– 95 –
Is the indoor unit "timer lamp" blinking?
Yes
Yes
Yes
No
No
No
Trouble shoot according to the
self-diagnosis lighting mode.
Run the unit using the following remote controller settings:
In the cooling season, set the temperature to 16ßC in the cooling
mode.
In the heating season, set the temperature to 32ßC in the heating
mode.
Does the operation lamp light or blink?
Open the indoor unit and check the voltage
between pins Nos.1 and 3 of CN3 on the
indoor unit control P.W.B.
Normal: DC35V (32-38V)
Red
Brown
* When the unit is not in operation, the
voltage may drop to DC20V (18-23V).
(See 11-1 "Power Circuit" for details.)
Is the voltage correct?
Is the compressor running?
Check if the connecting cable
connected incorrectly? inserted
incompletely? or disconnected?
Not running
Running
Open the outdoor unit and observe the self-diagnosis
lamp (LD301). Count how many times the lamp blinks.
Blinks other than 1 time.
Blinks 1 time.
Can the unit be operated using the outdoor unit
service switch?
(See the nameplate on the outdoor unit for operating
instructions.)
Check the outdoor
electrical parts.
Check the indoor
electrical parts.
Check the refrigerating cycle.
In the event of overload limit cut or OH
thermistor temperature rise, use the
self-diagnosis memory function because
such failure may evade detection due to
ambient temperature variations or other
factors.
No
Yes
CHECKING THE INDOOR/OUTDOOR UNIT ELECTRICAL
PARTS AND REFRIGERATING
RAS_25_35_AW_087-108
2003.12.31, 10:59 AM
95
Содержание RAC-25YH4
Страница 7: ... 5 RAS_25_35_AW_001 024 2003 12 31 10 43 AM 5 ...
Страница 31: ... 29 RAS_25_35_AW_029 030_A3 2003 12 31 10 48 AM 29 ...
Страница 32: ...RAS_25_35_AW_029 030_A3 2003 12 31 10 48 AM 30 ...
Страница 34: ...RAS_25_35_AW_031 032 2003 12 31 10 49 AM 32 ...
Страница 35: ... 33 RAS_25_35_AW_033 036_A2 2003 12 31 10 51 AM 33 ...
Страница 36: ...RAS_25_35_AW_033 036_A2 2003 12 31 10 51 AM 34 ...
Страница 37: ... 35 RAS_25_35_AW_033 036_A2 2003 12 31 10 51 AM 35 ...
Страница 38: ...RAS_25_35_AW_033 036_A2 2003 12 31 10 51 AM 36 ...
Страница 42: ...RAS_25_35_AW_037 040 2003 12 31 10 53 AM 40 ...
Страница 44: ...RAS_25_35_AW_041 042_A3 2003 12 31 10 54 AM 42 ...
Страница 45: ... 43 button RAS_25_35_AW_043 044_A3 2003 12 31 10 55 AM 43 ...
Страница 46: ...RAS_25_35_AW_043 044_A3 2003 12 31 10 55 AM 44 ...
Страница 48: ...RAS_25_35_AW_045 046 2003 12 31 10 55 AM 46 ...
Страница 50: ...RAS_25_35_AW_047 054_A3 2003 12 31 10 57 AM 48 ...
Страница 52: ...RAS_25_35_AW_047 054_A3 2003 12 31 10 57 AM 50 ...
Страница 54: ...RAS_25_35_AW_047 054_A3 2003 12 31 10 57 AM 52 ...
Страница 56: ...RAS_25_35_AW_047 054_A3 2003 12 31 10 57 AM 54 ...
Страница 68: ... 66 RAS_25_35_AW_055 086 2003 12 31 10 59 AM 66 ...
Страница 69: ... 67 Fig 3 4 RAS_25_35_AW_055 086 2003 12 31 10 59 AM 67 ...
Страница 70: ... 68 RAS_25_35_AW_055 086 2003 12 31 10 59 AM 68 ...
Страница 95: ... 93 SELF DIAGNOSIS LIGHTING MODE MODEL RAC 25YH4 RAC 35YH4 RAS_25_35_AW_087 108 2003 12 31 10 59 AM 93 ...