• Carefully read through the procedures of proper installation 

before starting installation work.

• The sales agent should inform customers regarding the correct 

operation of installation.

Tools Needed For Installation Work

(Mark   is exclusive use tool for R410A) • 

ª

 

·

 Screwdriver 

• Measuring Tape • Knife • Saw • ø65mm Power Drill 
• Hexagonal Wrench Key ( 

 4mm) • Wrench (14,17,19, 

22mm)   Gas leakage Detector • Pipe Cutter • Putty 
• Vinyl Tape • Pliers • Flare Tool   Vacuum Pump Adapter    

 Manifold Valve   Charge Hose   Vacuum Pump

FOR SERVICE PERSONNEL ONLY

 7 

OUTDOOR UNIT

RAC-25NXA1
RAC-35NXA1
RAC-50NXA1

HITACHI SPLIT UNIT AIR CONDITIONER

INSTALLATION MANUAL

SAFETY PRECAUTION

•  Read the safety precautions carefully before operating the unit.
•  The contents of this section are vital to ensure safety. Please pay special attention to the following sign.

  WARNING ............. Incorrect methods of installation may cause death or serious injury.
  CAUTION .............. Improper installation may result in serious consequence.

  Make sure to connect earth line.
  This sign in the 

fi

 gures indicates prohibition.

Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of the unit 
as described in the user’s guide. Ask customers to keep this installation manual together with the instruction manual.

 WARNING

• Please request your sales agent or quali

fi

 ed technician to install your unit. Water leakage, short circuit or 

fi

 re may occur if you do the installation work 

yourself.

•  Please observe the installation stated in the installation manual during the process of installation. Improper installation may cause water leakage, electric 

shock and 

fi

 re.

•  Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may collapse and 

impose danger.

•  Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing with the electrical 

work. Use cables which are approved of

fi

 cial in your country. Be sure to use the speci

fi

 ed circuit. A short circuit and 

fi

 re may occur due to the use of low 

quality wire or improper work.

•  Be sure to use the speci

fi

 ed cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the conductors of the 

wire are inserted into the terminals to prevent the external force is being applied to the connection section of the terminal base. Improper insertion and 
loose contact may cause over-heating and 

fi

 re.

•  Please use the speci

fi

 ed components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, 

fi

 re or stronger vibration 

may occur.

•  Be sure to use the speci

fi

 ed piping set for R410A. Otherwise, this may result in broken copper pipes or faults.

•  When installing or transferring an air conditioner to another location, make sure that air other than the speci

fi

 ed refrigerant (R410A) does not enter the 

refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.

•  Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with 

fi

 re, a poisonous gas may occur.

•  After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the room, coming into 

contact with 

fi

 re in the fan-driven heater, space heater, etc., a poisonous gas may occur.

•  Unauthorized modi

fi

 cations to the air conditioner may be dangerous. If a breakdown occurs please call a quali

fi

 ed air conditioner technician or electrician. 

Improper repairs may result in water leakage, electric shock and 

fi

 re, etc.

•  Be sure to connect the earth line from the power supply wire to the outdoor unit and between the outdoor and indoor unit. Do not 

connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the telephone unit. Improper earthing may cause 
electric shocks.

•  When 

fi

 nishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe. If you remove the refrigerant pipe while 

the compressor is operating and the service valve is released, air is sucked and a pressure in the freezing cycle system will build up steeply, causing 
an explosion or injury.

•  When installing the unit, be sure to install the refrigerant pipe before starting the compressor. 
  If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the pressure level of the refrigeration 

cycle may increase abnormally which could result in a rupture and injury.

 CAUTION

• A circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the outdoor unit. In case of other 

installations a main switch with a contact gap or more than 3mm has to be installed. Without a circuit breaker, the danger of electric shock exists.

• Do not install the unit near a location where there is 

fl

 ammable gas. The outdoor unit may catch 

fi

 re if 

fl

 ammable gas leaks around it.

• Please ensure smooth 

fl

 ow of water when installing the drain hose. Improper installing may wet your furniture.

• An IEC approved power cord should be used. Power cord type: NYM.

Names of Components

THE CHOICE OF MOUNTING SITE

  (Please note the following matters and obtain permission from customer before installation.)

  No.   

           Item 

Qty

 

1

 Bush 

 

1

 

 

 

  (RAC-50NXA1)  2

   Drain 

Pipe

 

2

   

 

 

1

OUTDOOR UNIT

 WARNING

• The outdoor unit must be mounted at a location which can support heavy weight. Otherwise, noise and vibration will increase.

 CAUTION

• Do not expose the unit under direct sunshine or rain. Besides, ventilation must be good and clear of obstruction.
• The air blown out of the unit should not point directly to animals or plants.
• The clearances of the unit from top, left, right and front are speci

fi

 ed in 

fi

 gure below. At least two of the above sides must be open air.

• Be sure that the hot air blown out of the unit and noise do not disturb the neighbourhood.
• Do not install at a location where there is 

fl

 ammable gas, steam, oil and smoke.

• The location must be convenient for water drainage.
• Place the outdoor unit and its connecting cord at least 1m away from the antenna or signal line of television, radio or telephone. This 

is to avoid noise interference.

Condensed water disposal of outdoor unit

•  There is holes on the base of outdoor unit for condensed water to exhaust.
•  In order to 

fl

 ow condensed water to the drain, the unit is installed on a stand or a block so that the unit is 100mm above 

the ground as shown 

fi

 gure. Join the drain pipe to one hole.

•  Cover the drain hole with a bush. To install the bush, put it on the drain hole as shown in the 

fi

 gure and press the both 

sides of the bush to 

fi

 t into the hole. After installation, check whether the drain pipe and bush cling to the base 

fi

 rmly.

  Please mount the outdoor unit on stable ground to prevent vibration and increase of noise level.

  Decide the location for piping after sorting out the different types of pipe available.

  When removing side cover, please pull the handle after undoing the hook by pulling it downward. Reinstall the side 

cover in reverse order of the removal.

Pull downward

Please face this side (suction 
side) of the unit to the wall.

Please remove side cover 
when connecting the piping 
and connecting cord.

•  Install the outdoor unit horizontally and make sure that condensate drains away.
•  In case of using in cold weather area 
  Especially when there are heavy snows in cold weather area, condensed water freezes on the base and may not drain. 

In this case, please remove the bush and the drain pipe at the bottom of the unit (left and centre near discharge portion 
of air, each 1 place) to restore smooth drainage. Ensure that the distance from the drain hole to the ground is 250mm 
or more.

RAC-25NXA1 / RAC-35NXA1

RAC-50NXA1

RAC-50NXA1

•  Do not touch the suction port, bottom surface, or aluminium 

fi

 n of the outdoor unit.

•  Failure to do so may cause an injury.

 CAUTION

Above 100mm

Base

Outer diameter: 16mm

Drain hole

Drain pipe

Bush

Above 100mm

Base

Outer diameter: 16mm

Drain hole

Drain pipe

Bush

Cover

AIR REMOV

AL

INST

ALLA

TION OF REFRIGERA

TING PIPES 

AND 

AIR REMOV

AL

Procedures of using vacuum pump for air removal

A

1. Preparation of pipe

 

•  Use a pipe cutter to cut the copper pipe and remove burr.

Die

Copper pipe

Die

Trimming tool

Copper pipe

2. Pipe connection

Flare nut

Wrench

Torque wrench

Remove the cap of valve core. Then, connect 
the charge hose. Remove the cap of valve 
head. Connect the vacuum pump adapter to the 
vacuum pump and connect the charge hose to the 
adapter.

Fully tighter the “Hi” shuttle of the manifold valve 
and completely unscrew the “Lo” shuttle. Run 
the vacuum pump for about 10-15 minutes, then 
completely tighten the “Lo” shuttle and switch off 
the vacuum pump.
•  Loosen the spindle of the service valve with 

small diameter by 1/4 turn and tighten the spindle 
immediately after 5 to 6 seconds.

•  Remove the charging hose from the service 

valve.

Completely unscrew the spindle of the service valve 
(at 2 places) in anticlockwise direction to allow the 

fl

 ow of refrigerant (using Hexagonal Wrench key).

Tighten the cap of valve head. Check the cap’s 
periphery if there is any gas leakage. The task is 
then completed.

1

2

3

4

Please use gas leakage detector to check if leakage occurs at connection of Flare nut as shown 
on the right.

If gas leakage occurs, further tighten the connection to stop leakage.

Cap of valve core

Cap of valve head

Hexagonal wrench key

3. Remove of air from the pipe and gas leakage inspection

Gas leakage inspection

 

 

 Outer diameter 

Torque N·m

 

 

of pipe (ø) 

(kgf·cm)

Small diameter side 

6.35 (1/4”) 

13.7 – 18.6 (140 – 190)

Large diameter side

 

9.52 (3/8”) 

34.3 – 44.1 (350 – 450)

 

 

12.7 (1/2”) 

44.1 – 53.9 (450 – 550)

  

Small diameter side 

6.35 (1/4”) 

19.6 – 24.5 (200 – 250)

Valve head cap 

Large diameter side

 

9.52 (3/8”) 

19.6 – 24.5 (200 – 250)

 

 

12.7 (1/2”) 

29.4 – 34.3 (300 – 350)

 

Valve core cap 

 

12.3 – 15.7 (125 – 160)

•  Before 

fl

 aring, please put on the 

fl

 are nut.

•  Please use exclusive tool for refrigerant R410A.

Outer diameter (ø) 

A (mm) Rigid Flaring Tool

 

 

For R410A tool 

For R22 tool

 

6.35 (1/4”) 

0 – 0.5 

1.0

 

9.52 (3/8”) 

0 – 0.5 

1.0

 

12.7 (1/2”) 

0 – 0.5 

1.0

•  Please be careful when bending the copper pipe.
•  Screw in manually while adjusting the center. 

After that, use a torque wrench to tighten the connection.

CONNECTION OF POWER CORD

Procedures of wiring

Connecting cord

Outdoor unit

Indoor unit

AC 220–240V

1ø 50Hz

 

WARNING

THIS APPLIANCE MUST BE EARTHED.

 

WARNING

•  The naked part of the wire core should be 10mm 

fi

 x it to the terminal tightly. Then try to pull the individual wire to 

check if the contact is tight. Improper insertion may burn the terminal.

•  Be sure to use only wire speci

fi

 ed for the use of air-conditioner.

•  Please refer to the manual for wire connection and the wiring technique should meet the standard of the electrical 

installation.

•  Leave some space in the connecting cord for maintenance purpose and be sure to secure it with the 

cord band.

•  Secure the connecting cord along the coated part of the wire using the cord band. Do not exert pressure 

on the wire as this may cause overheating or 

fi

 re.

Wiring of the outdoor unit

Please remove the side cover for wire connection.

 

WARNING

•  If you cannot attach the side plate due to the connection cord, please press the connecting cord in the direction to the front 

panel to 

fi

 x it.

•  Be sure that the hooks of the side cover 

fi

 xed in certainly. Otherwise water leakage may occur and this causes short circuit 

or faults.

•  The connecting cord should not touch to service valve and pipes. (It becomes high temperature in heating operation.)

•  Investigate the power supply capacity and other electrical conditions at the installing location.
•  Depending on the model of room air conditioner to be installed, request the customer to make arrangements for the necessary 

electrical work etc.

•  The electrical work includes the wiring work up the outdoor unit. In localities where electrical conditions are poor, use of a 

voltage regulation is recommended.

•  Install outdoor for the room air conditioner within the reaching range of the line cord.

IMPORTANT

Checking for the electric source and the voltage range

•  Before installation, the power source must be checked and necessary wiring work must be completed. To make the wiring 

capacity proper, use the wire gauge list below for the wiring from house distribution fuse box to the outdoor unit in consideration 
of the blocked rotor current.

IMPORTANT

When putting two connecting cords through the band.

Screw

Connecting cord

Insulating plate

Cord band

Earth terminal

RAC-25NXA1 / RAC-35NXA1 / RAC-50NXA1

When the meter reaches -101KPa 
(-76cmHg) during pumping fully 
tighten the shuttle.

Meter showing pressure

Closed

R410A Manifold valve

Vacuum pump

Vacuum pump adapter

Valve

Charge hose

Valve

When pumping starts, slightly loosen 
the 

fl

 are nut to check of air sucked in. 

Then tighten the 

fl

 are nut.

Cap of valve head

The body of service valve

Detail of cutting the connecting cord

• Outdoor unit

RAC-25NXA1/RAC-35NXA1

RAC-50NXA1

Cover

Earth terminal

Dimensions of Mounting Stand of the Outdoor Unit

Mounting Stand

•  Remove burr and jagged edge will cause leakage.
•  Point the side to be trimmed downwards during trimming to prevent copper chips from entering the pipe.

 CAUTION

•  In case of removing 

fl

 are nut of a indoor unit, 

fi

 rst remove a nut of small diameter side, or a seal cap of big diameter 

side will 

fl

 y out. Free from water into the piping when working.

•  Be sure to tighten the 

fl

 are nut to the spec

fi

 ed torque with a torque wrench. If the 

fl

 are nut is overtightened, the nut may 

be split after a long period has passed, and may cause a refrigerant leak.

 CAUTION

Fuse Capacity

16A time delay fuse

(unit : mm)

RAC-25NXA1/RAC-35NXA1

RAC-50NXA1

above 200mm

*

 A

above 100mm

above 200mm

( )

above 50 mm when 
installed on the 
ceiling of balcony

*

 B

(This 

fi

 gure is RAC-50NXA1)

•  The refrigerating machine oil is easily affected by moisture. Use caution 

to prevent water from entering the cycle.

• The difference in height between the indoor and outdoor unit should 

be kept below 10m. 

• The connecting pipe, no matter big or small, should all be insulated 

with insulation pipe and then wrapped with vinyl tape. (The insulator 
will deteriorate if it is not wrapped with tape.)

Inner diameter ø16mm

The connection of insulated drain hose.

Please use insulated drain hose for the indoor 
piping (commer cial product).

Maximum pipe length 20m

C, D

L, N

Green + Yellow

Green + Yellow

Strip wires

RAC-25NXA1 / RAC-35NXA1 / RAC-50NXA1

For outdoor unit installation, allow at least 2 sides of 
space around the unit to ensure ventilation 

fl

 ue.

RAC-25NXA1 

RAC-35NXA1

RAC-50NXA1

A

B

above 300mm

above 50mm

above 300mm

above 50mm

above 200mm

above 50mm

*

 give clearance as wide as possible

FINAL

 ST

AGE OF INST

ALLA

TION

1. Operation test

•  Please ensure that the air conditioner is in normal operating condition during the operation test.
•  Explain to your customer the proper operation procedures as described in the user’s manual.
•  If the indoor unit does not operate, check to see that the connections are correct.
•  Turn on the lamp in the room where the indoor unit is installed and check the remote controller for normal operation.

Insulation and maintenance of pipe connection

•  The connected terminals should be completed sealed with heat insulator and 

then tied up with rubber strap.

•  Please tie the pipe and power line together with vinyl tape as shown in the 

fi

 gure showing the installation of Indoor and outdoor units. Then 

fi

 x their position 

with holders.

•  To enhance the heat insulation and to prevent water condensation, please 

cover the outdoor part of the drain hose and pipe with insulation pipe.

•  Completely seal any gap with putty.

Force-cooling operation

•  When the service switch of the outdoor unit is pressed for 1 or more seconds, the force-cooling operation starts. Use 

this mode when performing the failure diagnosis or collecting refrigerant into the outdoor unit.

Sleeve of 
protection pipe

Putty

Putty

OUTSIDE    INSIDE

Screw

Cover

Service switch (If the switch is pressed 
for more than 1 second, the force-
cooling operation starts. If the switch 
is pressed for additional more than 1 
second, the operation stops.)

RAC-25NXA1 / RAC-35NXA1

RAC-50NXA1

 CAUTION

Do not operate the unit for more than 5 minutes while the spindle of the service valve is closed.

 

Wire length 

Wire gauge

 

up to 6m 

1.5mm

2

 up 

to 

15m  2.5mm

2

 up 

to 

20m  4.0mm

2

 

up to 6m 

1.5mm

2

 

up to 20m 

2.5mm

2

L, N

C, D

1_RAC-25_35_50NX2_Inst_Out_EN.indd   1

1_RAC-25_35_50

_Inst_Out_EN.indd   1

5/13/10   4:43:41 PM

5/13/10   4:43:41 PM

Please face this side (suction 
side) of the unit to the wall.

Please remove side cover 
when connecting the piping 
and connecting cord.

Pull downward

RAC-25NXA1/RAC-35NXA1

(RAC-25NXA1/RAC-35NXA1)

12

320

299

500
792

340

Screw

Cover

Service switch (If the switch is pressed 
for more than 1 second, the force-
cooling operation starts. If the switch 
is pressed for additional more than 1 
second, the operation stops.)

NXA1

Отзывы: