Microcomputer
Forced cooling
switch (Test switch)
Start
Stop
Fig. 4-2
Fig. 4-1
Analog tester
Digital tester
※
In each operating mode, if the tester is reverse-connected to the CN2 terminal,
the tester indicates a value on the – (negative) side.
Tester and CN2 terminal
connection point
Operating mode
Types of testers
Cooling operation
(including forced cooling operation)
(Reference) Heating operation
⊕
terminal of tester to CN2 pin
④
⊖
terminal of tester to CN2 pin
①
The tester indicates about 80 VDC and returns
to 0 V, and indicates about 80 VDC again.
The tester indicates a large value for an instant and
returns to 0 V, and indicates a large value again.
⊕
terminal of tester to CN2 pin
①
⊖
terminal of tester to CN2 pin
④
The tester indicates about 160 VDC and returns
to 0 V, and indicates about 160 VDC again.
The tester indicates a large value for an instant and
returns to 0 V, and indicates a large value again.
1
2
3
4
R441
R442
DB2
Cooling/Heating
switching relay
(RL4)
Reversing valve
(4-way Valve) relay
(RL3)
Cooling/Heating switching relay coil (RL4)
Reversing valve (4-way Valve) relay coil (RL3)
CN2
AC230V
28
27
12V
12V
HIC
Reversing valve
(4-way Valve) on
Reversing valve
(4-way Valve) cooling/
heating switching
Cooling Lo
Heating Hi
※
Voltage measurement timing
1s
1s
1s
Reversing valve
(4-way Valve)
Reversing valve
(4-way Valve)
Compressor
ON
OFF
・
This model is equipped with a reversing valve
(4-way Valve).
・
The reversing valve (4-way Valve) "slides" the
valve in the specified direction for each
operating mode and switches the route of
refrigerant and holds the route with a built-in
permanent magnet.
・
According to an operation command from the
indoor unit microcomputer, the reversing
valve (4-way Valve) control circuit applies current to
the reversing valve (4-way Valve) coil in the
specified direction, for each operating mode and
slides the valve.
・
Just before the compressor starts operation,
the current is applied twice at the interval of 1
sec as shown in Fig. 4-1.
・
During forced cooling operation, just after the
forced cooling switch turns on, the current is
applied twice at the interval of 1 sec as shown
in Fig. 4-1.
・
When the operation stops, the position of the
valve before the stop is held.
・
Before checking the application of current to the reversing valve (4-way Valve), disconnect the connector (CN2) and measure
the resistance of both ends of the connector, to see if it is [2500
Ω
±10%]. Only when the resistance is normal, check the
application of current using the following procedures.
If the resistance is abnormal, it is caused by either; breakage of a lead wire, or failure of the reversing valve (4-way Valve).
・
The voltage, when measured by a tester during the application of current to the reversing valve (4-way Valve)
(when the voltage is measured)
※
Switches the indoor unit to the "Ion Mist operation and air cleaning operation", and keep pressing the "Test switch" of the
outdoor unit electrical part from 1 sec to below 5 sec (while the self-diagnosis lamp LED301 is on).
Afterwards, when the "Test switch" is released, the application of current starts after 1 sec elapses. (Forced cooling operation)
・
At the voltage measurement timing, when the voltage is measured with a tester, if the tester indicates the values as shown in
the table above, the circuit is functioning normally. (Each tester indicates values differently. Since it is often difficult to read
the values of a digital tester, it is recommended to measure voltage with an analog tester.)
※
Since the current is applied only twice in 1 sec, if the timing is missed, correct operations cannot be measured.
※
If the main body of the reversing valve (4-way Valve) is functioning normally, it clicks twice synchronously with the voltage
measurement timing.
If this sound is heard, the reversing valve (4-way Valve) is functioning normally.
※
If the checking of the application of current becomes abnormal, it is a failure of an electrical part.
4. Reversing valve (4-way valve) control circuit
28
29
25
Содержание RAC-25WXEN
Страница 2: ... DANGER 2 ...
Страница 6: ...SPECIFICATIONS 3 RAC 25 35WXEN SHEATHED HEATER 200W AC 230V RAC 50WXEN 6 ...
Страница 13: ...WIRING DIAGRAM MODEL RAC 25 35 50WXEN 13 ...
Страница 14: ...MODEL RAC 25 35 50WXEN 14 ...
Страница 21: ...L N 300 330 L N 6 5 37 21 2 0 1 5 8 7 23 5 7 21 21 ...
Страница 22: ...300 330 C021 C023 500 450V 16V R249 33 ACT IP CUT 30 22 ...
Страница 26: ...5 5 1 74 74 70 70 74 75 5 1 HIC P W B 40 41 42 74 70 75 26 ...
Страница 28: ...2A Fuse DC300 330V 7 1 7 28 ...
Страница 29: ...2A DC300 330V 30 60 29 ...
Страница 39: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 25 35 50WXEN 39 ...
Страница 52: ...RAC 25WXEN RAC 35WXEN RAC 50WXEN JCH WH NO 0123E 52 ...