How to run the product with the outdoor unit test switch
CH
TEST SWIT
RAC-18/25WP
1. Turn on the outdoor terminal boards L and N (220-230 V AC).
If the indoor electrical parts is out of order and if you wish to run the outdoor unit
If you release your finger from the test switch within 1 sec to 5 sec after pressing the switch, the forced cooling operation starts.
※
(If you press the test switch for 5
or longer, the self-check diagnosis starts. In this case, turn the power off and start the procedure from 1 again.)
※
(For the initialization of the expansion valve, it may take 1 min until the operation starts.)
after the power turns on), confirm that the "LD301" changes to blinking 9 times (communication error).
2. Confirm that the "LD301" blinks once from the terminal side of the outdoor unit. Afterwards (when about 30 sec elapses
3. When the "LD301" is blinks 9 times, if you press the test switch, the "LD301" lights up.
4. When you press the test switch again for 1 sec or longer, the unit stops the operation.
sec
C
39
Содержание RAC-18WPC
Страница 2: ... DANGER 2 ...
Страница 11: ...WIRING DIAGRAM RAC 18 25WPC 11 ...
Страница 12: ...MODEL RA C 18 25WPC 12 ...
Страница 14: ...MODEL RAC 18 25WPC Indoor unit Indoor unit 14 ...
Страница 16: ...L N 300 330 Main parts L N C021 C022 375 420V R 15 AC 18 25WPC DESCRIPTION OF MAIN CIRCUIT OPERATION 16 ...
Страница 20: ...5 5 1 10 11 12 74 74 70 70 74 75 5 1 HIC P W B 74 70 75 20 ...
Страница 21: ...6 Electric expansion valve circuit 48 47 46 45 13 14 15 16 4 3 2 1 68 67 66 65 5 14 12 10 7 6 1 8 6 1 6 2 21 ...
Страница 22: ...2A Fuse DC300 330V 7 7 1 22 ...
Страница 23: ...2A DC300 330V 23 ...
Страница 32: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 18 25WPC 32 ...
Страница 43: ...HITACHI HHAW NO 0 E RAC 18WPC RAC 25WPC 10 0 0 43 ...