OUTDOOR UNIT

Please mount the outdoor
unit on stable ground to
prevent vibration and
increase of noise level.

Decide the location for piping
after sorting out the different
types of pipe available.

Open the side plate by
unscrewing the screws as
shown below.

Removal Of Air From The Pipe And Gas Leakage Inspection

Gas Leakage Inspection

Please use gas leakage detector to check if leakage
occurs at the connection of Flare nut as shown on
the right.

If gas leakage occurs, further tighten the connection
to stop leakage.

3

Procedures of using Vacuum Pump for Air Removal

As shown in right figure, remove the cap
of valve core. Then, connect the charge
hose. Remove the cap of valve head.
Connect the vacuum pump adapter to
the vacuum pump and connect the
charge hose to the adapter.

Fully tighten the “Hi” shuttle of the
manifold valve and completely unscrew
the  “Lo” shuttle. Run the vacuum pump
for about 10–15 minutes, then completely
tighten the “Lo” shuttle and switch off
the vacuum pump.

2

Completely unscrew the spindle of the
service valve (at 2 places) in anti-
clockwise direction to allow the flow of
coolant (using Hexagonal Wrench key).

3

Remove the Charge hose and tighten
the cap of valve head. Check the cap’s
periphery if there is any gas leakage.
The task is then completed.

4

1

   Preparation of Pipe

1

Use a pipe cutter to cut the copper pipe.

Jagged edge will cause leakage.

Point the side to be trimmed downwards during trimming to prevent copper
chips from entering the pipe.

Before flaring, please put on the flare nut.

   Pipe Connection

2

INST

ALLA

TION OF REFRIGERA

TING PIPES AND AIR REMO

VA

L

CAUTION

!

Copper pipe

Trimming tool

Outer

Diameter (mm)

6.35

12.7

15.8

Imperial flaring tool

0.8  – 1.5mm

1.0  – 2.0mm

1.0  – 2.0mm

Rigid flaring tool

0  – 0.5mm

0  – 1.0mm

0  – 1.0mm

A (mm)

AIR REMO

V

A

L

If you cannot attach the side cover due to the connecting cord,
press the connecting cord in direction to the front panel to fix it.

Be sure that the hooks of the side cover is fixed in certainly.
Otherwise water leakage may occur and this causes short circuit
or faults.

The connecting cord should not touch to service valve and pipes.
(It becomes high temperature in heating operation.)

Checking for the electric source and the
voltage range

Before installation, the power source must be checked and necessary wiring work
must be completed. To make the       proper wiring capacity, use the wire gauges
list below for the lead-in from a pole transformer and for the wiring from a switch board
of fuse box to the outlet in consideration of the locked rotor current.

Investigate the power supply capacity and other
electrical conditions at the installation location.
Depending on the model of room air conditioner
to be installed, request the customer to make
arrangements for the necessary electrical work etc.
The electrical work includes the wiring work up
the outlet. In localities where electrical conditions
are poor, use of a voltage regulation is
recommended.

IMPORTANT

Wiring Of The Outdoor Unit

Please remove the side cover for wire connection.

!

CONNECTION OF POWER CORD

A

Die

Die

Copper pipe

Wrench

Torque
wrench

Flare nut

Lo

Hi

Meter showing pressure

Manifold valve

Vacuum pump

Charge
hose

When pumping starts, slightly loosen
the flare nut to check of air sucked in.
Then tighten the flare nut.

When the meter reaches –101KPa (–76cmHg)
during pumping, fully tighten the shuttle.

The body of
service valve

Cap of
valve core

Hexagonal
Wrench Key

Cap of valve head

Cap of valve head

Please be careful when bending the copper pipe.

Screw in manually while adjusting the center. After that, use of torque wrench to
tighten the connection.

Please face this side
(suction side) of the
unit to the wall.

Please
remove
side cover
when
connecting
the piping
and
connecting
cord.

Pull
downward

Earth terminal

B

A

Wiring Of The Indoor Unit

For wire connection of the Indoor unit, you need to remove
electrical cover.

Method to remove electrical cover

CAUTION

!

Please make sure to remove
all spacers inside the unit.

Open the Top, Back and
Side cover of the unit.

Pull out the spacers inside.
(Spacers are only for
transportation purpose).
If not remove, vibration and
noise will occur.

Top cover

FINAL ST

A

GE OF INST

ALLA

TION

Insulation And Maintenance Of Pipe Connection

1

The connected terminals should be completed sealed with
heat insulator and then tied up with rubber strap.

Please tie the pipe and power line together with vinly tape as
shown in the figure showing the installation of Indoor and
Outdoor units. Then fix their position with holders.

To enchance the heat insulation and to prevent water
condensation, please cover the outdoor part of the drain hose
and pipe with insulation pipe.

Completely seal any gap with putty.

Power Source

CAUTION

!

Please use a new socket. Accident may occur due to the
use of old socket because of poor contact.

Please plug in and then remove the plug for 2 – 3 times.
This is to ensure that the plug is completely plugged into
the socket.

Keep additional length for the power cord and do not render
the plug under external force as this may cause poor
contact.

Do not fix the power cord with U-shape nail.

Insulation material for pipe connection

Sleeve of
protection pipe

Putty

Outer

dia.of pipe

6.35 (1/4")

12.7 (1/2”)

15.88 (5/8")

6.35 (1/4")

12.7 (1/2”)

15.88 (5/8")

Valve

head cap

Torque N·m

(kgf  · cm)

13.7  – 18.6 (140 – 190)

44.1  – 53.9 (450 – 550)

49  – 58.8 (500 – 600)

19.0  – 21.0 (194 ~ 214)

29.4  – 34.3 (300 – 350)

29.0  – 31.0 (296 ~ 316)

9.0 (92)

Small dia. side

Large dia. side

Small dia. side

Large dia. side

Cable length

up to 15m

up to 25m

Wire cross-section

2.5mm

2

4.0mm

2

IMPORTANT

Fuse Capacity

30A time delay fuse

WARNING

THIS APPLIANCE MUST BE EARTHED.

Procedures of Wiring

WARNING

!

Power is supplied from Outdoor Unit

L

N

D

C

B

A

D

C

B

A

Indoor Unit

Line Cord

Outdoor Unit

Connecting Cord

1.6 or 2.0

AC 220-240V

2.5

2.5

The naked part of the wire core should be 10 mm and fix it to the terminal tightly. Then try to pull the
individual wire to check if the contact is tight. Improper insertion may burn the terminal.

Be sure to use only power cables approved from the authorities in your country. For example in Germany:
Cable type: NYM 3x1.5mm

2

, (fuse = 30A time delay)

Please refer to the installation manual for wire connection to the terminals of the units. The cabling must
meet the standards of electrical installation.

There is a AC voltage of 220-240V between the L and N terminals. Therefore, before servicing, be sure
to remove the plug from the AC outlet or switch off the main switch.

Do not make any connection in the middle of the connecting cable. It may cause the wire over heated,
emit smoke and fire.

CONDENSED WATER DISPOSAL OF OUTDOOR UNIT

There are holes on the base of Outdoor unit for condensed water
to exhaust.

In order to flow condensed water to the drain, the unit is installed
on a stand or a block so that the unit is 100mm above the ground
as shown figure. Join the drain pipe to one hole.

At first insert one portion of the hook to the base (Portion A), then
pull the drain pipe in the direction shown by the arrow while inserting
the hook into the base. After installation, check whether the drain
pipe cling to the base firmly.

When using in cold region, etc.
In cold region with severe cold climate and heavy snow, water
discharged from heat exchanger freeze on the base surface and
this may affect drainage. In such a region, remove bush on the
bottom face of outdoor unit for better drainage. When using
drainpipe, consult our dealer.

Side cover

Back cover

BASE

DRAIN PIPE

A

DRAIN PIPE

BUSH

100 mm ABOVE

13

12

BUSH

11

C

D

Please use exclusive
tool

CAUTION

!

In case of removing flare nut of an indoor unit, first remove a nut
of small diameter side, or a seal cap of big diameter side will fly
out. Prevent water from entering into the piping when working.

Valve core cap

Power Source And Operation

Test

2

Power line

Control line

GRN + YEL

25mm

35mm

10mm

30mm

10mm

30mm

10mm

10mm

70mm

10mm

10mm

45mm

Indoor

Unit

GRN + YEL

Outdoor

Unit

Strip wires

WARNING

!

 

 

 

 

Insert and fix the
connecting cords
with screw.
(4 places)

Connecting
Cords.

A
B
C
D

Connect the earth wire.
(green and yellow wire)

After unscrew the band,
put the connecting cords
and fix again with screw.
(2 places)

65mm

60mm

Содержание RAC-50DH7

Страница 1: ...e unit under direct sunshine or rain Besides ventilation must be good and clear of obstruction The air blown out of the unit should not point directly to animals or plants The clearances of the unit from top left right and front are specified in figure below At least three of the above sides must be open air Be sure that the hot air blown out of the unit and noise do not disturb the neighbourhood ...

Страница 2: ...n Duct and Supply Duct 1 The return duct should be connected with the indoor through canvas ducts between inlet side of the indoor unit and ceiling of the room The supply duct should be connected with the indoor unit through canvas ducts in order to avoid abnormal sound vibration The unit is equipped with a pre drilled duct flange for the return and supply duct connection 2 Attach the vibration pr...

Страница 3: ...efer to the illustration below for detail installation Lead wires 3 strands are inserted through and fastened via a rib clip Location of wall mounting screw Lead wires connector Wires Wires Lead wires connector Wall recessed wiring installation Supplied Wall mounting screws 2 pieces to be used Inside top wiring installation Alternative Wires Wires Lead wires 3 strands Lead wires connector Wiring i...

Страница 4: ... Open the Top Back and Side cover of the unit Pull out the spacers inside Spacers are only for transportation purpose If not remove vibration and noise will occur Top cover FINAL STAGE OF INSTALLATION Insulation And Maintenance Of Pipe Connection 1 The connected terminals should be completed sealed with heat insulator and then tied up with rubber strap Please tie the pipe and power line together w...

Отзывы: