– 104 –
1. Power does not come on (no operation)
Is AC 220-240V AC being generated
between terminals L and N on the
outdoor unit terminal board?
Is DC 35V being generated between
terminals C and D on the outdoor
unit terminal board?
Check the indoor/outdoor unit
connection cable, and correct any
defective section (wrong connection,
incomplete insertion reversed).
Check AC outlet and breaker, and
repair any defective part.
Check the outdoor unit power circuit,
and repair the defective section.
Is DC 35V being generated between
terminals C and D on the terminal
board?
Are control voltages (12V, 5V)
being generated normally?
Check according to the proper method
for checking the power circuit.
No
No
No
No
Yes
Yes
Do the air deflectors perform initial
operation when the power supply is
turned on and off?
Check the indication P.W.B.
connection cord and light receiving
unit.
No
No
Is the microcomputer reset input
(pin 7 )
?
Replace the control P.W.B
Perform final operation check.
Check the reset circuit, and repair
any defective section.
Yes
No
Is the microcomputer clock signal
10MHz at pin
10 11
being
generated normally?
Replace the microcomputer and
oscillator.
Yes
Yes
Yes
CHECKING INDOOR UNIT ELECTRICAL PARTS
Содержание RAC-50NH5
Страница 32: ... 30 CONSTRUCTION AND DIMENSIONAL DIAGRAM ...
Страница 33: ... 31 CONSTRUCTION AND DIMENSIONAL DIAGRAM FOR OUTDOOR MODEL RAC 50NH5 ...
Страница 38: ... 39 ...
Страница 39: ... 41 ...
Страница 40: ... 43 ...
Страница 41: ... 44 MODEL RAK 50NH5 RECEIVING P W B MARKING ON P W B COMPONENT SIDE SOLDERING SIDE ...
Страница 42: ... 45 MAIN P W B ...
Страница 43: ... 47 ...
Страница 44: ... 49 ...
Страница 46: ... 53 ...
Страница 47: ... 55 ...
Страница 48: ... 57 ...
Страница 49: ... 59 ...
Страница 50: ... 61 ...
Страница 52: ... 64 N O I T C N U F G N I W S O T U A ...
Страница 53: ... 65 RAK 50NH5 ...
Страница 56: ... 68 ...
Страница 58: ... 70 ...
Страница 59: ... 71 ...
Страница 60: ... 72 ...
Страница 61: ... 73 ...
Страница 62: ... 74 ...
Страница 63: ... 75 ...
Страница 64: ... 76 ...
Страница 65: ... 77 ...
Страница 66: ... 78 ...
Страница 67: ... 79 ...
Страница 68: ... 80 ...
Страница 70: ... 82 ...
Страница 71: ... 83 6 Rotor magnetic pole position detection circuit Ð Ð Ð Ð ...
Страница 72: ... 84 7 Drive Circuit ...
Страница 73: ... 85 Low speed rotation mode High speed rotation mode ...
Страница 74: ... 86 8 HIC and Peripheral Circuits ...
Страница 75: ... 87 ...
Страница 76: ... 88 1 ...
Страница 77: ... 89 2 5 ...
Страница 78: ... 90 Ð Ð Ð Ð ...
Страница 79: ... 91 9 Temperature Detection Circuit ...
Страница 80: ... 92 10 Reset Circuit Ò Ó Ò Ó Ò Ó Ð ...
Страница 81: ... 93 Ð 11 Outdoor DC Fan Motor control circuit Ð Ð ...
Страница 83: ... 95 12 Power Factor Control Circuit ...
Страница 84: ... 96 ...
Страница 86: ... 98 OTHERS Q15 A15 Q16 A16 Q17 A17 Q18 A18 Q19 A19 ...
Страница 87: ... 99 TROUBLE SHOOTING Model RAK 50NH5 RAC 50NH5 M ...
Страница 91: ... 103 SELF DIAGNOSIS LIGHTING MODE ...
Страница 97: ... 109 ...
Страница 99: ... 111 ...
Страница 100: ... 112 ...
Страница 105: ... 117 HOW TO OPERATE USING THE SERVICE SWITCH THE OUTDOOR UNIT HOW TO OPERATE THE OUTDOOR UNIT INDEPENDENTLY ...
Страница 109: ... 121 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAK 50NH5 ...
Страница 111: ... 123 ...
Страница 113: ...RAK 50NH5 RAC 50NH5 HITACHI PM NO 0302E Printed in Malaysia ...