoor unit to push its lower part 15cm
forwards.

Place  the  drain  hose  through  the  hole  on  the  wall.
Insulate the connecting portion of coolant pipe with insulator.
Connect  the  power  cord.
After adjustment, the power cord and coolant pipes are placed
into  the  space  available  under  the  indoor  unit.
The  projection  of  indoor  unit  must  hook  to  the  mounting
plate.

TI

N

R

O

O

D

NI

Pipe

Power cord

Drain hose

Pipe

Rubber strap tied with great force

Pipe

below
5mm

Please bend at a small

radius to form an arc

about 15cm

Projection

Temporary stand

Hook

Power cord

Protection
pipe

Drain
hose

Connected
terminals
of coolant
pipes

Coolant pipes

Power cord

Heat insulation
pipe

Bending
upwards

Stagment
water

Drain

Stagment
water

Drain cap

Please insert
until here

Drain hose

Please insert
until here

Mounting Plate

Hook

Coolant pipe

Power Cord

Drain Hose

Protection
Pipe

Lift the body
of the unit
upwards and
then force
it downwards.

Mounting
Plate

Projection

Power line, pipe and
drain hose must be
tied together with
plastic tape.

2~5mm

Protection

pipe

Outdoor

Indoor

Seal with

putty

Sleeve of

protection

pipe

WALL

Remove the cap for drain hose installation

Drain cap

Drain hose

Condensed  water  may  leak  out  if  not  inserted  properly.

Pipe

support

Pull up the pipe after
bending downward

Transform the piping while holding down the lower portion
of  pipe-support  by  hand.

CAUITON

CAUITON

CAUITON

CAUITON

CAUITON

CAUITON

CAUITON

The drain hose can be installed from the lefe or right of the indoor unit.When installing

 the indoor unit,the mounting board must be fixed horizontally or slightly tilted down

 towards the side of drain hose.If it is tilted above the side of the drain hose,condensed

 water may overflow.

2.Push plug into the holes.

(As shown below)

3.Fix the hanger on wall with

4.1 x 32 screw.
(As shown in figure below)

1

 Hanger

2

 Screw

Wall

above 50mm

4.1 x 32 screw

Ceiling

Plug

Drain Hose

Drain cap

Openings

1.0m

Match the end of the refrigerating pipes with the 
locations marked with “

V

” symbol.

Drain hose

Drain hose

Wall hole

Wall hole

6

<

>

 : A 

E4340B

7   00mm

100mm

300mm

5m????

5

RAS-D RAC-DX24CHK

2

Drain pipe

1

9

10

20

INDOOR 

UNIT

INSTALLATION MANUAL

HITACHI SPLIT-UNIT AIR CONDITIONER

Remote controller holder

Drain cap

12

320

299

500
792

340

Содержание RAC-DX24CHK

Страница 1: ... 请确认水可否顺利的流出 不正确的安装可导致家具湿透 請使用IEC認證合格的電源線 安装场所的选定 下列几点注意事项 请先得到顾客的同意再安装 警告 本机体要安装在支撑充分 不产生振动 强固稳定的地方 注意 附近不要有热源 吹出口附近不可有障碍物 机体的上 左 右方要留有下图 印之尺寸的间隔 排水要方便 且可以和室外机配管接续在一起的地方 请勿安装在有易燃性气体泄漏及有蒸气 油烟的场所 否则有可能引发火苗 引起爆炸或造成树脂的恶化 破损 为了避免杂讯的影响 请将机体及遥控器 远离电视 收音 机等 以上 为了避免遥控器有误动作发生 请将遥控器远离高周波机器 及高出力的无线机器 如有电子点亮型的照明器具 则信号接收距离有可能会缩 短 有时还可能接收不到信号 安装高度离地板至少 警告 室外机要安装在能非常耐重的场所 否则噪音和震动会增加 注意 不要安装於易淋雨或阳光直射得到的地方 要维持通风良好...

Страница 2: ...螺母 小口径边检修 阀的控制阀 盖形螺母 气体泄漏检查 右图部份是使用验漏器来确认 冷媒有无从扩口螺母的接续部 份泄出 泄漏时请增加旋紧度以防止 泄漏 请确定使用 验漏器 出於环保的目的 设置场所变动时或拆卸时 请进行制冷剂 的回收 抽空 以强制制冷运转方式进行5分钟左右的预备运转 将小口径检修阀的阀轴朝顺时针方向旋转后关闭 在这一状态下进行 分钟的强制制冷运转 然后将大 口径检修阀的阀轴朝顺时针方向旋转后关闭 停止强制制冷运转 连接电线的连续方法 连接电线切口的细节 室内连接电线的方法 連接室內機前 要取下面框下護蓋和端子蓋 取下端子蓋後 用螺釘固定連接電線 注意 注意 端子标记 端子座护盖 1 2 3 缆线固定带 25A 警告 更换损坏的电缆时 必须使用制造商或维修人员所提供的特许电缆 制造商维修零件 连接电线需露出 的芯线 且被覆部要确实压入 然后拉拔各个电线确认有无问题 否则插入不...

Страница 3: ...ard piping use a knife to cut openings as shown in figure Then smoothen the edges of openings with a file INSTALLATION OF COOLANT PIPES AFTER CONNECTION The coolant pipes should be adjusted to fit into the hole on the wall and then ready for further connection The terminals of 2 connected pipes must be covered with insulator used for terminal connection Connect the power cord After adjustment fit ...

Страница 4: ...he vacuum pump Adapter is switched off Otherwise the nut of big diameter side will fly out WARNING Detail of Cutting the Connecting Cord If the supply cord is damaged it must be replaced by a special cord Maker s service parts available from the manufacturer or its service agent The naked part of the wire core should be 10mm fix it to the terminal tightly Then try to pull the individual wire to ch...

Отзывы: